Cumberland 4801-5098 - Farm Hand Vent Master Owner's manual

Type
Owner's manual
Part No. 4801-5098 Owners Manual Farm Hand Vent Master
Farm Hand Vent Master
16 Stage Environmental Controller
Cumberland
1004 E. Illinois St.
Assumption, IL 62510
Part No. 4801-5098 Farm Hand Vent Master Table of Contents
Table of Contents
1.Ratings and specifications .............................................................................................................................. 1
2.Warnings ........................................................................................................................................................ 1
3.Introduction .................................................................................................................................................... 2
4.Static Pressure Overview ................................................................................................................................ 3
5.Why Use a Pressure Controller? .................................................................................................................... 3
6.Pressure Ramping (Optional) Explanation ..................................................................................................... 4
7.Day to Day Operating Instructions ................................................................................................................. 5
7.1Checking/Adjusting Temperatures, and Timer Percentages ................................................................... 5
7.2Running Vent Machines ......................................................................................................................... 8
7.3Adjusting Stage On/OffPoints ................................................................................................................ 8
8.Program Mode ................................................................................................................................................ 9
8.1Sensors For Display (PSd)...................................................................................................................... 9
8.2Stage Parameters .................................................................................................................................... 9
8.2.1Stage Sensors (P1) .......................................................................................................................... 9
8.2.2Stage Mode (P2) ............................................................................................................................. 9
8.2.3Stage Timer Settings (P3) ............................................................................................................. 10
8.2.4Minimum Runtime Percentage (P10) (Variable Stages Only)...................................................... 10
8.2.5Motor Curve (P11) (Variable Stages Only) .................................................................................. 11
8.3Vent Parameters .................................................................................................................................... 11
8.4Pressure Ramping Parameters .............................................................................................................. 11
8.5Pressure Alarm Parameters ................................................................................................................... 12
8.6PC Compatible Network Parameters .................................................................................................... 12
8.7Cool Timer Settings (ON/OFF Stages Only) ....................................................................................... 12
8.8Sensor Calibration ................................................................................................................................ 12
9.Rarely Changed Settings .............................................................................................................................. 13
10.Controller Installation and Setup .............................................................................................................. 15
11.Programming Examples ........................................................................................................................... 15
11.1Setting Stage OnPoints and OffPoints .................................................................................................. 15
11.2Setting up Stage Modes, and Timer Status ........................................................................................... 16
11.3Setting Up Tunnel Control ................................................................................................................... 16
11.4Cool Timer Stage Operation ................................................................................................................. 17
11.5Variable Speed Stage Operation ........................................................................................................... 18
11.5.1Variable Speed Stage Operation (Variable Stage Model Only) ................................................... 18
11.5.2Progressive Cool Timer Option .................................................................................................... 19
12.Maintenance ............................................................................................................................................. 19
13.Wiring Diagrams, Schematics, etc. .......................................................................................................... 20
13.1Connecting the Vent Machines to the Vent Master .............................................................................. 22
13.2Connecting Sensors to the Vent Master ............................................................................................... 23
13.3Connecting Stages to a Relay Panel ..................................................................................................... 24
13.4Connecting AC Power to the Vent Master ........................................................................................... 25
13.5Variable Speed Wiring ......................................................................................................................... 26
13.6Variable Speed Wiring with an External Hookup ................................................................................ 27
13.7Connecting the Vent Master to a Data Shuttle ..................................................................................... 28
13.8Connecting the Vent Master to a Static Pressure Monitor.................................................................... 29
13.9Connecting the Vent Master to a Series or Parallel Alarm ................................................................... 30
14.Program Reference ................................................................................................................................... 31
15.Error Codes............................................................................................................................................... 34
15.1Descriptions .......................................................................................................................................... 34
15.2Possible Solutions ................................................................................................................................. 35
15.3Temperature vs. Sensor Resistance Table ............................................................................................ 36
16.Program Parameter Listing ....................................................................................................................... 37
17.Error Code Listing .................................................................................................................................... 38
18.Program Data Sheet .................................................................................................................................. 39
19.Warranty ................................................................................................................................................... 40
Part No. 4801-5098 Farm Hand Vent Master 1
1. Ratings and specifications
115/230 Volts (Depending on switch position.)
50/60 Hz.
12 Amps per stage.
12 Amps per variable speed stage.
8 Amps per vent machine.
Room must be kept above 32F/0C and below 122F/50C.
2. Warnings Warning!
Before connecting power to the machine, be sure to check the position of the
voltage selector switch located next to the transformer on the relay board.
Improper positioning of this switch will cause system failure.
Warning!
When this controller is used in a life support heating and ventilation system
where failure could result in loss or injury, the user should provide adequate
back-up, or accept the risk of such loss or injury!
Part No. 4801-5098 Farm Hand Vent Master 2
3. Introduction
There are two models of the Vent Master controller:
(1) Farm Hand Vent Master without Variable Speed
(2) Farm Hand Vent Master with Variable Speed
The only difference between the models is the variable speed option.
The Farm Hand Vent Master Stage Controller is designed to be one of the simplest controllers on the
market to operate, but to also be one of the most powerful. The Vent Master combines the features of the
Farm Hand Stage Master 12 with the capabilities of the Farm Hand Power Vent into a single controller.
The Vent Master has four main regions on the faceplate: the main display, stage displays, the control
button region and the vent machine control region. The main display area includes the main display, and
four green LED’s which tell what the main display is indicating. If the green light beside “Temperature” is
lit, then the display is showing the display option chosen in the Program Mode under the parameter PSd.
