Kogan KAVWAC2KYA VERTICAL WINDOW AIR CONDITIONER User guide

Category
Mobile air conditioners
Type
User guide
VERTICAL WINDOW AIR
CONDITIONER
(1.75KW, COOLING ONLY)
KAVWAC2KYA
Warnings
Any person who is involved with working on or breaking into a refrigerant circuit
should hold a currently valid certificate from an industry-accredited assessment
authority. This authorises their competence to handle refrigerants safety by an
industry recognised assessment specification.
Dispose the appliance packaging responsibly.
The appliance shall be stored in a well-ventilated area. The size of the area
corresponds to the room area specified for operating the appliance.
Store the appliance safely to prevent any mechanical damage.
Ensure the following regarding the refrigerant pipes:
o The installation of pipework shall be kept to a minimum.
o The pipework shall be protected from physical damage and, in the case
of flammable refrigerants, shall not be installed in an unventilated space.
o Compliance with national gas regulations shall be observed.
o The mechanical connections shall be accessible for maintenance
purposes.
o For appliances containing flammable refrigerants, the minimum floor
area of the room shall be mentioned in the form of a table or a single
figure without reference to a formula.
Keep any required ventilation openings clear of obstruction.
Ensure ducts connected to the appliance does not contain a potential ignition
source.
When the portable air conditioner or dehumidifier is turned on, the fan can work
continuously under normal conditions to provide the minimum air volume of
100m3/h even when the compressor is closed due to the temperature controller.
Do not pierce or burn the appliance.
Use only implements recommended by the manufacturer for defrosting or
cleaning.
Do not perforate any of the components in the refrigerant circuit. Refrigerant gas
may be odourless.
Maintenance and repairs requiring the assistance of other qualified personnel must
be carried out under the supervision of specialists in the use of inflammable
refrigerants.
SAFETY & WARNINGS
Appliance with R290 Refrigerant Gas
Caution: Risk of fire
DANGER: It is hazardous for anyone other than an authorised service person to
service this appliance. In Queensland, the authorised service person MUST hold a
Gas Work Authorisation for hydrocarbon refrigerants to carry out servicing or
repairs which involve the removal of covers.
This appliance contains approximately 150 grams of R290 refrigerant gas.
The appliance shall be installed, operated, and stored in a room with a floor area
larger than 4 metres square.
Precautions
This appliance is not intended for use by persons (including children) with weak
physical, sensory, or mental abilities or lack of experience and knowledge unless
their use is supervised or instructed by personnel responsible for their safety.
Supervise children to ensure they do not play with this appliance.
Install the appliance correctly to ensure it is at a minimum allowable distance from
the adjacent structures. See the Installation section of this user guide.
Follow the correct wiring connection type when operating or repairing.
Do not use the appliance in an explosion-hazardous room.
Do not use the appliance in a corrosive environment.
Keep the appliance upright and stable.
Allow the appliance to dry after wet cleaning. Do not operate when wet.
Do not use the appliance with wet hands.
Do not spray water directly on the appliance.
Never insert any objects or limbs into the appliance.
Do not cover or transport the appliance during operation.
Do not sit on the appliance.
Do not leave the device unattended during operation.
Electrical connections must meet technical requirements.
Note: Refer to the rating plate on your appliance to know the type of
refrigerant gas used.
Insert the power plug into a properly secured power outlet.
When selecting an extension cord for a power cord, pay attention to the power
input of the device, the cable length, and the intended use. Fully extend the
expansion cable. Avoid electrical overload
Before repairing the appliance, unplug the power plug from the electrical outlet.
Hold the power plug when doing this; do not pull on the cord.
When not using the appliance, turn off the device and unplug the power cord from
the power outlet.
If you notice damage to the power plug or power cord, cease the use of the
appliance and contact Kogan.com
When placing the appliance, pay attention to the minimum distance from walls
and other objects. For storage and operating conditions, see the Cleaning and
Care section of this user guide.
Ensure that air inlets and outlets are not blocked.
Make sure the suction side is free of dust and loose objects
Do not remove any safety signs, stickers, or labels from the device.
Drain the collected condensate water before transportation and storage. Do not
drink it as it is harmful to health.
Air Conditioner
1
Front Panel
2
Vertical Blade (Auto Swing)
3
Level Blade (Manually Swing)
4
Filter
5
Display Panel
6
Power Line
7
Indoor Water Hole
8
Back Panel
9
Outdoor Air Inlet
10
Outdoor Water Hole
11
Outdoor Air Outlet
12
Standard Frame
13
Chassis
OVERVIEW
Air Conditioner Window Frame
Protect Plate
Seal Sponge
Inside Frame
Dead Plate
Fix Screw
Standard Frame
Sliding Plate
Unit Fixed Screw
Unit Locker
Down Sliding Plate
Before Installation
To avoid damage, place the unit in an upright position for at least 24 hours before
installation.
Make sure that the air outlet and air inlet are never blocked.
Operate the unit on a horizontal surface to avoid water leakage.
Air Conditioner Window Frame Installation Requirements
The height of the window should be higher than 85cm.
The window should have a groove.
If there is no groove (e.g. wood window) contact professional people to install.
The window height should be shorter than the max height of the frame to avoid
the appliance from falling.
INSTALLATION
The following instruments are required:
o Tape
o Cross screwdriver
o Scissor
Power supply details:
o Connect to a power supply directly and do not use an extension cord.
o Ensure the plug is connected.
Sketch the map of the frame for installation:
Installation Steps
Step 1: Choose the installation location.
Step 2: Install the air conditioner window frame.
Sliding
Locked
Screw
Standard Frame
Inside Frame
Unit Location
Fixed Screw
Protect Plate
First Groove
Inside
Outside
Note: Cover the window completely with the Standard Frame.
Note: To install the air conditioner, wait for two hours after delivery to
keep the refrigerant gas stable.
1. Open the window from left or right.
2. Ensure the bottom of the Inside Frame is inserted at the first groove (as shown
in the image I).
3. Stretch the Inside Frame and ensure it is aligned to the groove of the window
(II).
4. Slide the Inside Frame to the side of the window (III).
5. Use two screws to lock the Inside Frame. Position the protector between the
top and bottom and tighten the screws (IV).
6. Use a suitable sponge to seal the remaining gaps (V).
Step 3: Install the air conditioner.
1. Unscrew the standard frame.
2. There are two holes with a locker on the backside of the air conditioner, push
one time to lock.
Unit Lock Screw
Unit Locker
Frame inside
the rubber
Back Side
Note: Ensure the air conditioner frame installation is stable.
3. The grey bulge part is a Standard Frame. The Standard Frame bottom should
be locked completely between the sponge and inside groove.
4. Tighten the Unit Fixed Screw to lock the air conditioner
Step 4: Disassemble the air conditioner
1. Follow the air condition installation steps in the reverse order to disassemble
the air conditioner.
2. Push the Unit Locker to left and hold the air conditioner to avoid dropping.
Unit Fixed
Screw
Note: Be careful when disassembling the air condition. Do not drop the
air conditioner.
Note: Ensure the air condition is installed securely.
Operation Panel and Remote Control
1 AUTO Press this button to operate air conditioner in the automatic mode.
2 POWER Press this button to turn on the air conditioner.
3 CHILD LOCK Press this button to lock operation panel.
4 TIMER Press this button to turn off or turn on the timer.
5 FAN Press this button to change the fan speed (high, middle, or low).
6 UP/DOWN Press to increase or decrease the temperature and timer settings.
7 SWING Press this button to turn on or off the swing function.
8 SLEEP Press this button to put the air conditioner to sleep mode.
9 MODE Press this button to switch between auto, cooling, fan, and dry
modes.
OPERATION
Time setting
Standby State
1. Press the TIMER button to start the timer. The timing range is 0-24 hours.
2. Press the UP and DOWN keys to set the time. Before 6 hours, every up or down
adjustment is 0.5 hours, after 6 hours, every up or down adjustment are 1 hour, and
the corresponding timer status indicator lights up.
Power-on State
1. Press the TIMER button to set the timer shutdown.
2. Press the UP and DOWN keys to set the time. Before 6 hours, every up or down
adjustment is 0.5 hours, after 6 hours, every up or down adjustment are 1 hour, and
the corresponding timer status indicator lights up.
Working Mode Operation
Cooling mode:
1. Press the MODE button to select the cooling mode during the power-on state. At
this point, the corresponding indicator lights up.
2. Press the UP and DOWN keys to set the appropriate temperature. The setting
range is 16~30°C. Each time you press the up or down button, the temperature will
rise or fall by 1°C.
3. Press the FAN button to select the appropriate fan speed and you can cycle
through low, mid, and high wind.
4. Press the SWING button to turn the swing function on or off.
Dehumidify mode:
1. Press the MODE button to select the dehumidification mode during power-on
state. The corresponding indicator lights up.
2. Wind speed is not adjustable.
3. Press the SWING button to turn the swing function on or off
Fan mode:
1. Press the MODE button to select the fan mode during power-on stage. The
corresponding indicator lights up.
2. Press the FAN button to select the appropriate fan speed and you can cycle
through the low wind, mid and high speed.
3. The temperature is not adjustable.
4. Press the SWING button to turn the swing function on or off.
Automatic mode:
1. Press the MODE key in the power-on state or press the AUTO button to select the
automatic mode. The corresponding indicator lights up.
2. The automatic mode operates in the cooling mode. The default setting
temperature is 24°C. The setting range is 16~30C and the temperature can be
adjusted within this range.
