Airwell FADE030 User manual

Category
Split-system air conditioners
Type
User manual

This manual is also suitable for

YUDE Series
Indoor Units
Outdoor Units
CADE024
DBDE024
FADE024
YUDE024
CADE030
DBDE030
FADE030
YUDE030
CADE036
DBDE036
FADE036
YUDE036
CADE036
DBDE036
FADE036
YUDE036T
R410A
HEAT PUMP
SM YUDE 2-A.1 GB
SEP-2015
Version:2
LIST OF EFFECTIVE PAGES
SM YUDE 2-A.1 GB
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent
effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Total number of pages in this publication is 81 consisting of the following:
Page
No.
Revision
No. #
Page
No.
Revision
No. #
Page
No.
Revision
No. #
* Zero in this column indicates an original page.
TABLE OF CONTENTS
SM YUDE 2-A.1 GB
Table of Contents
1. INTRODUCTION ............................................................................................................................. 1-1
2. PRODUCT DATA SHEET ............................................................................................................... 2-1
3. RATING CONDITIONS ................................................................................................................... 3-10
4. OUTLINE DIMENSIONS ................................................................................................................. 4-1
5. PERFORMANCE DATA ................................................................................................................. 5-1
6. AIRFLOW CURVES ........................................................................................................................ 6-1
7. ELECTRICAL DATA ....................................................................................................................... 7-1
8. WIRING DIAGRAMS ...................................................................................................................... 8-1
9. REFRIGERATION DIAGRAMS ...................................................................................................... 9-1
10. TUBING CONNECTIONS ............................................................................................................... 10-1
11. CONTROL SYSTEM ....................................................................................................................... 11-1
12. TROUBLESHOOTING .................................................................................................................... 12-1
13. EXPLODED VIEWS AND SPARE PART LISTS ............................................................................ 13-1
14. APPENDIX ...................................................................................................................................... 14-1
INTRODUCTION
SM YUDE 2-A.1 GB 1-1
1. INTRODUCTION
1.1 General
The YUDE series DC inverter is major designed for light commercial air-
conditioning needs with the DC inverter technology, this series of products
provides the most comfort and energy saving. This new line come with the comply
to the new ECO Design regulation of 2014.
The outdoor can match following indoors:
-Indoor Floor/Ceiling DCI: 3 sizes including 24/30/36kBtu/h
-Indoor Cassette DCI: 3 sizes including 24/30/36Btu/h
-Indoor Ducted DCI:3 sizes including 24/30/36kBtu/h
The outdoor unit has two options of 1 phase/3 phases:
1 Phase: 3 sizes including 24/30/36kBtu/h
3 Phase: 36kBtu/h
1.2 Main Features
DCI R410A models
Auto mode.
SEER / SCOP A-A level for all models.
Cooling
Heating
Dehumidification
Sleep mode
ON/OFF timer
Auto swing (cassette and floor ceiling)
4-dimension swing(cassette only )
Intelligent deicing
Memory from power failure
Cold air prevention in heating
Self diagnostic (Error indications) for ease of maintenance
Outdoor -15 C for cooling
INTRODUCTION
1-2 SM YUDE 2-A.1 GB
1.3 Indoor Unit
The CADE indoor unit is ceiling mounted, the FADE indoor unit is ceiling or floor
mounted, the DBDE indoor unit is a low silhouette ducted unit and can be easily fitted
to many types of residential and commercials applications.
It includes:
Coil with hydrophilic aluminum fins.
Motorized flaps (step motors) for CADE and FADE
Advanced electronic control box assembly
1.4 Filtration
The series presents air filters:
Easily accessible, and re-usable pre-filters (mesh)
1.5 Control
The microprocessor indoor controller, and an infrared remote control and wired
controller, supplied as standard, provide complete operating function and programming.
For further details please refer to the Operation Manual, Appendix A.
INTRODUCTION
SM YUDE 2-A.1 GB 1-3
1.6 Outdoor Unit
The outdoor units can be installed as floor or wall mounted units by using a wall
supporting bracket. The metal sheets are protected by anti- corrosion paint work
allowing long life resistance. All outdoor units are pre-charged. For further information
please refer to the Product Data Sheet, Chapter 2.
It includes :
Compressor mounted in a soundproofed compartment :
Axial fan.
Outdoor coil with hydrophilic louver fins for RC units.
Outlet air fan grill.
Service valves” flare” type connection.
1.7 Tubing Connections
Flare type interconnecting tubing to be produced on site.
For further details please refer to the Installation Manual, Chapter 10.