Refer to Section 6.1 for an explanation of the PSd parameter.
On the left hand side of the controller face are the stage displays. When the controller is operating the
OnPoint of each stage (the temperature the stage will turn on) is displayed. Next to the stage indicators, is a
button with the number of the stage printed on it. Press this button to set the On and OffPoints for that
stage. (Stage OnPoints and OffPoints are discussed later in the manual.) The blank white region is for
labeling equipment such as (front heat, back heat, sidewall fans, etc.). Finally, there is a small red LED on
the bottom right of this white region. This is the stage status indicator. This light will be lit if the stage is
on, and will flash on and off if it is running because it is on a timer.
Just below the main display on the right hand side of the controller is the control button region. This
region has three buttons, Mode, +, and -. You will learn the use of these three buttons later in this manual.
Finally, on the bottom right hand side of the controller is the vent machine control region. This region
includes an Automatic/Manual switch, and an Open/Off/Close switch for each machine.
Main Display
Control Buttons
Display Indicators
Stage Status Indicators
V
ariable Stages
(Depending On Model)
Vent Machine Controls
Stage Buttons
Notice: If the Farm Hand Vent Master is a Variable Speed Model, then stages 1 & 2 are the
Variable Speed stages.
Farm Hand Vent Master 16
Part No. 4801-5098 Farm Hand Vent Master 3
4. Static Pressure Overview
The Farm Hand Vent Master has been designed with the producer in mind. Routine tasks such as changing
the pressure limits are easily reset, and are familiar in nature.
This controller has only two basic pressure settings, a Target Pressure, and a Pressure Differential. The
Target Pressure is the static pressure that the system tries to maintain within the limits of the Pressure
Differential. The Pressure Differential is the range around the Target Pressure that is considered
satisfactory. From the Target Pressure and the Pressure Differential the High and Low Pressure limits are
calculated. The High Pressure limit is the Target Pressure plus half of the Pressure Differential and the
Low Pressure limit is the Target Pressure minus half of the Pressure Differential. The controller will open
and close the vents as needed to maintain pressure between the high and low limits.
Low Pressure
High Pressure Limit
Low Pressure Limit
When pressure is
in this range, the
controller will not
adjust vents.
When pressure is
above the high
limit, the vent
machine will open
vents to lower
pressure.
When pressure is
below the low
limit, the vent
machine will close
vents to raise
pressure.
High Pressure
Room Pressure
Now that we know how the pressure limits are established, lets move on to how to set up those limits.
Press the mode button a few times, and you will see that the display changes each time. If you will look
just to the right of the display, you will see four green lights labeled Temperature, Static Pressure,
Var/Timer Percent, and Target. The green light tells you what setting you are looking at in the main
display. If the light beside Static Pressure is lit, the numbers in the display show you the current pressure
in your building. However, for viewing Target Temperature both the LEDs beside “Target” and
“Temperature” will be lit. For viewing Target Static Pressure both the LEDs beside “Target” and “Static
Pressure” will be lit.
Assume that you have this controller installed in your house, and you decide you want pressure to be kept a
little bit lower. You walk to the controller, press and release the mode button, watching the green lights
until the “Target” and “Static Pressure” LED is lit. If you look at the display now, you see the present
setting for the Target Pressure. To lower it, press and release the minus (-) button until you see the new
limit you want. The controller will now start operating using your new limit. If you want the Vent Master
to maintain the Target Pressure within narrower limits decrease the Pressure Differential. See Section 6 for
a graphic example using the Target Pressure and Pressure Differential.
5. Why Use a Pressure Controller?
The Farm Hand Vent Master is used to control vent inlets in agricultural enclosures. Maintaining a slight
negative pressure inside a building ensures that air flows in evenly from all openings in the building.
However, as static pressure increases, the speed and volume of the incoming air increases. It is important
to set the pressure at an appropriate level to ensure maximum efficiency. Too little vacuum, and the
livestock could suffer from drafting, and temperature shock. Too much vacuum, and fan efficiency is
reduced, increasing the levels of moisture, ammonia in the enclosure, and also driving up electricity costs.
Part No. 4801-5098 Farm Hand Vent Master 4
6. Pressure Ramping (Optional) Explanation
High Volume of Slow Warm Air
Low volume of fast moving air enters the vents and is "thrown"
to the ceiling, where it is slowed, and warmed by the mixing with
the warmer air in the top of the enclosure before settling down
to the bottom of the building.
The above illustrations show the need for a different air flow rate when the temperature changes. This is
accomplished with the ramping feature.
Ramping allows you to set a band of pressure to be maintained, taking into account the OUTSIDE
temperature. (After all, outside air is what is flowing into the house.) If the outside temperature is warm, it
will allow taking in a large volume of slow moving warm air (low static pressure), but when outside air is
cold, the Vent Master will adjust to allow a low volume of fast moving cold air (high static pressure).
Using figures from the chart above; the controller was programmed as follows:
P21 = Pressure Differential 0.02” w.c.
P30 = Ramping Mode ON
P31 = High Temperature Limit 80°F
P32 = High Temperature Target Pressure 0.03" w.c.
P34 = Low Temperature Limit 40°F
P35 = Low Temperature Target Pressure 0.11" w.c.
0.12
0.10
0.08
0.06
0.04
0.02
0
Temperature (F)
Negative
Pressure
("w.c.)
010 20 30 40 50 60 70 80 90 100 110
Above Target High Pressure
Vent Machine Opens
Below Target Low Pressure
Vent Machine Closes
Acceptable Target Pressure
No Machine Operation
Pressure Differential
Target Pressure
Part No. 4801-5098 Farm Hand Vent Master 5
As you can see from the graph, if outside temperature is 50°F, the controller will try to maintain a static
pressure between .08, and .1” w.c. If the pressure goes above .1” w.c. the vent machine will open, and
reduce static pressure, and if the pressure goes below .0.08” w.c., the vent machine will close, increasing
the static pressure.
7. Day to Day Operating Instructions
This section of the manual will give you all you need to know about the day to day operation of your
controller.
7.1 Checking/Adjusting Temperatures, and Timer Percentages
When no one has pressed a button for over one minute, the display will automatically show the
room temperature and the display indicator will indicate “Temperature”. To see the Static
Pressure, press the button labeled “Mode”. This button is located in the center of the controller
facepad. When this button is pressed, watch the green LED’s beside the main display. Whenever
a single LED is lit, this is the parameter you are viewing.
For viewing Target Temperature both the LEDs beside “Target” and “Temperature” will be lit.
For viewing Target Static Pressure both the LEDs beside “Target” and “Static Pressure” will be
lit.
Room Temperature
The temperature read by the sensor(s) chosen in the Program Mode under the parameter
PSd. Refer to Section 8.1 for an explanation of the PSd parameter.
Static Pressure
The static pressure sensed by the controller. While displaying the Static Pressure, the
controller will also display the temperatures read by sensors 1, 2, 3 & 4 in the
corresponding stage displays. The remaining stage displays will be blank at this time.
Var/Timer Percentage
The Var/Timer percentage parameter can be used to set variable speed and/or runtime
percentage depending on the model of the Farm Hand Vent Master.
Variable Speed refers to the increase or decrease of fan speed as regulated by the controller
based on temperature. For example, a Var/Timer Pct. set to 50 means that a fan will run at
50% of its maximum speed at a particular temperature.
Temperature
displays Room
Stage Status
Indicator LED
Displays reading of Sensor
Displays reading of Sensor
Displays reading of Sensor
Displays reading of Sensor
4
Part No. 4801-5098 Farm Hand Vent Master 6
Runtime percentage refers to the percentage of the timer cycle that a stage on a timer will
run. For example, if the Var/Timer Pct. is set for 30, and your timer cycle is set for 10
minutes, the timed stages will run for 3 minutes out of every 10 minutes (i.e. 30% of the
timer cycle).
There are two models of the Farm Hand Vent Master Controller. On the Non-variable
speed model, this setting refers to the Runtime percentage for any of the stages that are on
the system timer. On the Variable speed model, this setting is used to set the minimum
speed for stages 1 & 2 and also the Runtime percentage for any of the remaining ON/OFF
stages that are on the system timer. Please note your model. You can determine the model
by comparing the main display sequence to that described in the following diagrams.
Non-variable Speed Model - (Runtime Percentage)
The Var/Timer Pct. parameter sets the Runtime percentage of all stages that are placed on a
timer (See Section 9.2). The value of the Var/Timer Pct. in the main display refers to a
Runtime % which can be set to values between 5 and 100 using the "+" and "-" buttons.
When you step through the main display parameters, notice the stage status indicators. As
the Mode button is pressed, a Var/Timer Pct. value will appear in the main display, and
stages affected by this setting will have stage status indicators lit.
Variable Speed Model - (Minimum Speed %)
On the variable speed model, this setting allows you to program three parameters: the
Minimum speed % for stage 1, the Minimum speed % for stage 2, and the Runtime % for
the remaining ON/OFF stages. If using the variable stages as progressive cool timer
stages, this setting becomes the Minimum runtime % instead of the Minimum speed %.
(Refer to Section 9.5.2 for more discussion on this option).
As you step through the main display and you get to the Var/Timer Pct. setting, notice
the stage status indicators. These indicators show which setting you are programming.
The Var/Timer Pct setting is displayed as shown in the following diagram.
Non-variable Speed Model
(
Parameter selection se
q
uence
)
Room
Temperature Static
Pressure Target
Temperature
Var/Timer
Percentage
on/off stages
Runtime %
Target
Pressure
Variable Speed Model
(Parameter selection sequence)
Part No. 4801-5098 Farm Hand Vent Master 7
Target Temperature
The target temperature is the temperature the system tries to maintain.
To adjust these settings, press the mode button until you see the setting you want to
adjust, then use the + button to raise the value, and the - button to lower the value. When
you are finished setting a new value, either press the mode button again, or do nothing,
and the system will return to normal operation within a few seconds.
Target Static Pressure
The Static Pressure the system tries to maintain within the limits of the Pressure
Differential.
To adjust the Target Static Pressure, press the mode button until you see the setting you
want to adjust, then use the + button to raise the value, and the - button to lower the
value. When you are finished setting a new value, either press the mode button again, or
do nothing, and the system will return to normal operation within a few seconds.
The Pressure Differential is the range around the Target Pressure that is considered
satisfactory. From the Target Pressure and the Pressure Differential the target high and
low pressure limits are calculated as follows:
Target High Pressure Limit = Target Pressure + ½ Pressure Differential
Target Low Pressure Limit = Target Pressure + ½ Pressure Differential
For Target Temperature, both
the Target LED and the
Temperature LED will be
lighted.
Room
Temperature Static
Pressure Target
Temperature
V
ar/Timer
Percentage
Stage 1
(Minimum Speed %)
Stage 2
(Minimum Speed %)
on/off stages
(Runtime %)
Target
Pressure
For Target Pressure, both the
Target LED and the Static
Pressure LED will be lighted.
Part No. 4801-5098 Farm Hand Vent Master 8
Stages
Press any stage
button to set
On/OffPoints.
Adjust value
with + and -
buttons.
Stage Button
7.2 Running Vent Machines
Under normal circumstances the machines should be left in automatic (Auto) as shown above.
This way, if the controller needs to open the vents, it will open them. However, if you want to
open or close them for any reason do the following.
1. Find the switches for the machine you want to run, and check that the Open/Off/Close switch
is in the Off position. This makes sure that the machine does not run until you want it to.
2. Place the Automatic/Manual switch for that machine in the “Manual” position.
3. To open the machine place the Open/Off/Close switch to the position marked “Open”.
4. To close the machine place the Open/Off/Close switch to the position marked “Close”.
5. Finally when you are finished positioning the machine, place the switch back into the “Off”
position. Note: "Off" position is between "Open" and "Close".
6. When you are ready for the controller to take over control of the vents, return the
Automatic/Manual switch to the automatic position.
7.3 Adjusting Stage On/OffPoints
If you decide that a fan stage comes on too soon, or waits until temperature is too high to come
on, you can easily adjust that setting. To adjust the stage OnPoint, press the numbered stage
button one time. The individual stage display will
flash, and the main display will flash between
“On” and the Target Temperature. Use the +
button to raise the value in the individual stage
display until you see the correct temperature, or
the - button to lower the value until the stage
OnPoint is where you want it. When you are
finished setting a new value, press the individual
stage button again and the main display will read
“Off” and flash the target temperature. Use the +
and/or - buttons until the correct setting shows in
the individual stage display.
Notice that as you press the stage button the first time, all of the individual stage displays show
their stage’s OnPoints. Only one stage will flash this reading. When you press the + and/or -
button, you will only adjust that particular stage's value. To adjust another stage, press that
stage’s button.
When you have finished setting your stage On/OffPoints press the individual stage button once
more, and the system will not flash any stage displays, and the main display will read a steady
value. Your Vent Master is now operating normally again.
Note: In this manual, a stage's OnPoint parameter is referenced as (ON). A stage's OffPoint
parameter is referenced as (OFF). For Variable stages, the Minimum OnPoint is the value of
the (OFF) parameter. The Maximum OnPoint is the value of the (ON) parameter.
Manual Open
(UP), Off (Center)
and Close
(DOWN) switch
Auto/Manual
switch
Part No. 4801-5098 Farm Hand Vent Master 9
8. Program Mode
Settings that are usually set up once per growout, or maybe even just for summer or winter are referred to
as program parameters and are accessed by taking the controller to program mode. Some examples of
these settings are Vent Machine Time Delay, Runtime, Stages on Timers, and Sensor Calibration. To get
to program mode, press and hold the “Mode” button for five seconds. When the controller has entered
program mode, the main display will flash between “PSd” and the value of this parameter.
The “PSd” is known as a parameter number. All the program items for the controller have a parameter
number assigned to them. The numbers are listed in the section called “Program Reference” in the back of
this manual with a short description of each parameter. When in program mode, you change the current
parameter by using the + and - buttons as needed. When you have finished with the current setting, press
the “Mode” button to move to the next parameter.
8.1 Sensors For Display (PSd)
The user is given the choice as to what he/she wants to display for Room Temp. The choice is
made in Program Mode under the parameter PSd. The following is a list of choices:
PSd = Room Temperature Display
100 = Sensor 1
020 = Sensor 2
120 = Average of Sensors 1 & 2
003 = Sensor 3
103 = Average of Sensors 1 & 3
023 = Average of Sensors 2 & 3
123 = Average of Sensors 1, 2, & 3
8.2 Stage Parameters
The following parameters are used to program each stage on the Farm Hand Vent Master.
Through these parameters, the user has complete control over the operation of each stage. The
following sections explain each parameter in detail.
P1 = Stage Sensors
P2 = Stage Mode
P3 = Stage Timer Settings
P10 = Minimum Runtime Percentage (Variable Speed Stages Only)
P11 = Motor Curve (Variable Speed Stages Only)
8.2.1 Stage Sensors (P1)
A stage can be programmed to run off of any sensor or combination of sensors. The following is
the list of P1 options:
P1 = Stage Sensors
100 = Sensor 1
020 = Sensor 2
120 = Average of Sensors 1 & 2
003 = Sensor 3
103 = Average of Sensors 1 & 3
023 = Average of Sensors 2 & 3
123 = Average of Sensors 1, 2, & 3
8.2.2 Stage Mode (P2)
The Farm Hand Vent Master is a very intelligent controller, therefore, it needs to not only know
whether this is a heating or cooling stage but also what type of cooling stage. This feature allows
the grower to program the cooling stages to work exactly like he wants them to without the
expense of hard wiring through relays and limit switches. This feature allows the Farm Hand
Part No. 4801-5098 Farm Hand Vent Master 10
Vent Master to better react to the environment. Any Stage can be programmed to be one of the
following:
1 = Heat
This mode allows the equipment to operate when room temperature is
below the OnPoint for the stage.
2 = Cool Stir
This mode setting is for cool stages that stir inside sir. This stage will not
run during tunnel mode.
3 = Cool Negative
This mode setting is primarily for negative cross ventilation fans. This
stage will not run during tunnel mode.
4 = Cool Negative Tunnel
This mode setting works exactly like the Cool Negative setting except it
will run if the controller goes into tunnel mode. This stage is sometimes
referred to as a transitional stage. In other words, it operates before it
goes into tunnel and also during tunnel.
5 = Cool Tunnel
This mode setting only works when the controller is in tunnel mode.
8.2.3 Stage Timer Settings (P3)
The Farm Hand Vent Master is equipped to satisfy any of your minimum ventilation
needs for regular runtime timers, to cool timers, to progressive timers.
00 = No Timer
Select 0 for the timer setting if you do not want the stage to be on a timer.
01 = Runtime Timers
Any one of the On/Off stages can be placed on the system timer by
placing a "1" in parameter 3 (P3) of the stage. By doing this the stage
will operate off of the system timer while the temperature is below the
stage's OnPoint. Once the temperature reaches the stage OnPoint, the
stage will come on full time.
02 = Cool Timers
On/Off Stages
Any one of the On/Off Stages can be placed on a cool timer.
By doing this the stage will operate off the system timer only while the
temperature is above the stage OffPoint (OFF). Refer to Section 11.4
"Cool Timer Stage Operation" for proper setup.
Variable Stages
Any of the variable stages can be placed on a cool timer. By doing this
the stage will be placed on the system timer all the time. It will run full
speed for a certain percentage of time that is set in Var Timer/PCT. This
percentage will progressively increase as the temperature rises above the
minimum OnPoint setting (OFF). Refer to Section 11.5 "Variable Speed
Stage Operation" for proper setup.
8.2.4 Minimum Runtime Percentage (P10) (Variable Stages Only)
This setting is the percentage of the system timer that the variable stage will run at
minimum speed if the stage sensor's temperature is below the Minimum OnPoint (OFF)
for the stage.
Part No. 4801-5098 Farm Hand Vent Master 11
8.2.5 Motor Curve (P11) (Variable Stages Only)
The controller is programmed to operate single phase or three phase fan motors at their
optimum performance levels. Select the correct motor curve parameter (P11) for your
particular application from the following table.
8.3 Vent Parameters
This controller runs 1 or 2 vent machines independently. No additional resources – including
external timers – are necessary. A brief overview of the programmable parameters for the vent
machines follows:
P20 – Vent Machine Time Delay
This setting is the length of time a pressure reading must be out of range before
the controller will operate the vents. This will keep the vents from constantly
cycling open, then closed. If your vents cycle too much, increase this setting
using the plus (+) button.
P21 – Static Pressure Differential
The range over which the Target Pressure will be maintained.
P22 – Tunnel Target Pressure
In tunnel mode, this is the Target Pressure that will be maintained if and only if
SWX 4 of the Tunnel Switches is ON.
P25 – Tunnel OnPoint
This is the sensor 4 temperature at which the controller will enter tunnel mode.
This is only applicable when tunneling on outside temperature.
P26 -- Tunnel OffPoint
This is the sensor 4 temperature at which the controller will exit tunnel mode.
This is only applicable when tunneling on outside temperature.
8.4 Pressure Ramping Parameters
P30 – Ramping Mode On/Off
Ramping mode may be turned on or off. If you choose “OFF”, you will not see
the following settings. However, if you choose “ON”, with the plus or minus
button, you turn ramping on, and will have to set the following items. See
Section 6 on ramping for more information on this feature.
P31 – High Temperature Limit
The outside temperature the controller will use in determining the low range of
its limits.
P32 – High Temperature Target Pressure
The target pressure when the outside temperature is at the high temperature
limit.
P34 – Low Temperature Limit
The outside temperature the controller will use in determining the high range of
its limits.
Curve Conditions
0 This curve is optimized for use with Cumberland’s line of Funnel Flow Fans that are 24” or less. Also, line
voltage must be Single Phase.
1 This curve lends itself better to operation of 36” fans. The power distributed at each percentage is somewhat
greater than that of curve 0. Therefore, the speed will be a little greater than that of curve 0
2 This curve is for 3-Phase systems. Its purpose is to shift the voltage curve to give a much higher power from
the varied phase. Conditions that would warrant the use of this curve is a variable speed fan that varies a great
deal from 100% speed to 95% speed.
3 This curve is for 3-Phase systems. Its purpose is to shift the voltage curve to give much less power from the
varied phase. Conditions that would warrant the use of this curve is a variable speed fan that varies very little
from 100% speed to 5% speed.
Part No. 4801-5098 Farm Hand Vent Master 12
P35 – Low Temperature Target Pressure
The target pressure when the outside temperature is at the low temperature limit.
8.5 Pressure Alarm Parameters
P60 – Low Pressure Alarm
The Low Pressure alarm will send a signal when pressure drops below the Low
Pressure setpoint for greater than 45 seconds. This alarm warns if the vents
failed to close for some reason. Setting the Low Pressure alarm setpoint to
“OFF” prevents the alarm from sounding.
P61 – High Pressure Alarm
The High Pressure alarm will send a signal to your existing alarm system in the
same manner as the Low Pressure alarm, but only when pressure exceeds the
High Pressure Setpoint for greater than 45 seconds. (High Negative Pressure.)
This alarm warns if the vents did not open for some reason. Setting the alarm
setpoint to .20 ”OFF” prevents the alarm from sounding.
P63 – Cycle Pressure Alarm
The cycle alarm is a very important alarm in that it will warn if your timer fans
failed to operate. The controller will look for a pressure surge which would
normally be caused when the timer fans turn on. If this pressure surge is not
sensed within the timer period you specify, the controller will signal your alarm
system, thus triggering an alarm. Setting the value of this limit to “OFF”
prevents the alarm from sounding.
8.6 PC Compatible Network Parameters
This option requires Cumberland’s Farm Manager Software. The controller has three functions
which are used to set it up on the Cumberland PC compatible inter-controller network (HHNet).
These are:
P40 - HHNet Address
HHNet allows you to connect up to 32 controllers on a single communications
port of your personal computer (PC). In order for the computer to recognize the
communications from the controllers, each controller must have a unique address.
For example, if you have two Vent Masters, and two Power Vents you would need
to set the first Vent Master to be address 1, the second Vent Master to address 2,
the first Power Vent to address 3, and the second Power Vent to address 4. Valid
settings are 1 - 32. (You do not have to address the controllers in any particular
order.)
P41 -- Version Number
This is not settable. It is the version of controller software.
P42 -- Controller Type
This is not settable. It is a unique number that allows the network software
(Farm Manager) to know the type controller.
8.7 Cool Timer Settings (ON/OFF Stages Only)
The following two settings allow the user to set the Runtime range for their cool timer stages.
These settings apply to the cool timers on the On/Off stages only.
P70 = Cool Timer Maximum Percentage
This sets the maximum Runtime percentage that a cool timer stage can operate.
P71 = Cool Timer Minimum Percentage
This sets the minimum Runtime percentage that a cool timer stage can operate.
8.8 Sensor Calibration
The Vent Master has four sensors that may be calibrated. The parameter(s) for calibration are PSx
with x being the sensor number. The sensor temperature reading is alternately displayed along
Part No. 4801-5098 Farm Hand Vent Master 13
with the parameter number. You should never attempt to calibrate a sensor more than 8 degrees.
If you have a setting that far out of range, it indicates that there is a problem that should be
corrected.
PS1 - Calibrate Sensor 1
This reading can be changed by pressing the + or - button until the desired
reading is displayed.
PS2 - Calibrate Sensor 2
This reading can be changed by pressing the + or - button until the desired
reading is displayed.
PS3 - Calibrate Sensor 3
This reading can be changed by pressing the + or - button until the desired
reading is displayed.
PS4 - Calibrate Sensor 4
This reading can be changed by pressing the + or - button until the desired
reading is displayed.
9. Rarely Changed Settings
Settings which are rarely, or never, changed are found on two banks of switches located inside the front
panel of the controller. The left hand bank of switches is for Tunnel Control, and the right hand bank of
switches controls the status of the controller. When a switch is up it is ON, when a switch is down it is
OFF. The functions of the switches are as follows:
Tunnel Switches
SWX 1 - Tunnel On/Off
This switch is used to enable or disable the tunnel mode of the controller. When
this switch is in the OFF position, the controller will not go into tunnel for any
reason.
SWX 2 - Tunnel On Stage
This switch tells the controller whether it is tunneling off of the lowest
programmed tunnel stage or if it is tunneling off of outside temperature. If this
switch is OFF, the controller will use the “Tunnel On Point” setting for entry
into tunnel.
HIRED-HAND R
V FAN IN V FAN OUT
# 1
Farm Hand Vent Master
Tunnel Switch Bank
Status Switch Bank
Part No. 4801-5098 Farm Hand Vent Master 14
SWX 4 – Split Target Pressures
If SWX 4 is OFF the Target Pressure will be used for both the Vent and Tunnel
machines. If SWX 4 is ON the controller will use the Target Pressure for the
Vent machine and the Tunnel Target Pressure (P22) for the Tunnel machine.
Status Switches
SWX 1 - Lock
This switch is used to lock the controller. When it is on, the user may change
settings such as target temperature and minimum speed/timer percentages but
they can not change the settings in program mode. If the switch is set to ON the
program settings are locked.
SWX 2 – English/Metric Units
This switch toggles between the use of English or Metric units. For English, the
temperatures are displayed in Fahrenheit and the pressure is displayed in inches
of water column (“ w.c.). For Metric units, the temperature is displayed in
Celsius and the pressure is displayed in Pascals or millimeters of water (mm
H2O) depending on the setting of SWX 6. (Note: If SWX 2 is changed, you
will have to reset your tunnel on points and OffPoints and your target
temperature.)
SWX 3 - 5/10 minute timer
This switch selects between a 5 and 10 minute system timer. If the switch is
ON, the timer is 10 minutes.
SWX 4 - Sensor 3 Active
This switch turns off sensor 3. If the switch is off, sensor 3 is turned off.
Note: This is used to disable the sensor in the back half of a half house
brooding situation. This way the low temperature reading does not affect the
temperature readings for the rest of the house. Just be sure that Sensor 3 is
placed in the non-brood end of the house. If the switch is ON, sensor 3 is used.
SWX 5 – Split Vent Units
If SWX 5 is ON, PowerTrak #1 will control the Vents and PowerTrak #2 will
control the Tunnel mode. If SWX 5 is OFF, PowerTrak #1 and PowerTrak #2
will always work together to maintain static pressure.
SWX 6 - Pascals/mm H2O
If SWX 2 is set for Metric units, and SWX 6 is set to ON, pressure is displayed
in millimeters of water (mm H2O). If SWX 6 is set to OFF, the pressure is
displayed in Pascals.
SWX 7 – Initialize Defaults
This switch is not implemented and must remain in the OFF position.
SWX 8 - Program ‘A’ or ‘B’
This switch is used to toggle between 2 preset programs. This could be used to
store separate summer/winter programs for instance. The ON position is for
Program A, and the OFF position is for Program B.
Part No. 4801-5098 Farm Hand Vent Master 15
10. Controller Installation and Setup
Tools Required
Mini Screwdriver Standard Screwdriver
Wire Strippers
Installation Instructions
1. Unpack system, and check that all components are present.
1 Farm Hand Vent Master
1 Installation Kit
1 Fuse Kit
4 Sensors
1 Static Pressure Monitor
1 Manual
2. Hang Farm Hand Vent Master with four screws.
3. Make sure all power supplies are disconnected before breaking any wires, or reaching
into the enclosure.
4. Open the Vent Master and find all connections. Refer to wiring diagrams in back of this
manual.
5. Run sensors out to locations inside the house. (Outside sensor should be installed outside
the house.) Be sure that the sensors are in a safe location, free from any temperature
influences (direct sunlight, water, etc.) Use care when securing sensor wires so that you
do not cut the wire. Any short, or break in the wire will cause improper sensor operation.
6. Connect each sensor to its appropriate terminals inside the enclosure. (See wiring
diagrams in the back of this manual.)
7. Connect wires from stage terminals to the contactor panel, or relay box. See wiring
diagrams for locations of terminals.
8. Hookup three wire connections from Vent Master board to the vent machines. See
wiring diagrams for locations of terminals.
9. Connect the remote pressure unit.
10. CHECK THE POSITION OF THE VOLTAGE SELECTOR SWITCH. Connect
the wires for 120/240V power to the terminals specified in the wiring diagram.
11. Programming Examples
When following these examples, you will need to refer to the Program Reference section to see which
options are available for each of the parameters (P1, P24, etc.).
11.1 Setting Stage OnPoints and OffPoints
OnPoint and OffPoint are easily set by pressing the numbered button on the left hand side of the
front panel. When you press one of the stage buttons, the main display will show “ON”. Then use
the + and - buttons until you see your setting in the individual stage display. (The stage display
you are adjusting will flash until you press the stage button again.) If you want to program all the
stages OnPoints, you may do so by clicking on another stage’s button, then using the + and -
buttons.
Press the stage button again, and the main display will show “OFF” adjust the OffPoint just like
you did the on point. When you are finished, press the stage button again, and you will return to
normal operation. Repeat this process for each of the twelve stages.
Part No. 4801-5098 Farm Hand Vent Master 16
11.2 Setting up Stage Modes, and Timer Status
There are three parameters used in programming any stage. They are P1-P3. The following is an
overview of how to program a stage:
1. Enter Program Mode by pressing and holding the Mode button for 5 seconds until
P1 is displayed, and the stage 1 display begins to flash. This parameter selects the
sensor(s) that this stage watches for on/off operation.
2. Select the stage you want to program by pressing the stage button (next to the stage
display.)
3. Press the + or - button until the desired sensor is displayed. 100= sensor 1; 020 =
sensor 2; 120 = Average of Sensors 1& 2; 003 = Sensor 3; 103 = Average of Sensors
1 & 3; 023 = Average of Sensors 2 & 3; 123 = Average of Sensors 1,2,& 3. If you
want to program more stages sensors, press the next stage’s button, and repeat step
3.
4. Press the Mode button again and P2 is shown. This parameter selects what mode the
stage operates as.
5. Press the + or - button until the desired mode is displayed.
6. If you want to program more stages modes, press the next stage’s button, and repeat
step 6.
7. Press the Mode button until P3 is displayed. This parameter allows you to put a
stage on the system timer (5 or 10 minutes).
8. Press the + or - button until the desired setting is displayed.
9. If you want to program more stages stage timer settings, press the next stage’s
button, and repeat step 9.
10. Exit Program Mode by pressing the Mode button until after PS4 has been displayed
or wait 1 minute.
11.3 Setting Up Tunnel Control
Note: If you do not want the controller to ever enter tunnel mode just make sure that the Tunnel
On/Off switch is in the off position and you can ignore this section.
The Vent Master is a very versatile tunnel controller. It provides the grower with many different
ways to tunnel based on the layout of the house. It also provides two different ways of initiating
tunnel mode. The following are some tips and examples of setting up this controller to tunnel
your house appropriately.
1. The first step in setting up your tunnel house is to configure the stages that you want as your
cool tunnel stages. If some stages need to operate in tunnel mode and in normal mode, then
program these stages to be cool negative tunnel stages. See the Program Reference section
in the back of this manual for more information on the operation of various stage modes.
2. The next step is to determine if you would like to operate your building at a different static
pressure while in tunnel. If so, you must set the Split Target switch (Tunnel Switch SWX 4)
to ON. Then set the desired tunnel pressure with P22.
3. The last step in setting up your tunnel house is determining how you would like to initiate
tunnel mode. You can initiate tunnel mode by outside temperature or by your lowest
programmed cool tunnel stage. The lowest programmed cool tunnel stage is determined by
the lowest OnPoint. If you would like to tunnel based on outside temperature you must set
the Tunnel On Stage (SWX-2) switch to off. You can then set the temperature at which you
would like to enter tunnel mode at P25 and the temperature at which you would like to exit
tunnel mode at P26. Otherwise, set the Tunnel On Stage (SWX-2) to ON.
Part No. 4801-5098 Farm Hand Vent Master 17
11.4 Cool Timer Stage Operation
On the Farm Hand Vent Master any of the ON/OFF can be placed on a cool timer. A cool timer
stage will come on and run at the timer percentage whenever temperature is above it’s OffPoint
(Off), and its timer percentage will increase as temperature rises. The following graph shows how
you can vary this percentage.
Refer to Graph 1 and Table 1. The stage is placed on a cool timer by setting P3=2. A Cool Timer
stage always varies its runtime based on the stage's temperature and its ON and OFF settings. In
this example, the OffPoint is set to 80ºF (OFF=80), and the OnPoint is set to 86ºF (ON=86). The
stage will not run if the temperature is below the OffPoint, as shown in Graph 1. When the
temperature reaches the OffPoint, the stage is placed on the system timer.
To enhance temperature control, the Runtime percentage of a cool timer stage can be varied. The
percentage of the Runtime that the cool timer stage is ON can be varied when the temperature is
between the OffPoint and the OnPoint by setting parameters P70 and P71. In this example, the
Minimum Runtime percentage is 50%, as set by P71 = 50. The Maximum Runtime percentage is
90%, as set by P70 = 90.
When the temperature reaches 80º F the stage runs for 50% of the Runtime period (2-1/2 minutes
if the system timer is set for 5 minutes, or 5 minutes if the system timer is set for 10 minutes). As
the temperature increases, the Runtime percentage of the stage progressively increases up to the
Maximum Runtime percentage of 90% when the temperature reaches 86º F. Above 86ºF, the
Runtime percentage remains constant at 90%.
Table 1 Example Of Cool Timer Stage Operation
Brief Description Of Cool Timer Stage Operation
As you can see, a stage will be placed on the system timer once the temperature rises above 80ºF
(OFF) and will start running 50% (P71) of the time. If the temperature continues to increase then
the run time percentage will also increase toward 90% (P70).
Setting Stage Sensor Stage Mode Stage Timer OffPoint OnPoint Cool Timer
Max % Cool Timer
Min %
Parameter P1 P2 P3
OFF ON P70 P71
Value 10 02 02 80 86 90 50
Option Sensor 1 Cool Stir Timer ON Minimum
OnPoint Maximum
OnPoint Maximum
Runtime % Minimum
Runtime %
75 80 85 90
Runtime Percentage
Graph 1 ON/Off Stages
86ºF
OnPoint
90
50 80º F
OffPoint
Tem
p
erature
(
F
)
Part No. 4801-5098 Farm Hand Vent Master 18
11.5 Variable Speed Stage Operation
Depending on the Farm Hand Vent Master model, you have 0 or 2 variable stages. The Variable stages
can be used in one of two ways: Variable Speed or Progressive Cool Timer. The two options are selected
by the parameters P3. The following sections explain the operation of both options.
11.5.1 Variable Speed Stage Operation (Variable Stage Model Only)
Note: This option applies to stages 1 and 2 of the Variable Stage Farm Hand Vent Master.
The variable speed option (P3=0) allows the user to configure the variable stage to vary the speed of the
fan for their minimum ventilation needs. The following explains the setup and operation.
In this case, the stage timer setting is P3=0 to indicate variable speed operation. The Minimum OnPoint
(OFF) is set for 75ºF, and the Maximum OnPoint (ON) is set for 80ºF. This establishes the temperature
range (75º-80º) over which the speed is varied. The variable speed percentage is set by the "Var/Timer
Pct." parameter as described in Section 5.1. In this example, Var/Timer Pct. is set to 50%. The Minimum
Runtime percentage is set to 40% (P10=40).
Below 75ºF, a fan connected to the variable speed stage will run at 50% speed for 40% of the system timer
(either 2 minutes for a 5 minute timer, or 4 minutes for a 10 minute timer). When the temperature reaches
75ºF, the fan will run at minimum speed (50%) continuously. As the temperature increases, the fan speed
progressively increases from 50% up to 100% at 80ºF. Above 80ºF, the fan runs continuously at its
maximum speed.
Table 2 Example Of Variable Speed Fan Control
Brief Description Of Variable Speed Fan Control
From the graph, you can see that at 78F, the variable speed fan will run at 70% of maximum
speed. Below 75F the variable speed fan will run at it’s minimum speed, for the minimum timer
percentage (P10). Above 80F the variable speed fan will run at 100% continuously.
Percent
Of Runtime Percent Of
Full Speed
100
50
50
100
76 78 8077
75 79
TEMPERATURE
(
F
)
Graph 2 Variable Speed Fan
Minimum OnPoint
Minimum Speed Maximum
Maximum Speed
Setting Stage
Sensor Stage
Mode Stage
Timer Minimum
OnPoint Maximum
OnPoint Minimum
Runtime % Motor
Curve Var/Timer
Percentage
Parameter P1 P2 P3 OFF ON P10 P11 N/A
Value 10 02 00 75 80 40 0 50
Option Sensor 1 Cool Stir No Timer Fan begins
Varying
Speed
Fan begins
Maximum
Speed
Runtime
40% Standard
single
phase
Refer to
Section 5.1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42