  • Hello! I am an AI chatbot trained to assist you with the Generac 11 kW G0070331 User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
8
A
7 6 5 4 3 2 1
B
C
D
A
B
C
D
8 7 6 5 4 3 1
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
635
[25.0]
733
[28.8]
648
[25.5]
218
[8.6]
345
[13.6]
COMPACTED SOIL
GRAVEL PAD/
127 [5.0]
521
[20.5]
197
[7.7]
849
[33.4]
68
[2.7]
393
[15.5]
679
[26.8]
768
[30.2]
267
[10.5]
356
[14.0]
1218
[48.0]
1232
[48.5]
914 [36.0]
MINIMUM OPEN AREA
457 [18.0]
MINIMUM OPEN AREA
914 [36.0]
MINIMUM OPEN AREA
914 [36.0]
MINIMUM OPEN AREA
SH
1/1
REV
B
WINDCHILL VERSION
B.15
FIRST USE: G0070432
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
TITLE
INSTALL HSB GENERATOR WM 60HZ
ISSUE DATE: 12/19/16
SIZE CAGE NO DWG NO
10000010258
REV
B
N/A
B
SCALE
NTS
WT-KG N/A SHEET
1 of 1
AIR OUTLET
AIR INTAKE
AIR INTAKE
TOP VIEW
ALL DIMENSIONS IN:
MILLIMETERS [INCHES]
LEFT SIDE VIEW
RIGHT SIDE VIEW
REAR VIEW
RIGHT VIEW
INTAKE PANEL REMOVED
FUEL INLET : 1/2" NPT (9-11kW)
: 3/4" NPT (16-22kW)
REQUIRED FUEL PRESSURE : NATURAL GAS : 3.5-7" WATER COLUMN
LIQUID PROPANE (VAPOR) : 10-12" WATER COLUMN
MAIN AC/CONTROL WIRING HOLE FOR 3/4" CONDUIT
MAIN AC/CONTROL WIRING HOLE FOR 1 1/4" CONDUIT
"DO NOT LIFT BY ROOF"
LIFTING HOLES 4 CORNERS: 30 [ 1.2]
- MUST BE LIFTED WITH STEEL RODS
- RECOMMENDED LIFTING ROD SIZE: 25 [ 1.0]
FRONT VIEW
BOLTS RECOMMENDED
10 [3/8] DIA. MASONRY ANCHOR
HOLE (3) PLACES,
16 [5/8] DIA. CLEARANCE
A CONCRETE PAD
OPTIONAL MOUNTING TO
HOLE LOCATIONS FOR
FRONT OF UNIT
MOUNTING TO CONCRETE PAD
TRANSFER SWITCH
(IF SUPPLIED)
WIRELESS MODULE
AUXILIARY SHUTDOWN SWITCH
-REMOVE FACTORY PLUGS AND DISCARD
-CLOSE ANY UNUSED HOLE WITH A NEMA
3R RATED PLUG (FIELD SUPPLIED)
(
)
/