1.8 Accessories
RCWE Wall Mounted Remote Control
The RCWE remote control is mounted on the wall, and controls the unit either as an
infrared remote control or as a wired controller. The wired controller can control up to
10 indoor units with the same program settings and adjustment.
For further details please refer to the Technical Service Manual.
1.9 Inbox Documentation
Each unit is supplied with its own installation and operation manuals.
INTRODUCTION
1-4 SM YUDE 2-A.1 GB
1.10 Matching Table
OUTDOOR
UNITS
INDOOR UNITS
AWSI-DBDE024-N11
AWSI-DBDE030-N11
AWSI-DBDE036-N11
AWSI-CADE024-N11
AWSI-CADE030-N11
AWSI-CADE036-N11
AWSI-FADE024-N11
AWSI-FADE030-N11
AWSI-FADE036-N11
AWAU-YUDE024-H11
AWAU-YUDE030-H11
AWAU-YUDE036-H11
AWAU-YUDE036-H13
PRODUCT DATA SHEET
SM YUDE 2-A.1 GB 2-1
2. PRODUCT DATA SHEET
2.1 AWSI-DBDE024-N11 // AWAU-YUDE024-H11
Model Indoor Unit
AWAU-DBDE024-N11
Model Outdoor Unit
AWAU-YUDE024-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
7,0(2,2-8,5)
8,0(2,4-9,5)
Pdesign
kW
7,0
7,0
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
480
2579
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-20
Rated power input (Maximum power input)
kW
3,80
4,00
Rated current (Maximum current)
A
17,5
18,4
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
1280/1200/1140/960
1280/1200/1140/960
Air flow
(3)
H/M/L
m3/hr
1400/1300/1200/1000
1400/1300/1200/1000
External static
pressure
Min-Max
Pa
25(0-100)
Sound power level
(4)
H/M/L
dB(A)
64
Sound pressure level
(5)
H/M/L
dB(A)
47/46/44/40
Moisture removal
l/hr
2,3
Condensate drain tube I.D
mm
20mm
Dimensions
WxHxD
mm
1239x268x558
Weight
kg
34
Package dimensions
WxHxD
mm
1348x597x283
Packaged weight
kg
39
Units per pallet
units
7
Stacking height
units
7
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
840
Air flow
H/L
m3/hr
4000
Sound power level
(4)
H/L
dB(A)
65
Sound pressure level
(5)
H/L
dB(A)
57
Dimensions
WxHxD
mm
980x790x427
Weight
kg
67
Package dimensions
WxHxD
mm
1083x855x488
Packaged weight
kg
72
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
2.2
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
PRODUCT DATA SHEET
2-2 SM YUDE 2-A.1 GB
2.2 AWSI-FADE024-N11 // AWAU-YUDE024-H11
Model Indoor Unit
AWAU-FADE024-N11
Model Outdoor Unit
AWAU-YUDE024-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
7,0(2,4-8,2)
8,0(2,4-9,0)
Pdesign
kW
7,0
7,0
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
480
2579
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-20
Rated power input (Maximum power input)
kW
3,80
4,00
Rated current (Maximum current)
A
17,5
18,4
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
1150/1100/1020/800
1150/1100/1020/800
Air flow
(3)
H/M/L
m3/hr
1200/1000/900/800
1200/1000/900/800
External static
pressure
Min-Max
Pa
0
Sound power level
(4)
H/M/L
dB(A)
62
Sound pressure level
(5)
H/M/L
dB(A)
49/48/46/40
Moisture removal
l/hr
2,5
Condensate drain tube I.D
mm
17
Dimensions
WxHxD
mm
1220x225x700
Weight
kg
40
Package dimensions
WxHxD
mm
1343x823x315
Packaged weight
kg
50
Units per pallet
units
6
Stacking height
units
6
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
840
Air flow
H/L
m3/hr
4000
Sound power level
(4)
H/L
dB(A)
65
Sound pressure level
(5)
H/L
dB(A)
57
Dimensions
WxHxD
mm
980x790x427
Weight
kg
67
Package dimensions
WxHxD
mm
1083x855x488
Packaged weight
kg
72
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
2.2
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
PRODUCT DATA SHEET
SM YUDE 2-A.1 GB 2-3
2.3 AWSI-CADE024-N11 // AWAU-YUDE024-H11
Model Indoor Unit
AWAU-CADE024-N11
Model Outdoor Unit
AWAU-YUDE024-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
7,0(2,4-8,5)
8,0(2,4-9,5)
Pdesign
kW
7,0
7,2
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
480
2653
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-20
Rated power input (Maximum power input)
kW
3,80
4,00
Rated current (Maximum current)
A
17,5
18,4
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
650/620/560/500
650/620/560/500
Air flow
(3)
H/M/L
m3/hr
1300
1300
External static
pressure
Min-Max
Pa
0
Sound power level
(4)
H/M/L
dB(A)
62
Sound pressure level
(5)
H/M/L
dB(A)
47/46/42/38
Moisture removal
l/hr
2,5
Condensate drain tube I.D
mm
25mm
Dimensions
WxHxD
mm
840x840x240
Weight
kg
26
Package dimensions
WxHxD
mm
963x963x325
Packaged weight
kg
32
Units per pallet
units
6
Stacking height
units
6
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
840
Air flow
H/L
m3/hr
4000
Sound power level
(4)
H/L
dB(A)
65
Sound pressure level
(5)
H/L
dB(A)
57
Dimensions
WxHxD
mm
980x790x427
Weight
kg
67
Package dimensions
WxHxD
mm
1083x855x488
Packaged weight
kg
72
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
2.2
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
PRODUCT DATA SHEET
2-4 SM YUDE 2-A.1 GB
2.4 AWSI-DBDE030-N11 // AWAU-YUDE030-H11
Model Indoor Unit
AWAU-DBDE030-N11
Model Outdoor Unit
AWAU-YUDE030-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
8,3(2,4-8,7)
9,2(2,4-9,9)
Pdesign
kW
8,3
7,6
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
570
2800
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-25
Rated power input (Maximum power input)
kW
3,90
4,10
Rated current (Maximum current)
A
18,1
19,0
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
1280/1200/1140/960
1280/1200/1140/960
Air flow
(3)
H/M/L
m3/hr
1400/1300/1200/1000
1400/1300/1200/1000
External static
pressure
Min-Max
Pa
37(0-100)
Sound power level
(4)
H/M/L
dB(A)
64
Sound pressure level
(5)
H/M/L
dB(A)
47/46/44/40
Moisture removal
l/hr
2,3
Condensate drain tube I.D
mm
20mm
Dimensions
WxHxD
mm
1239x268x558
Weight
kg
34
Package dimensions
WxHxD
mm
1348x597x283
Packaged weight
kg
39
Units per pallet
units
7
Stacking height
units
7
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
840
Air flow
H/L
m3/hr
4000
Sound power level
(4)
H/L
dB(A)
65
Sound pressure level
(5)
H/L
dB(A)
58
Dimensions
WxHxD
mm
980x790x427
Weight
kg
71
Package dimensions
WxHxD
mm
1083x855x488
Packaged weight
kg
76
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
2.4
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
PRODUCT DATA SHEET
SM YUDE 2-A.1 GB 2-5
2.5 AWSI-FADE030-N11 // AWAU-YUDE030-H11
Model Indoor Unit
AWAU-FADE030-N11
Model Outdoor Unit
AWAU-YUDE030-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
8,5(2,6-9,2)
9,2(2,4-9,9)
Pdesign
kW
8,5
7,6
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
583
2800
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-25
Rated power input (Maximum power input)
kW
3,90
4,10
Rated current (Maximum current)
A
18,1
19,0
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
1050/1000/960/740
1050/1000/960/740
Air flow
(3)
H/M/L
m3/hr
1500/1400/1200/1000
1500/1400/1200/1000
External static
pressure
Min-Max
Pa
0
Sound power level
(4)
H/M/L
dB(A)
62
Sound pressure level
(5)
H/M/L
dB(A)
49/46/44/38
Moisture removal
l/hr
3,0
Condensate drain tube I.D
mm
17
Dimensions
WxHxD
mm
1420x245x700
Weight
kg
48
Package dimensions
WxHxD
mm
1548x828x345
Packaged weight
kg
56
Units per pallet
units
6
Stacking height
units
6
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
840
Air flow
H/L
m3/hr
4000
Sound power level
(4)
H/L
dB(A)
65
Sound pressure level
(5)
H/L
dB(A)
58
Dimensions
WxHxD
mm
980x790x427
Weight
kg
71
Package dimensions
WxHxD
mm
1083x855x488
Packaged weight
kg
76
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
2.4
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
PRODUCT DATA SHEET
2-6 SM YUDE 2-A.1 GB
2.6 AWSI-CADE030N11 // AWAU-YUDE030-H11
Model Indoor Unit
AWAU-CADE030-N11
Model Outdoor Unit
AWAU-YUDE030-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
8,3(2,6-9,2)
9,2(2,4-9,9)
Pdesign
kW
8,3
7,6
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
570
2800
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-25
Rated power input (Maximum power input)
kW
3,90
4,10
Rated current (Maximum current)
A
18,1
19,0
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
620/580/530/410
620/580/530/410
Air flow
(3)
H/M/L
m3/hr
1500
1500/
External static
pressure
Min-Max
Pa
0
Sound power level
(4)
H/M/L
dB(A)
63
Sound pressure level
(5)
H/M/L
dB(A)
49/48/45/40
Moisture removal
l/hr
3,0
Condensate drain tube I.D
mm
25
Dimensions
WxHxD
mm
840x840x320
Weight
kg
31
Package dimensions
WxHxD
mm
963x963x409
Packaged weight
kg
38
Units per pallet
units
5
Stacking height
units
5
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
840
Air flow
H/L
m3/hr
4000
Sound power level
(4)
H/L
dB(A)
65
Sound pressure level
(5)
H/L
dB(A)
58
Dimensions
WxHxD
mm
980x790x427
Weight
kg
71
Package dimensions
WxHxD
mm
1083x855x488
Packaged weight
kg
76
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
2.4
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
PRODUCT DATA SHEET
SM YUDE 2-A.1 GB 2-7
2.7 AWSI-DBDE036-N11 // AWAU-YUDE036-H11
Model Indoor Unit
AWAU-DBDE036-N11
Model Outdoor Unit
AWAU-YUDE036-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
10,0(3,2-11,5)
12,0(2,9-14,5)
Pdesign
kW
10,0
10,4
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
687
3832
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-32
Rated power input (Maximum power input)
kW
4,65
4,75
Rated current (Maximum current)
A
21,5
22,0
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
1380/1350/1200/1050
1380/1350/1200/1050
Air flow
(3)
H/M/L
m3/hr
2100/1950/1800/1700
2100/1950/1800/1700
External static
pressure
Min-Max
Pa
37(0-150)
Sound power level
(4)
H/M/L
dB(A)
64
Sound pressure level
(5)
H/M/L
dB(A)
53/52/48/44
Moisture removal
l/hr
2,3
Condensate drain tube I.D
mm
20mm
Dimensions
WxHxD
mm
1226x290x775
Weight
kg
46
Package dimensions
WxHxD
mm
1338x877x305
Packaged weight
kg
63
Units per pallet
units
6
Stacking height
units
6
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
900
Air flow
H/L
m3/hr
5300
Sound power level
(4)
H/L
dB(A)
70
Sound pressure level
(5)
H/L
dB(A)
63
Dimensions
WxHxD
mm
1107x1100x440
Weight
kg
92
Package dimensions
WxHxD
mm
1158x1235 x493
Packaged weight
kg
100
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
3,5
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
PRODUCT DATA SHEET
2-8 SM YUDE 2-A.1 GB
2.8 AWSI-FADE036-N11 // AWAU-YUDE036-H11
Model Indoor Unit
AWAU-FADE036-N11
Model Outdoor Unit
AWAU-YUDE036-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
10,0(3,2-11,5)
12,0(2,9-14,5)
Pdesign
kW
10,0
10,4
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
687
3832
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-32
Rated power input (Maximum power input)
kW
4,75
4,85
Rated current (Maximum current)
A
22,0
22,5
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
1200/1150/1000/860
1200/1150/1000/860
Air flow
(3)
H/M/L
m3/hr
1900/1630/1520/1350
1900/1630/1520/1350
External static
pressure
Min-Max
Pa
0
Sound power level
(4)
H/M/L
dB(A)
65
Sound pressure level
(5)
H/M/L
dB(A)
54/53/51/46
Moisture removal
l/hr
3,8
Condensate drain tube I.D
mm
17
Dimensions
WxHxD
mm
1420x245x700
Weight
kg
48
Package dimensions
WxHxD
mm
1548x828x345
Packaged weight
kg
56
Units per pallet
units
6
Stacking height
units
6
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
900
Air flow
H/L
m3/hr
5300
Sound power level
(4)
H/L
dB(A)
70
Sound pressure level
(5)
H/L
dB(A)
63
Dimensions
WxHxD
mm
1107x1100x440
Weight
kg
92
Package dimensions
WxHxD
mm
1158x1235 x493
Packaged weight
kg
100
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
3,5
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
PRODUCT DATA SHEET
SM YUDE 2-A.1 GB 2-9
2.9 AWSI-CADE036-N11 // AWAU-YUDE036-H11
Model Indoor Unit
AWAU-CADE036-N11
Model Outdoor Unit
AWAU-YUDE036-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Average
Capacity
(1)
kW
10,0(3,2-11,5)
12,0(2,9-14,5)
Pdesign
kW
10,0
10,4
SEER / SCOP
(2)
W/W
5.1
3.8
Energy efficiency class
A
A
Annual energy consumption
kWh
687
3832
Tbiv
o
C
N/A
-7
Tol
o
C
N/A
-15
Power supply
V/Ph/Hz
220-240V/Single/50Hz
Circuit breaker rating(Indoor-Outdoor)
A
10-32
Rated power input (Maximum power input)
kW
4,65
4,85
Rated current (Maximum current)
A
21,5
22,5
INDOOR
Fan type & quantity
Centrifugal fan-2
Fan speeds
H/M/L
RPM
720/680/600/520
720/680/600/520
Air flow
(3)
H/M/L
m3/hr
1850
1850
External static
pressure
Min-Max
Pa
0
Sound power level
(4)
H/M/L
dB(A)
63
Sound pressure level
(5)
H/M/L
dB(A)
51/49/46/43
Moisture removal
l/hr
3,8
Condensate drain tube I.D
mm
25mm
Dimensions
WxHxD
mm
840x840x320
Weight
kg
31
Package dimensions
WxHxD
mm
963x963x409
Packaged weight
kg
38
Units per pallet
units
5
Stacking height
units
5
OUTDOOR
Refrigerant control
EEV
Compressor type, model
Rotary DC Inverter
Fan type & quantity
Axial x 1
Fan speeds
H/L
RPM
900
Air flow
H/L
m3/hr
5300
Sound power level
(4)
H/L
dB(A)
70
Sound pressure level
(5)
H/L
dB(A)
63
Dimensions
WxHxD
mm
1107x1100x440
Weight
kg
92
Package dimensions
WxHxD
mm
1158x1235 x493
Packaged weight
kg
100
Units per pallet
Units
6
Stacking height
Units
2
Refrigerant type
R410A
Refrigerant charge (standard connecting
tubing length)
kg(5m)
3,5
Additional charge per 1 meter
gr / 1m
5m<L<30m 60g/m
Connections
between units
Liquid line
In.(mm)
3/8"(9.53)
Suction line
In.(mm)
5/8"(15.88)
Max.tubing length
m.
Max.30
Max.height difference
m.
Max.15
Operation control type
Remote control/Wired Remote control
Heating elements
kW
-
Others
-
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
(2) SEER / SCOP calculation accordance with EN14825.
(3) Airflow in ducted units; at nominal external static pressure.
(4) Sound power in ducted units is measured at air discharge.
(5) Sound pressure level measured at 1.4 meter distance from unit.
PRODUCT DATA SHEET
3-10 SM YUDE 2-A.1 GB
3. RATING CONDITIONS
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
Cooling:
Indoor: 27
o
C DB 19
o
C WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6
o
C WB
3.1 Operating Limits
R410A
Indoor
Outdoor
Cooling
Upper limit
32
o
C DB 23
o
C WB
48
o
C DB
Lower limit
21
o
C DB 15
o
C WB
-15
o
C DB
Heating
Upper limit
27
o
C DB
24
o
C DB 18
o
C WB
Lower limit
10
o
C DB
-15
o
C DB
Voltage
1PH
198 264 V
3PH
360 440 V
OUTLINE DIMENSIONS
SM YUDE 2-A.1 GB 4-1
4. OUTLINE DIMENSIONS
4.1 CADE024-030-036
Unit:mm
Model
A
B
C
D
E
F
CADE024
950
840
780
680
160
240
CADE030/036
950
840
780
680
160
320
4.2 DBDE 024-030-036
Unit: mm
A
B
C
D
E
F
G
H
I
J
DBDE024
1101
515
820
1159
1239
558
1002
160
235
268
DBDE030
1101
515
820
1159
1239
558
1002
160
235
268
DBDE036
1011
748
820
1115
1226
775
979
160
231
290
OUTLINE DIMENSIONS
4-2 SM YUDE 2-A.1 GB
4.3 FADE024-030-036
A
B
Unit: mm
Model
A
B
C
D
H
FADE024
1220
225
1158
280
700
FADE030
1420
245
1354
280
700
FADE036
1420
245
1354
280
700
OUTLINE DIMENSIONS
SM YUDE 2-A.1 GB 4-3
4.4 Outdoor Unit:
Unit: mm
Model
A
B
C
D
E
YUDE024
980
427
790
610
390
YUDE030
980
427
790
610
390
YUDE036
1107
440
1100
631
400
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Airwell FADE030 User manual

Category
Split-system air conditioners
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI