D100256XUS2
Installation Guide
English – November 2009
Types 95H and 95HD
www.sherregulators.com
Introduction
This installation guide provides instructions
for installation, startup, and adjustment. To
receive a copy of the instruction manual, contact
your local Sales Ofce or view a copy at
www.sherregulators.com. For further information
refer to:
Types 95L and 95H instruction manual (form 1151,
D100256X012) or Types 95LD and 95HD instruction
manual (form 1396, D100257X012).
P.E.D. Categories
This product may be used as a safety accessory
with pressure equipment in the following Pressure
Equipment Directive 97/23/EC categories. It may
also be used outside of the Pressure Equipment
Directive using sound engineering practice (SEP)
per table below.
PRODUCT SIZE CATEGORIES FLUID TYPE
DN 25 / NPS 1/4 to 1 SEP
1
DN 40 to 50 / NPS 1-1/2 to 2 I, II
Specications
Available Constructions
Type 95H: High-pressure regulator for 0,34 to
10,3 bar / 5 to 150 psig outlet pressures. DN 15,
20, 25, 40, and 50 / NPS 1/4, 1/2, 3/4, 1, 1-1/2,
and 2 body sizes are available in cast iron, steel,
or stainless steel.
Type 95HD: High-pressure differential regulator
for 0,34 to 10,3 bar / 5 to 150 psi differential
pressures. DN 15, 20, 25, 40, and 50 / NPS 1/4,
1/2, 3/4, 1, 1-1/2, and 2 body sizes are available
in cast iron, steel, or stainless steel.
Maximum Inlet and Outlet Pressures
(1)(3)
Cast Iron: 17,2 bar / 250 psig
Steel and Stainless Steel: 20,7 bar / 300 psig
Proof Test Pressure
All Pressure Retaining Components have been
proof tested per Directive 97/23/EC - Annex 1,
Section 7.4
Outlet Pressure Ranges
(1)
DN 15, 20, and 25 / NPS 1/4, 1/2, 3/4, and 1:
1,0 to 2,1 bar / 15 to 30 psig; 1,7 to 5,2 bar / 25
to 75 psig; and 4,8 to 10,3 bar / 70 to 150 psig
DN 40 and 50 / NPS 1-1/2 and 2: 0,34 to
5,5 bar / 5 to 80 psig; 4,1 to 8,3 bar / 60 to
120 psig; 6,9 to 9,7 bar / 100 to 140 psig; and
8,3 to 10,3 bar / 120 to 150 psig
Temperature Capabilities
(1)(2)
Elastomer Parts
Nitrile (NBR)/Neoprene (CR): -40° to 82°C /
-40° to 180°F
Fluorocarbon (FKM): -18° to 149°C / 0° to 300°F;
hot water limited to 93°C / 200°F
Ethylenepropylene (EPDM): -40° to 135°C /
-40° to 275°F
Polytetrauoroethylene (PTFE): -40° to 204°C /
-40° to 400°F
Peruoroelastomer (FFKM): -18° to 218°C /
0° to 425°F
Metal Parts
Cast Iron: -40° to 208°C / -40° to 406°F
Steel: -29° to 232°C / -20° to 450°F
Stainless Steel: -40° to 232°C / -40° to 450°F
Installation
WARNING
Only qualied personnel should install
or service a regulator. Regulators
should be installed, operated, and
maintained in accordance with
international and applicable codes and
regulations, and Emerson Process
Management Regulator Technologies,
Inc. instructions.
If the regulator vents uid or a leak
develops in the system, it indicates that
service is required. Failure to take the
regulator out of service immediately may
create a hazardous condition.
Personal injury, equipment damage,
or leakage due to escaping uid
or bursting of pressure-containing
parts may result if this regulator is
overpressured or is installed where
service conditions could exceed
the limits given in the Specications
section, or where conditions exceed
any ratings of the adjacent piping or
piping connections.
To avoid such injury or damage,
provide pressure-relieving or
pressure-limiting devices (as required
by the appropriate code, regulation,
or standard) to prevent service
conditions from exceeding limits.
1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.
2. Pressures and/or the body end connection may decrease these maximum temperatures.
3. Temperature and/or the body end connection may decrease these maximum pressures.