3. The fan speed will adjust automatically to the set temperature and the ambient
temperature and the speed is not adjustable.
4. The automatic mode swing function is enabled by default and the swing function
can be turned off or on by the SWING button.
Sleep mode:
1. Press the SLEEP button to select the sleep mode in the power-on state. The
corresponding indicator lights up. In this mode, it operates according to the cooling
function.
2. The default setting temperature is 26°C. The setting range is 16~30C and the
temperature can be adjusted within this range.
3. The fan speed is set to low and is not adjustable.
4. Press the swing key to turn off and turn on the swing function.
5. After entering sleep mode, the indicator light turns dark and the set temperature
increases by 2°C for two hours. After 8 hours of sleep mode, the air conditioner
shuts down.
Child lock function:
1. Press the CHILD LOCK button for 3 seconds to lock the operation panel. Press this
button again for 3 seconds to unlock.
Note: When the water level indicator shows water is full, the machine will stop
working and you should drain the water. After draining, the machine can be
restarted. See the Cleaning and Care section of this user guide.
Repairing Appliances Containing R290
1. Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety
checks are necessary to ensure that the risk of ignition is minimised. For repair to
the refrigerating system, the following precaution shall be completed prior to
conducting work on the system.
2. Work procedure
Work shall be undertaken under a controlled procedure to minimise the risk of a
flammable gas or vapour being present while the work is being performed.
3. General work area
All maintenance staff and others working in the local area shall be instructed on
the nature of work being carried out. Work in confined spaces shall be avoided.
4. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and
during work, to ensure the technician is aware of potentially toxic or flammable
atmospheres. Ensure that the leak detection equipment being used is suitable for
use with all applicable refrigerants, i.e. non-sparking, adequately sealed or
intrinsically safe.
5. Presence of fire extinguisher
If any hot work is to be conducted on the refrigerating equipment or any
associated parts, appropriate fire extinguishing equipment shall be available to
hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
6. No ignition sources
No person carrying out work in relation to a refrigerating system which involves
exposing any pipe work shall use any sources of ignition in such a manner that it
may lead to the risk of fire or explosion. All possible ignition sources, including
cigarette smoking, should be kept sufficiently far away from the site of installation,
repairing, removing and disposal, during which refrigerant can possibly be released
to the surrounding space. Prior to work taking place, the area around the
equipment is to be surveyed to make sure that there are no flammable hazards or
ignition risks. “No Smoking” signs shall be displayed.
7. Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation shall
continue during the period that the work is carried out. The ventilation should
safely disperse any released refrigerant and preferably expel it externally into the
atmosphere.
8. Checks to the refrigerating equipment
Where electrical components are being changed, they shall be fit for the purpose
and to the correct specification. At all times, the manufacturer’s maintenance and
service guidelines shall be followed. If in doubt, consult the manufacturer’s
technical department for assistance.
REPAIR
The following checks shall be applied to installations using flammable refrigerants:
The actual refrigerant charge is in accordance with the room size within which the
refrigerant containing parts are installed.
The ventilation machinery and outlets are operating adequately and are not
obstructed.
If an indirect refrigerating circuit is being used, the secondary circuit shall be
checked for the presence of refrigerant.
Marking to the equipment continues to be visible and legible. Markings and signs
that are illegible shall be corrected.
Refrigerating pipe or components are installed in a position where they are unlikely
to be exposed to any substance which may corrode refrigerant containing
components, unless the components are constructed of materials which are
inherently resistant to being corroded or are suitably protected against being so
corroded.
9. Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures. If a fault exists that could
compromise safety, then no electrical supply shall be connected to the circuit until
it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is
necessary to continue operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment, so all parties are advised.
Initial safety checks shall include:
That capacitor is discharged: this shall be done safely to avoid the possibility
of sparking,
That no live electrical components and wiring are exposed while charging,
recovering, or purging the system,
That there is continuity of earth bonding.
10. Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected
from the equipment being worked upon before any removal of sealed covers, etc. If
it is necessary to have an electrical supply to equipment during servicing, then a
permanently operating form of leak detection shall be located at the most critical
point to warn of a potentially hazardous situation.
Particular attention shall be paid to the following to ensure that by working on
electrical components, the casing is not altered in such a way that the level of
protection is affected. This shall include damage to cables, an excessive number of
connections, terminals not made to original specification, damage to seals,
incorrect fitting of glands, etc.
Ensure that the apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded to the point that they no
longer serve the purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be by the manufacturer’s specifications.
11. Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without
ensuring that this will not exceed the permissible voltage and currently permitted
for the equipment in use.
Intrinsically safe components are the only types that can be worked on while living
in the presence of a flammable atmosphere. The test apparatus shall be at the
correct rating.
Replace components only with parts specified by the manufacturer. Other parts
may result in the ignition of refrigerant in the atmosphere from a leak.
12. Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure,
vibration, sharp edges, or any other adverse environmental effects. The check shall
also consider the effects of ageing or continual vibration from sources such as
compressors or fans.
13. Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching
for or detection of refrigerant leaks. A halide torch (or any other detector using a
naked flame) shall not be used.
14. Removal and evacuation
When breaking into the refrigerant circuit to make repairs or for any other
purpose – conventional procedures shall be used. However, for flammable
refrigerants, best practice must be followed since flammability is a consideration.
The following procedure shall be adhered to:
Remove refrigerant
Purge the circuit with inert gas
Evacuate
Purge with inert gas
Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. For
appliances containing flammable refrigerants, the system shall be purged with
oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This
process may need to be repeated several times. Compressed air or oxygen shall
not be used for purging refrigerant systems.
For appliances containing flammable refrigerants, refrigerants purging shall be
achieved by breaking the vacuum in the system with oxygen-free nitrogen and
continuing to fill until the working pressure is achieved, then venting to atmosphere
and finally pulling down to a vacuum. This process shall be repeated until no
refrigerant is within the system. When the final oxygen-free nitrogen charge is
used, the system shall be vented down to atmospheric pressure to enable work to
take place. This operation is vital if brazing operations on the pipework are to take
place.
Ensure that the outlet for the vacuum pump is not close to any potential ignition
sources and that ventilation is available.
15. Charging procedures
In addition to conventional charging procedures, the following requirements shall
be followed.
Ensure that contamination of different refrigerants does not occur when using
charging equipment. Hoses or lines shall be as short as possible to minimise
the amount of refrigerant contained in them.
Cylinders shall be kept in an appropriate position according to the instructions.
Ensure that the refrigerating system is earthed before charging the system
with refrigerant.
Label the system when charging is complete (if not already).
Extreme care shall be taken not to overfill the refrigerating system.
Before recharging the system, it shall be pressure-tested with the appropriate
purging gas. The system shall be leak-tested on completion of charging but before
commissioning. A follow-up leak test shall be carried out before leaving the site.
16. Decommissioning
Before carrying out this procedure, the technician must be completely familiar with
the equipment and all its detail. It is recommended good practice that all
refrigerants are recovered safely. Before the task being carried out, an oil and
refrigerant sample shall be taken in case analysis is required before re-use of
recovered refrigerant. Electrical power must be available before the task is
commenced.
a) Become familiar with the equipment and its operation.
b) Isolate the system electrically.
c) Before attempting the procedure, ensure that:
Mechanical handling equipment is available, if required, for handling
refrigerant cylinders.
All personal protective equipment is available and being used correctly.
The recovery process is always supervised by a competent person.
Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down the refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be
removed from various parts of the system.
f) Make sure that the cylinder is situated on the scales before recovery takes
place.
g) Start the recovery machine and operate by instructions.
h) Do not overfill cylinders (no more than 80% volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even
temporarily.
j) When the cylinders have been filled correctly and the process completed,
make sure that the cylinders and the equipment are removed from the site
promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigerating system
unless it has been cleaned and checked.
17. Labelling
Equipment shall be labelled stating that it has been de-commissioned and
emptied of refrigerant. The label shall be dated and signed. For appliances
containing flammable refrigerants, ensure that there are labels on the equipment
stating the equipment contains flammable refrigerant.
18. Recovery
When removing refrigerant from a system, either for servicing or decommissioning,
it is recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed. Ensure that the correct number of
cylinders for holding the total system charge is available. All cylinders to be used
are designated for the recovered refrigerant and labelled for that refrigerant (i.e.
special cylinders for the recovery of refrigerant). Cylinders shall be complete with a
pressure-relief valve and associated shut-off valves in good working order. Empty
recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions
concerning the equipment that is at hand and shall be suitable for the recovery of
all appropriate refrigerants including, when applicable, flammable refrigerants.
Also, a set of calibrated weighing scales shall be available and in good working
order. Hoses shall be complete with leak-free disconnect couplings and in good
condition. Before using the recovery machine, check that it is in satisfactory
working order, has been properly maintained and that any associated electrical
components are sealed to prevent ignition in the event of a refrigerant release.
Consult the manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct
recovery cylinder and the relevant waste transfer note arranged. Do not mix
refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been
evacuated to an acceptable level to make certain that flammable refrigerant does
not remain within the lubricant. The evacuation process shall be carried out before
returning the compressor to the suppliers. Only electric heating to the compressor
body shall be employed to accelerate this process. When the oil is drained from a
system, it shall be carried out safely.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Kogan KAVWAC2KYA VERTICAL WINDOW AIR CONDITIONER User guide

Category
Mobile air conditioners
Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI