LG AUUQ48GH2 Installation guide

Category
Split-system air conditioners
Type
Installation guide
P/NO : MFL67448519
www.lg.com
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
ENGLISH ESPAÑOL
PORTUGUESE
2
TIPS FOR SAVING ENERGY
ENGLISH
• Do not cool excessively indoors. This may be harmful to your health and may consume more elec-
tricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condition-
er is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them labeled on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
TIPS FOR SAVING ENERGY
IMPORTANT SAFETY INSTRUCTIONS
3
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation work must be performed in accordance with the National Electric Code by quali-
fied and authorized personnel only.
• The information contained in the manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal-
function, property damage, personal injury and/or death.
Installation
• Always perform grounding. Otherwise, it may cause electrical shock.
• Don’t use a power cord, a plug or a loose socket which is damaged. Otherwise, it may cause a fire
or electrical shock.
• For installation of the product, always contact the service center or a professional installation
agency. Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor unit.
If the electrical part cover of the indoor unit and the service panel of the outdoor unit are not
attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an air leakage breaker and a dedicated switching board. No installation may cause a
fire and electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner. Otherwise, it may
cause a fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long time.
It may cause injury or an accident.
• Do not disassemble or repair the product randomly. It will cause a fire or electrical shock.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress
air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
There is the risk of death, injury, fire or explosion.
• Do not install the product at a place that there is concern of falling down. Otherwise, it may result in
personal injury.
• Use caution when unpacking and installing. Sharp edges may cause injury.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box
cover are removed or opened. Otherwise, it may cause fire, electric shock, explosion or death.
!
!
!
4
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
Operation
• Do not share the outlet with other appliances. It will cause an electric shock or a fire due to heat
generation.
• Do not use the damaged power cord. Otherwise, it may cause a fire or electrical shock.
• Do not modify or extend the power cord randomly. Otherwise, it may cause a fire or electrical
shock.
• Take care so that the power cord may not be pulled during operation. Otherwise, it may cause a fire
or electrical shock.
• Unplug the unit if strange sounds, smell, or smoke comes from it. Otherwise, it may cause electrical
shock or a fire.
• Keep the flames away. Otherwise, it may cause a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet
hands. Otherwise, it may cause a fire or electrical shock.
• Do not use the power cord near the heating tools. Otherwise, it may cause a fire and electrical
shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation.
Otherwise, it may electrical shock and failure.
• Do not allow water to run into electrical parts. Otherwise, it may cause the failure of machine or
electrical shock.
• Hold the plug by the head when taking it out. It may cause electric shock and damage.
• Never touch the metal parts of the unit when removing the filter. They are sharp and may cause
injury.
• Do not step on the indoor/outdoor unit and do not put anything on it. It may cause an injury through
dropping of the unit or falling down.
• Do not place a heavy object on the power cord. Otherwise, it may cause a fire or electrical shock.
• When the product is submerged into water, always contact the service center. Otherwise, it may
cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit. Otherwise, children may be seriously
injured due to falling down.
CAUTION
Installation
• Install the drain hose to ensure that drain can be securely done. Otherwise, it may cause water leak-
age.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any damage to
the neighbors. Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product. Otherwise, it may cause the
failure of product.
• Keep level parallel in installing the product. Otherwise, it may cause vibration or water leakage.
Operation
• Avoid excessive cooling and perform ventilation sometimes. Otherwise, it may do harm to your
health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent. The appearance of the air
conditioner may deteriorate, change color, or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision
machine, or art articles. Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet. Otherwise, it may cause the failure of appli-
ance or an accident.
!
TABLE OF CONTENTS
5
ENGLISH
2
TIPS FOR SAVING ENERGY
3 IMPORTANT SAFETY
INSTRUCTIONS
6 INSTALLATION OF OUT-
DOOR UNIT
9 Night Silent Operation setting
10 WIRING CONNECTION
10 Electrical Wiring
11 Connecting Cables between Indoor Unit
and Outdoor Unit
13 Connecting the cable to Outdoor Unit
14 CONNECTING PIPES
14 Preparation of Piping
15 Connecting the pipes to the Outdoor
unit
16 Forming the piping
17 LEAKAGE TEST AND
EVACUATION
17 Preparation
17 Leakage test
18 Evacuation
19 TEST RUNNING
21 FUNCTION
21 Forced Cooling Operation
22 SELF-DIAGNOSIS FUNC-
TION
22 Error Indicator (Outdoor)
24 INSTALLATION GUIDE AT
THE SEASIDE
TABLE OF CONTENTS
6
INSTALLATION OF OUTDOOR UNIT
ENGLISH
- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows around front, back and side of the unit.
- Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are
minimum.
- Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
More than
300mm
Fence or
obstacles
More than 700mm
More than 600mm
More thanMore than
300mm300mm
More than
300mm
Sunroof
Unit : mm
Installation Places
MODEL CAPACITY
Pipe Size Length A (m) Elevation B (m)
Additional
Refrigerant
(g/m)
Gas Liquid Standard Max. Standard Max.
AUUQ18GH2 5kW Ø12.7(1/2) Ø6.35(1/4) 5 30 5 15 20
AUUQ24GH2 7kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
AUUQ36GH2 10kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
AUUQ48GH2 13.4kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
AUUQ54GH2 15.8kW Ø19.05(3/4) Ø9.52(3/8) 5 50 5 30 20
Free Joint Single Outdoor
Piping length and the elevation
INSTALLATION OF OUTDOOR UNIT
INSTALLATION OF OUTDOOR UNIT
7
ENGLISH
MODEL CAPACITY
Pipe Size Length A (m) Elevation B (m)
Additional
Refrigerant
(g/m)
Gas Liquid Standard Max. Standard Max.
ATUQ18GPLE5
ATUQ18GQLE5
5kW Ø12.7(1/2) Ø6.35(1/4) 5 30 5 15 20
ATUQ24GPLE5
ATUQ24GQLE5
7kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
ATUQ36GPLE5 10kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
ATUQ48GMLE5 13.4kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
ATUQ54GMLE5 15.8kW Ø19.05(3/4) Ø9.52(3/8) 5 50 5 30 20
MODEL CAPACITY
Pipe Size Length A (m) Elevation B (m)
Additional
Refrigerant
(g/m)
Gas Liquid Standard Max. Standard Max.
AVUQ18GJLA2 5kW Ø12.7(1/2) Ø6.35(1/4) 5 30 5 15 20
AVUQ24GJLA2 7kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
AVUQ36GKLA2 10kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
AVUQ48GLLA2 13.4kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
AVUQ54GLLA2 15.8kW Ø19.05(3/4) Ø9.52(3/8) 5 50 5 30 20
Ceiling Cassette
Ceiling Suspended Air conditioner
MODEL CAPACITY
Pipe Size Length A (m) Elevation B (m)
Additional
Refrigerant
(g/m)
Gas Liquid Standard Max. Standard Max.
APUQ36GRA2 10kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
APUQ48GTA2 13.4kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
Floor Standing Air Conditioner
MODEL CAPACITY
Pipe Size Length A (m) Elevation B (m)
Additional
Refrigerant
(g/m)
Gas Liquid Standard Max. Standard Max.
ABUQ18GM1A2
ABUQ18GL2A1
5kW Ø12.7(1/2) Ø6.35(1/4) 5 30 5 15 20
ABUQ24GM1A2
ABUQ24GL3A1
7kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
ABUQ36GM2A2 10kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
ABUQ48GM3A2 13.4kW Ø15.88(5/8) Ø9.52(3/8) 5 50 5 30 20
ABUQ54GM3A2 15.8kW Ø19.05(3/4) Ø9.52(3/8) 5 50 5 30 20
Ceiling Concealed Duct
Ceiling Concealed Duct – Low Static
8
INSTALLATION OF OUTDOOR UNIT
ENGLISH
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
• Capacity is based on standard length and maximum allowance length is on the basis of
reliability.
• Improper refrigerant charge may result in abnormal cycle.
CAUTION
!
If installed tube is shorter than 15 m, additional charging is not necessary.
Additional Refrigerant = (A -15) x Additional refrigerant (g)
INSTALLATION OF OUTDOOR UNIT
9
ENGLISH
Unless the applicable dip switch is set properly, the product may not work.
If you want to set a specific function, request that the installer sets the dip switch appro-
priately during installation.
CAUTION
!
Night Silent Operation setting
- Open the Side panel or Top Cover of outdoor unit.
- Set the SW1 or DIP-SW01D.
AUUQ36GH2
ATUQ36GPLE5
ABUQ36GM2A2
AVUQ36GKLA2
APUQ36GRA2
AUUQ48GH2 / AUUQ54GH2
ATUQ48GMLE5 / ATUQ54GMLE5
ABUQ48GM3A2 / ABUQ54GM3A2
AVUQ48GLLA2 / AVUQ54GLLA2
APUQ48GTA2
6 7 8 9 10
6 7 8 9 10
SW1
DIP–SW01D
6 7 8 9 10
- Close the Side panel or Top Cover.
• When you set the dip switch, you should turn off the circuit breaker or shut the power
source of the product down.
WARNING
!
Step 1
Step 2
10
WIRING CONNECTION
ENGLISH
Electrical Wiring
Perform the electrical wiring work according
to the electrical wiring connection.
- All wiring must comply with local require-
ments.
- Select a power source that is capable of sup-
plying the current required by the air condi-
tioner.
- Use a recognized ELCB(Electric Leakage
Circuit Breaker) between the power source
and the unit. A disconnection device to ade-
quately disconnect all supply lines must be
fitted.
- Model of circuit breaker recommended by
authorized personnel only
Outdoor
Indoor
Main
power source
Switch box
ELCB
Model Phase(Ø) ELCB
AUUQ18GH2
ATUQ18GPLE5 / ATUQ18GQLE5
ABUQ18GM1A2 / ABUQ18GL2A1
AVUQ18GJLA2
1 20A
AUUQ24GH2
ATUQ24GPLE5 / ATUQ24GQLE5
ABUQ24GM1A2 / ABUQ24GL3A1
AVUQ24GJLA2
1 25A
AUUQ36GH2
ATUQ36GPLE5 / ABUQ36GM2A2
AVUQ36GKLA2 / APUQ36GRA2
1 30A
AUUQ48GH2
ATUQ48GMLE5 / ABUQ48GM3A2
AVUQ48GLLA2 / APUQ48GTA2
1
40A
AUUQ54GH2
ATUQ54GMLE5 / ABUQ54GM3A2
AVUQ54GLLA2
1
WIRING CONNECTION
WIRING CONNECTION
11
ENGLISH
Connecting Cables between Indoor Unit and Outdoor Unit
Outdoor
unit
Indoor
unit
1
2
3
1
2
3
The power cord connected to the outdoor unit should be complied withIEC 60245 or HD 22.4
S4 (This equipment shall be provided with a cord set complying with the national regulation.
The connecting cable connected to the outdoor unit should be complied with IEC 60245 or
HD 22.4 S4 (This equipment shall be provided with a cord set complying with the national
regulation.)
If the supply cord is damaged, it must be replaced by a special cord or assembly availible
from the manufacturer of its service agent.
When the connection line between the indoor unit and out-
dooor unit is over 40m, connect the telecommunication line
and power line separately.
CAUTION
!
GN/YL
20mm
35±5mm
10±3mm
NORMAL
CROSS-SECTIONAL
AREA 0.75mm
2
20mm
GN/YL
35±5mm
10±3mm
Model Phase(Ø) Area(mm
2
)
AUUQ18GH2 / ATUQ18GPLE5 / ATUQ18GQLE5
ABUQ18GM1A2 / ABUQ18GL2A1 / AVUQ18GJLA2
AUUQ24GH2 / ATUQ24GPLE5 / ATUQ24GQLE5
ABUQ24GM1A2 / ABUQ24GL3A1 / AVUQ24GJLA2
AUUQ36GH2 / ATUQ36GPLE5 / ABUQ36GM2A2
AVUQ36GKLA2 / APUQ36GRA2
1 2.5
AUUQ48GH2 / ATUQ48GMLE5 / ABUQ48GM3A2
AVUQ48GLLA2 / APUQ48GTA2
AUUQ54GH2 / ATUQ54GMLE5 / ABUQ54GM3A2
AVUQ54GLLA2
16
12
WIRING CONNECTION
ENGLISH
Use round pressure terminals for connections to the power terminal block.
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power
wiring may cause abnormal heat.)
- When connecting wiring which is the same thickness, do as shown in the figure below.
- For wiring, use the designated power wire and connect firmly, then secure to prevent outside
pressure being exerted on the terminal block.
- Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small
head will strip the head and make proper tighterning impossible.
- Over-tightening the terminal screws may break them.
Precautions when laying power wiring
WIRING CONNECTION
13
ENGLISH
Connecting the cable to Outdoor Unit
Remove the side panel for wiring connection.
Use the cord clamp to fix the cord.
Earthing work
- Connect the cable of diameter more to the earthing terminal provided in the control box and do
earthing.
Connecting cable terminal
Power cord terminal
Cord clamp
* Make sure the rubber bushes are
properly used in knock-out holes after
connecting main power.
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring the wiring diagram.
• The Power cord connected to the unit should be selected according to the following speci-
fications.
CAUTION
!
14
CONNECTING PIPES
ENGLISH
Preparation of Piping
Main cause of gas leakage is defect in flaring work.
Carry out correct flaring work in the following procedure.
Cut the pipes and the cable.
- Use the accessory piping kit or the pipes pur-
chased locally.
- Measure the distance between the indoor
and the outdoor unit.
- Cut the pipes a little longer than measured
distance.
- Cut the cable 1.5m longer than the pipe
length.
Burrs removal
- Completely remove all burrs from the cut
cross section of pipe/tube.
- Put the end of the copper tube/pipe to down-
ward direction as you remove burrs in order
to avoid to let burrs drop in the tubing.
Putting nut on
- Remove flare nuts attached to indoor and
outdoor units, than put them on pipe/tube
having completed burr removal.
(Not possible to put them on after flaring
work)
Flaring work
- Carry out flaring work using dedicated flaring
tool for R-410A as shown below.
Firmly hold copper tube in a bar(or die) as
indicated dimension in the table above.
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the
flared section and do flaring work again.
Copper
tube
90°
Slanted Uneven Rough
Pipe
Reamer
Point down
Flare nut
Copper tube
Bar
Copper pipe
Clamp handle
Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Inclined
Inside is shining without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Outside diameter
A
mm inch mm
Ø 6.35 1/4 1.1~1.3
Ø 9.52 3/8 1.5~1.7
Ø 12.7 1/2 1.6~1.8
Ø 15.88 5/8 1.6~1.8
Ø 19.05 3/4 1.9~2.1
CONNECTING PIPES
CONNECTING PIPES
15
ENGLISH
Connecting the pipes to the Outdoor unit
Align the center of the piping and sufficiently
tighten the flare nut by hand.
Finally, tighten the flare nut with torque
wrench until the wrench clicks.
- When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
Preventing foreign objects from entering
- Plug the pipe through-holes with putty or
insulation material(procured locally)to stop up
all gaps.
Torque
wrench
Contin
-uous
Gas side piping
Liquid side piping
Drain hose
Connecting wire
h When tighten the pipe, hold the haxago-
nal body.
Outside diameter
Torque
mm inch N·m
Ø 6.35 1/4 16±2
Ø 9.52 3/8 38±4
Ø 12.7 1/2 55±6
Ø 15.88 5/8 75±7
Ø 19.05 3/4 110±10
Insects or small animals entering the outdoor unit may cause a short circuit in the electrical
box.
CAUTION
!
16
CONNECTING PIPES
ENGLISH
Forming the piping
Form the piping by wrapping the connecting
portion of the indoor unit with insulation mate-
rial and secure it with two kinds of vinyl tape.
- If you want to connect an additional drain
hose, the end of the drain outlet should be
routed above the ground. Secure the drain
hose appropriately.
In cases where the outdoor unit is installed
below the indoor unit perform the following.
1 Tape the piping, drain hose and connecting
cable from down to up.
2 Secure the tapped piping along the exterior
wall using saddle or equivalent.
• Trap is required to prevent water from entering
into electrical parts.
Taping
Drain hose
Pipings
Connecting
cable
Power supply
cord
Plastic
Plastic
band
band
Plastic
band
Seal a small
Seal a small
opening around
opening around
the pipings with
the pipings with
gum type sealer.
gum type sealer.
Seal a small
opening around
the pipings with
gum type sealant.
In cases where the outdoor unit is installed
above the indoor unit perform the following.
1 Tape the piping and connecting cable from
down to up.
2 Secure the taped piping along the exterior
wall. Form a trap to prevent water entering
the room.
3 Fix the piping onto the wall by saddle or
equivalent.
Trap
TrapTrapTrap
Seal a small opening Seal a small opening
around the pipings around the pipings
with gum type sealer.with gum type sealer.
Seal a small opening
around the pipings
with gum type sealant.
LEAKAGE TEST AND EVACUATION
17
ENGLISH
Preparation
Check that each tube(both liquid and gas side
tubes) between the indoor and outdoor units
have been properly connected and all wiring
for the test run has been completed. Remove
the service valve caps from both the gas and
the liquid side on the outdoor unit. Check that
both the liquid and the gas side service valves
on the outdoor unit are kept closed at this
stage.
Leakage test
Connect the manifold valve(with pressure
gauges) and dry nitrogen gas cylinder to this
service port with charge hoses.
CAUTION
Be sure to use a manifold valve for leakage
test. If it is not available, use a stop valve for
this purpose. The "Hi" knob of the manifold
valve must always be kept close.
- Pressurize the system to no more than
3.0 Mpa with dry nitrogen gas and close
the cylinder valve when the gauge read-
ing reached 3.0 MPa Next, test for leaks
with liquid soap.
!
CAUTION
To avoid nitrogen entering the refrigerant
system in a liquid state, the top of the
cylinder must be higher than its bottom
when you pressurize the system. Usually,
the cylinder is used in a vertical standing
position.
!
- Do a leakage test of all joints of the
tubing(both Indoor unit and outdoor unit) and
both gas and liquid side service valves.
Bubbles indicate a leak. Be sure to wipe off
the soap with a clean cloth.
- After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening
the charge hose connector at the nitrogen
cylinder. When the system pressure is
reduced to normal, disconnect the hose from
the cylinder.
Air and moisture remaining in the refrigerant
system have undesirable effects as indicated
below.
- Pressure in the system rises.
- Operating current rises.
- Cooling(or heating) efficiency drops.
- Moisture in the refrigerant circuit may freeze
and block capillary tubing.
- Water may lead to corrosion of parts in the
refrigeration system.
Therefore, the indoor/outdoor unit and con-
necting tube must be checked for leak tight,
and vacuumed to remove incondensible gas
and moisture in the system.
Charge hose
Indoor unit
Outdoor unit
Manifold valve
Pressure
gauge
Nitrogen gas
cylinder(in vertical
standing position)
Lo Hi
LEAKAGE TEST AND EVACUATION
18
LEAKAGE TEST AND EVACUATION
ENGLISH
- When the desired vacuum is reached, close
the "Lo and Hi" knob of the manifold valve
and stop the vacuum pump.
Required time for evacuation when 30 gal/h
vacuum pump is used
If tubing length is
less than 10 m(33 ft)
If tubing length is
longer than 10 m(33 ft)
30 min. or more 60 min. or more
0.07 kPa or less
- With a service valve wrench, turn the valve
stem of liquid side valve counter-clockwise to
fully open the valve.
- Turn the valve stem of gas side valve counter-
clockwise to fully open the valve.
- Loosen the charge hose connected to the gas
side service port slightly to release the pressure,
then remove the hose.
- Replace the flare nut and its bonnet on the gas
side service port and fasten the flare nut secure-
ly with an adjustable wrench. This process is
very important to prevent leakage from the sys-
tem.
- Replace the valve caps at both gas and liquid
side service valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Open
Open
Pressure
gauge
Finishing the job
Evacuation
- Connect the charge hose end described in
the preceding steps to the vacuum pump to
evacuate the tubing and indoor unit.
Confirm the "Lo and Hi" knob of the manifold
valve is open. Then, run the vacuum pump.
The operation time for evacuation varies with
tubing length and capacity of the pump. The
following table shows the time required for
evacuation.
TEST RUNNING
19
ENGLISH
- The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
- The test run is started by pressing the room temperature checking button and down timer but-
ton for 3 seconds at the same time.
- To cancel the test run, press any button.
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
- After completing work, be sure to measure and record trial run properties, and store measured
data, etc.
- Measuring items are room temperature, outside temperature, suction temperature, blow out
temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and
noise, operating pressure, piping temperature, compressive pressure.
- As to the structure and appearance, check following items.
- Connect the power supply cord to the independent power supply.
Circuit breaker is required.
- Operate the unit for fifteen minutes or more.
Precautions In Test Running
Connection of power supply
Evaluation of the performance
CAUTION
For test run, carry out the cooling operation firstly even during heating season. If heating operation
is carried out firstly, it leads to the trouble of compressor. Then attention must be paid.
Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes later automatically)
!
Is the circulation of air adequate?
Is the draining smooth?
Is the heat insulation complete
(refrigerant and drain piping)?
Is there any leakage of refrigerant?
Is the remote controller switch operated?
Is there any faulty wiring?
Are not terminal screws loosened?
M4......118 N·cm {12 kgf·cm}
M5......196 N·cm {20 kgf·cm}
M6......245 N·cm {25 kgf·cm}
M8......588 N·cm {60 kgf·cm}
- Measure the temperature of the intake and discharge air.
- Ensure the difference between the intake temperature and the discharge one is more than 8°C
(Cooling) or reversely (Heating).
TEST RUNNING
20
TEST RUNNING
ENGLISH
CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1 Never fail to have an individual power specialized for the air conditioner. As for the
method of wiring, be guided by the circuit diagram pasted on the inside of control box
cover.
2 Provide a circuit breaker switch between power source and the unit.
3 The screw which fasten the wiring in the casing of electrical fittings are liable to come
loose from vibrations to which the unit is subjected during the course of transportation.
Check them and make sure that they are all tightly fastened. (If they are loose, it could
give rise to burn-out of the wires.)
4 Specification of power source
5 Confirm that electrical capacity is sufficient.
6 Be sure that the starting voltage is maintained at more than 90 percent of the rated volt-
age marked on the name plate.
7 Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8 Never fail to equip a leakage breaker where it is wet or moist.
9 The following troubles would be caused by voltage drop-down.
- Vibration of a magnetic switch, damage on the contact point there of fuse breaking, dis-
turbance to the normal function of a overload protection device.
- Proper starting power is not given to the compressor.
!
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25

LG AUUQ48GH2 Installation guide

Category
Split-system air conditioners
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI