York VRF Low Ambient Heat Pump Outdoor Unit 208/230V User manual

Category
Split-system air conditioners
Type
User manual
SM-16007
SERVICE MANUAL
INVERTER-DRIVEN MULTI-SPLIT SYSTEM
HEAT PUMP AIR CONDITIONERS
Service Manual
< Outdoor Units
(Low Ambient VRF Heat Pump)
>
(H,Y)VAHP072(3,4)1CW
(H,Y)VAHP096(3,4)1CW
(H,Y)VAHP144(3,4)1CW
(H,Y)VAHP168(3,4)1CW
(H,Y)VAHP192(3,4)1CW
(H,Y)VAHP288(3,4)1CW
SM-16007
i
Temperature
Maximum Minimum
Cooling
Operation
Indoor 89
o
F DB/73
o
F WB (32
o
C DB/23
o
C WB) 69
o
F DB/59
o
F WB (21
o
C DB/15
o
C WB)
Outdoor 118
o
F DB (48
o
C DB)
*1), *2)
14
o
F DB (-10
o
C DB)
*3), *4)
Heating
Operation
Indoor 80
o
F DB (27
o
C DB) 59
o
F DB ( 15
o
C DB)
Outdoor 59
o
F WB (15
o
C WB)
*5)
-4
o
F WB (-20
o
C WB)
*6)
DB: Dry Bulb, WB: Wet Bulb
*1) When the outdoor air temperature is 100
o
F DB (38
o
C DB) or more and the outdoor unit operation capacity
ratio is 100% or more, the outdoor unit will be Thermo-OFF to protect the compressor from failure.
*2) When the outdoor air temperature is 109
o
F (43
o
C) or more during the outdoor unit cooling operation, the
maximum connectable indoor unit capacity ratio is 100%.
*3) When the outdoor air temperature is 23
o
F (-5
o
C) or less during the outdoor unit cooling operation, the
minimum connectable indoor unit capacity is 18,000 Btu/h.
In this case, install the snow protection hood (optional).
*4) When operating the outdoor unit under the low cooling load conditions and in the low outdoor air
temperature, (applox. 50
o
F DB (10
o
C DB) or less), the indoor unit will be Thermo-OFF to prevent the heat
exchanger of the indoor unit from being frosted.
*5) When operating the outdoor unit under the low heating load conditions and the outdoor temperature is
59
o
F DB (15
o
C DB) or more, the outdoor unit will be Thermo-OFF to protect the compressor from failure.
*6) Operation in the outdoor temperature of 5~-4
o
F WB (-15~20
o
C WB) is assumed to limited conditions such
as start-up in early morning.
Long time operation in this condition may shorten the life of the compressor.
Important Notice
Ɣ Johnson Controls Inc. pursues a policy of continuing improvement in design and performance in its
products. As such, Johnson Controls Inc. reserves the right to make changes at any time without prior
notice.
Ɣ Johnson Controls Inc. cannot anticipate every possible circumstance that might involve a potential
hazard.
Ɣ This heat pump air conditioning unit is designed for standard air conditioning applications only. Do not
use this unit for anything other than the purposes for which it was intended for.
Ɣ 7KHLQVWDOOHUDQGV\VWHPVSHFLDOLVWVKDOOVDIHJXDUGDJDLQVWOHDNDJHLQDFFRUGDQFHZLWKORFDOSLSH¿WWHU
and electrical codes. The following standards may be applicable, if local regulations are not available.
International Organization for Standardization: (ISO 5149 or European Standard, EN 378). No part of
this manual may be reproduced in any way without the expressed written consent of Johnson Controls
Inc.
Ɣ This heat pump air conditioning unit will be operated and serviced in the United States of America and
comes with a full complement of the appropriate Safety, Danger, and Caution, warnings.
Ɣ If you have questions, please contact your distributor or dealer.
Ɣ This manual provides common descriptions, basic and advanced information to maintain and service
this heat pump air conditioning unit which you operate as well for other models.
Ɣ 7KLVKHDWSXPSDLUFRQGLWLRQLQJXQLWKDVEHHQGHVLJQHGIRUDVSHFL¿FWHPSHUDWXUHUDQJH)RURSWLPXP
performance and long life, operate this unit within the range limits according to the table below.
Ɣ This manual should be considered as a permanent part of the air conditioning equipment and should
remain with the air conditioning equipment.
ii
SM-16007
Product Inspection upon Arrival
1. Upon receiving this product, inspect it for any damages incurred in transit. Claims for damage, either
DSSDUHQWRUFRQFHDOHGVKRXOGEH¿OHGLPPHGLDWHO\ZLWKWKHVKLSSLQJFRPSDQ\
2. Check the model number, electrical characteristics (power supply, voltage, and frequency rating), and
any accessories to determine if they agree with the purchase order.
3. The standard utilization for this unit is explained in these instructions. Use of this equipment for
purposes other than what it designed for is not recommended.
4. Please contact your local agent or contractor as any issues involving installation, performance, or
PDLQWHQDQFHDULVH/LDELOLW\GRHVQRWFRYHUGHIHFWVRULJLQDWLQJIURPXQDXWKRUL]HGPRGL¿FDWLRQV
performed by a customer without the written consent of Johnson Controls, Inc. Performing any
mechanical alterations on this product without the consent of the manufacturer will render your warranty
null and void.
SM-16007
iii
1. Introduction
2. Important Safety Instructions
This manual should be considered as a permanent part of the air conditioning equipment and should
remain with the air conditioning equipment.
(Transportation/Installation Work) > (Refrigerant Piping Work) > (Electrical Wiring Work) > (Ref. Charge Work) > (Test
Run) > (User)
This manual concentrates on the Outdoor Heat Pump Unit. Read this installation and maintenance manual
carefully before installation. Read over the installation manual for the Indoor Unit also.
Signal Words
Indicates a hazardous situation that, if not avoided, could result in death or
serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or
moderate injury.
Indicates information considered important, but not hazard-related (for
example, messages relating to property damage).
General Precautions
To reduce the risk of serious injury or death, read these instructions thoroughly
and follow all warnings or cautions included in all manuals that accompanied
the product and are attached to the unit. Refer back to these safety
instructions as needed.
Ɣ 7KLVV\VWHPVKRXOGEHLQVWDOOHGE\SHUVRQQHOFHUWL¿HGE\-RKQVRQ&RQWUROV,QF3HUVRQQHOPXVWEH
TXDOL¿HGDFFRUGLQJWRORFDOVWDWHDQGQDWLRQDOEXLOGLQJDQGVDIHW\FRGHVDQGUHJXODWLRQV,QFRUUHFW
LQVWDOODWLRQFRXOGFDXVHOHDNVHOHFWULFVKRFN¿UHRUH[SORVLRQ,QDUHDVZKHUH6HLVPLFµ¶3HUIRUPDQFH
UHTXLUHPHQWVDUHVSHFL¿HGWKHDSSURSULDWHPHDVXUHVVKRXOGEHWDNHQGXULQJLQVWDOODWLRQWRJXDUG
against possible damage or injury that might occur in an earthquake if the unit is not installed correctly,
injuries may occur due to a falling unit.
Ɣ Use appropriate Personal Protective Equipment (PPE), such as gloves and protective goggles and,
where appropriate, have a gas mask nearby. Also use electrical protection equipment and tools suited
IRUHOHFWULFDORSHUDWLRQSXUSRVHV.HHSDTXHQFKLQJFORWKDQGD¿UHH[WLQJXLVKHUQHDUE\GXULQJEUD]LQJ
Use care in handling, rigging, and setting of bulky equipment.
Ɣ When transporting, be careful when picking up, moving and mounting these units. Although the unit may
be packed using plastic straps, do not use them for transporting the unit from one location to another. Do
not stand on or put any material on the unit. Get a partner to help, and bend with your knees when lifting
WRUHGXFHVWUDLQRQ\RXUEDFN6KDUSHGJHVRUWKLQDOXPLQXP¿QVRQWKHDLUFRQGLWLRQHUFDQFXW¿QJHUV
so wear protective gloves.
Ɣ Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features,
disengagement, and interlocks must be in place and functioning correctly before the equipment is put
into operation. If these devices are improperly adjusted or tampered with in any way, a serious accident
can occur. Never bypass or jump-out any safety device or switch.
Ɣ Johnson Controls will not assume any liability for injuries or damage caused by not following steps
RXWOLQHGRUGHVFULEHGLQWKLVPDQXDO8QDXWKRUL]HGPRGL¿FDWLRQVWR-RKQVRQ&RQWUROVSURGXFWVDUH
prohibited as they…
ƕ May create hazards which could result in death, serious injury or equipment damage;
ƕ Will void product warranties;
ƕ 0D\LQYDOLGDWHSURGXFWUHJXODWRU\FHUWL¿FDWLRQV
ƕ May violate OSHA standards;
iv
SM-16007
Take the following precautions to reduce the risk of property damage.
Ɣ Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant cycle during
installation work. Foreign matter could damage internal components or cause blockages.
Ɣ ,IDLU¿OWHUVDUHUHTXLUHGRQWKLVXQLWGRQRWRSHUDWHWKHXQLWZLWKRXWWKHDLU¿OWHUVHWLQSODFH,IWKHDLU
¿OWHULVQRWLQVWDOOHGGXVWPD\DFFXPXODWHDQGEUHDNGRZQPD\UHVXOW
Ɣ Do not install this unit in any place where silicon gases can coalesce. If the silicon gas molecules
DWWDFKWKHPVHOYHVWRWKHVXUIDFHRIWKHKHDWH[FKDQJHUWKH¿QQHGVXUIDFHVZLOOUHSHOZDWHU$VD
UHVXOWDQ\DPRXQWRIGUDLQDJHPRLVWXUHFRQGHQVDWHFDQRYHUÀRZIURPWKHGUDLQFRQGHQVDWHSDQDQG
could run inside of the electrical box, possibly causing electrical failures.
Ɣ When installing the unit in a hospital or other facility where electromagnetic waves are generated
from nearby medical and/or electronic devices, be prepared for noise and electronic interference
Electromagnetic Interference (EMI). Do not install where the waves can directly radiate into the
electrical box, controller cable, or controller. Inverters, appliances, high-frequency medical equipment,
and radio communications equipment may cause the unit to malfunction. The operation of the unit
may also adversely affect these same devices. Install the unit at least 10 ft. (approximately 3m) away
from such devices.
Ɣ When a wireless controller is used, locate at a distance of at least 3.3 ft. (approximately 1 meter)
EHWZHHQWKHLQGRRUXQLWDQGHOHFWULFOLJKWLQJ,IQRWWKHUHFHLYHUSDUWRIWKHXQLWPD\KDYHGLI¿FXOW\
receiving operation commands.
Ɣ Do not install the unit in any location where animals and plants can come into direct contact with the
outlet air stream. Exposure could adversely affect the animals and plants.
Ɣ Do not install the unit with any downward slope to the side of the drain adaptor. If you do, you may
KDYHGUDLQZDWHUÀRZLQJEDFNZKLFKPD\FDXVHOHDNV
Ɣ Be sure the drain hose discharges water properly. If connected incorrectly, it may cause leaks.
Ɣ Do not install the unit in any place where oil can seep onto the units, such as table or seating areas in
restaurants, and so forth. For these locations or social venues, use specialized units with oil-resistant
features built into them. In addition, use a specialized ceiling fan designed for restaurant use. These
specialized oil-resistant units can be ordered for such applications. However, in places where large
quantities of oil can splash onto the unit, such as a factory, even the specialized units cannot be used.
These products should not be installed in such locations.
Installation Precautions
To reduce the risk of serious injury or death, the following installation
precautions must be followed.
Ɣ When installing the unit into…
Ɠ $ZDOO0DNHVXUHWKHZDOOLVVWURQJHQRXJKWRKROGWKHXQLW¶VZHLJKW,WPD\EHQHFHVVDU\WR
construct a strong wood or metal frame to provide added support.
Ɠ A room: Properly insulate any refrigerant tubing run inside a room to prevent “sweating” that can
FDXVHGULSSLQJDQGZDWHUGDPDJHWRZDOODQGÀRRUV
Ɠ Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the unit to prevent water damage and abnormal vibration.
Ɠ An area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame.
3URYLGHDVXLWDEOHDLUEDIÀH
Ɠ A snowy area: Install the outdoor unit on a raised platform that is higher than drifting snow. Provide
snow vents.
Ɣ 'RQRWLQVWDOOWKHXQLWLQWKHIROORZLQJSODFHV'RLQJVRFDQUHVXOWLQDQH[SORVLRQ¿UHGHIRUPDWLRQ
corrosion, or product failure.
Ɠ ([SORVLYHRUÀDPPDEOHDWPRVSKHUH
Ɠ :KHUH¿UHRLOVWHDPRUSRZGHUFDQGLUHFWO\HQWHUWKHXQLWVXFKDVLQFORVHSUR[LPLW\RUGLUHFWO\
above a kitchen stove.
Ɠ Where oil (including machinery oil) may be present.
Ɠ :KHUHFRUURVLYHJDVHVVXFKDVFKORULQHEURPLQHRUVXO¿GHFDQDFFXPXODWHVXFKDVQHDUDKRW
tub or hot spring.
Ɠ :KHUHGHQVHVDOWODGHQDLUÀRZLVKHDY\VXFKDVLQFRDVWDOUHJLRQV
Ɠ Where the air quality is of high acidity.
Ɠ Where harmful gases can be generated from decomposition.
SM-16007
v
Ɣ Do not position the drain pipe for the indoor unit near any sanitary sewers where corrosive gases
may be present. If you do, toxic gases can seep into breathable air spaces and can cause respiratory
LQMXULHV,IWKHGUDLQSLSHLVLQVWDOOHGLQFRUUHFWO\ZDWHUOHDNDJHDQGGDPDJHWRWKHFHLOLQJÀRRU
furniture, or other possessions may result. If condensate piping becomes clogged, moisture can back
up and can drip from the indoor unit. Do not install the indoor unit where such dripping can cause
moisture damage or uneven locations: Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the unit to prevent water damage and abnormal vibration.
Ɣ %HIRUHSHUIRUPLQJDQ\EUD]LQJZRUNEHVXUHWKDWWKHUHDUHQRÀDPPDEOHPDWHULDOVRURSHQÀDPHV
nearby.
Ɣ Perform a test run to ensure normal operation. Safety guards, shields, barriers, covers, and protective
GHYLFHVPXVWEHLQSODFHZKLOHWKHFRPSUHVVRUXQLWLVRSHUDWLQJ'XULQJWKHWHVWUXQNHHS¿QJHUVDQG
clothing away from any moving parts.
Ɣ &OHDQXSWKHVLWHZKHQ¿QLVKHGUHPHPEHULQJWRFKHFNWKDWQRPHWDOVFUDSVRUELWVRIZLULQJKDYH
been left inside the unit being installed.
Ɣ During transportation, do not allow the backrest of the forklift make contact with the unit, otherwise,
it may cause damage to the heat exchanger and also may cause injury when stopped or started
suddenly
.
Ɣ
5HPRYHJDVLQVLGHWKHFORVLQJSLSHZKHQWKHEUD]LQJZRUNLVSHUIRUPHG,IWKHEUD]LQJ¿OOHUPHWDOLV
melted with remaining gas inside, the pipes will be blown off and it may cause injury.
Ɣ Be sure to use nitrogen gas for an airtight test. If other gases such as oxygen gas, acetylene gas or
ÀXRURFDUERQJDVDUHDFFLGHQWDOO\XVHGLWPD\FDXVHH[SORVLRQRUJDVLQWR[LFDWLRQ
After installation work for the system has been completed, explain the “Safety Precautions,” the proper use
and maintenance of the unit to the customer according to the information in all manuals that came with the
system. All manuals and warranty information must be given to the user or left near the Indoor Unit.
Refrigerant Precautions
To reduce the risk of serious injury or death, the following refrigerant
precautions must be followed.
Ɣ As originally manufactured, this unit contains refrigerant installed by Johnson Controls. Johnson
&RQWUROVXVHVRQO\UHIULJHUDQWVWKDWKDYHEHHQDSSURYHGIRUXVHLQWKHXQLW¶VLQWHQGHGKRPHFRXQWU\
or market. Johnson Controls distributors similarly are only authorized to provide refrigerants that
have been approved for use in the countries or markets they serve. The refrigerant used in this unit
LVLGHQWL¿HGRQWKHXQLW¶VIDFHSODWHDQGRULQWKHDVVRFLDWHGPDQXDOV$Q\DGGLWLRQVRIUHIULJHUDQWLQWR
WKLVXQLWPXVWFRPSO\ZLWKWKHFRXQWU\¶VUHTXLUHPHQWVZLWKUHJDUGWRUHIULJHUDQWXVHDQGVKRXOGEH
obtained from Johnson Controls distributors. Use of any non-approved refrigerant substitutes will void
the warranty and will increase the potential risk of injury or death.
Ɣ If installed in a small room, take measures to prevent the refrigerant from exceeding the maximum
allowable concentration in the event that refrigerant gases should escape. Refrigerant gases can
cause asphyxiation (0.026
lbs/ft
3
(0.42 kg/m
3
) based on ISO 5149 for R410A). Consult with your
distributor for countermeasures (ventilation system and so on). If refrigerant gas has leaked during the
installation work, ventilate the room immediately.
Ɣ Check the design pressure for this product is 601 psi (4.15MPa).
The pressure of the refrigerant
R410A is 1.4 times higher than that of the refrigerant R22. Therefore, the refrigerant piping for
5$VKDOOEHWKLFNHUWKDQWKDWIRU50DNHVXUHWRXVHWKHVSHFL¿HGUHIULJHUDQWSLSLQJ,IQRWWKH
refrigerant piping may rupture due to an excessive refrigerant pressure. Besides, pay attention to
the piping thickness when using copper refrigerant piping. The thickness of copper refrigerant piping
differs depending on its material.
Ɣ The refrigerant R410A is adopted. The refrigerant oil tends to be affected by foreign matters such
DVPRLVWXUHR[LGH¿OPRUIDW3HUIRUPWKHLQVWDOODWLRQZRUNZLWKFDUHWRSUHYHQWPRLVWXUHGXVWRU
different refrigerant from entering the refrigerant cycle. Foreign matter can be introduced into the
cycle from such parts as expansion valve and the operation may be unavailable.
Ɣ To avoid the possibility of different refrigerant or refrigerant oil being introduced into the cycle, the
sizes of the charging connections have been changed from R407C type and R22 type. It is necessary
to prepare the appropriate tools before performing installation work.
Ɣ Use refrigerant pipes and joints which are approved for use with R410A.
Ɣ A compressor/unit comprises a pressurized system. Never loosen threaded joints while the system is
under pressure and never open pressurized system parts.
vi
SM-16007
Ɣ Before installation is complete, make sure that the refrigerant leak test has been performed. If
UHIULJHUDQWJDVHVHVFDSHLQWRWKHDLUWXUQ2))WKHPDLQVZLWFKH[WLQJXLVKDQ\RSHQÀDPHVDQG
contact your service contractor. Refrigerant (Fluorocarbon) for this unit is odorless. If the refrigerant
VKRXOGOHDNDQGFRPHLQWRFRQWDFWZLWKRSHQÀDPHVWR[LFJDVFRXOGEHJHQHUDWHG$OVREHFDXVHWKH
ÀXRURFDUERQVDUHKHDYLHUWKDQDLUWKH\VHWWOHWRWKHÀRRUZKLFKFRXOGFDXVHDVSK\[LDWLRQ
Ɣ When installing the unit, and connecting refrigerant piping, keep all piping runs as short as possible,
and make sure to securely connect the refrigerant piping before the compressor starts operating. If
the refrigerant piping is not connected and the compressor activates with the stop valve opened, the
refrigerant cycle will become subjected to extremely high pressure, which can cause an explosion or
¿UH
Ɣ 7LJKWHQWKHÀDUHQXWZLWKDWRUTXHZUHQFKLQWKHVSHFL¿HGPDQQHU'RQRWDSSO\H[FHVVLYHIRUFHWRWKH
ÀDUHQXWZKHQWLJKWHQLQJ,I\RXGRWKHÀDUHQXWFDQFUDFNDQGUHIULJHUDQWOHDNDJHPD\RFFXU
Ɣ When maintaining, relocating, and disposing of the unit, dismantle the refrigerant piping after the
compressor stops.
Ɣ When pipes are removed out from under the piping cover, after the insulation work is completed,
FRYHUWKHJDSEHWZHHQWKHSLSLQJFRYHUDQGSLSHVE\DSDFNLQJ¿HOGVXSSOLHG,IWKHJDSLVQRW
covered, the unit may be damaged if snow, rain water or small animals enter the unit.
Ɣ Do not apply an excessive force to the spindle valve at the end of opening. Otherwise, the spindle
YDOYHÀLHVRXWGXHWRUHIULJHUDQWSUHVVXUH$WWKHWHVWUXQIXOO\RSHQWKHJDVDQGOLTXLGYDOYHV
otherwise, these devices will be damaged. (It is closed before shipment.)
Ɣ ,IWKHDUUDQJHPHQWIRURXWGRRUXQLWVLVLQFRUUHFWLWPD\FDXVHÀRZEDFNRIWKHUHIULJHUDQWDQGUHVXOWLQ
failure of the outdoor unit.
Ɣ The refrigerant system may be damaged if the slope of the piping connection kit exceeds +15
o
.
Electrical Precautions
7DNHWKHIROORZLQJSUHFDXWLRQVWRUHGXFHWKHULVNRIHOHFWULFVKRFN¿UHRU
explosion resulting in serious injury or death.
Ɣ Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections and inadequate grounding can cause serious
injury or death.
Ɣ Perform all electrical work in strict accordance with this installation and maintenance manual and all
the relevant regulatory standards.
Ɣ Before servicing, open and tag all disconnect switches. Never assume electrical power is
disconnected. Check with meter and equipment.
Ɣ Only use electrical protection equipment and tools suited for this installation.
Ɣ 8VHVSHFL¿HGFDEOHVEHWZHHQXQLWV
Ɣ The new air conditioner may not function normally in the following instances:
Ɠ
If electrical power for the new air conditioner is supplied from the same transformer as the device*
referred to below.
Ɠ
If the power source cables for this device* and the new air conditioner unit are located in close
proximity to each other.
'HYLFH([DPSOH$OLIWFRQWDLQHUFUDQHUHFWL¿HUIRUHOHFWULFUDLOZD\LQYHUWHUSRZHU
device, arc furnace, electric furnace, large-sized induction motor and large-sized switch.
Regarding the cases mentioned above, surge voltage may be inducted into the power supply
cables for the packaged air conditioner due to a rapid change in power consumption of the
device and an activation of a switch.
&KHFN¿HOGUHJXODWLRQVDQGVWDQGDUGVEHIRUHSHUIRUPLQJHOHFWULFDOZRUNLQRUGHUWRSURWHFWWKH
power supply for the new air conditioner unit.
Ɣ Communication cabling shall be a minimum of AWG18 (0.82mm
2
), 2-Conductor, Stranded Copper.
Shielded cable must be considered for applications and routing in areas of high EMI and other
sources of potentially excessive electrical noise to reduce the potential for communication errors.
When shielded cabling is applied, proper bonding and termination of the cable shield is required
as per Johnson Controls guidelines. Plenum and riser ratings for communication cables must be
considered per application and local code requirements.
Ɣ 8VHDQH[FOXVLYHSRZHUVXSSO\IRUWKHDLUFRQGLWLRQHUDWWKHXQLW¶VUDWHGYROWDJH
SM-16007
vii
Ɣ Be sure to install circuit breakers (ground fault interrupter, isolating switch, molded case circuit
EUHDNHUDQGVRRQZLWKWKHVSHFL¿HGFDSDFLW\(QVXUHWKDWWKHZLULQJWHUPLQDOVDUHWLJKWHQHGVHFXUHO\
WRUHFRPPHQGHGWRUTXHVSHFL¿FDWLRQV
Ɣ Clamp electrical wires securely with a cable clamp after all wiring is connected to the terminal block.
In addition, run wires securely through the wiring access channel.
Ɣ When installing the power lines, do not apply tension to the cables. Secure the suspended cables at
regular intervals, but not too tightly.
Ɣ Make sure that the terminals do not come into contact with the surface of the electrical box. If the
terminals are too close to the surface, it may lead to failures at the terminal connection.
Ɣ Turn OFF and disconnect the unit from the power source when handling the service connector. Do not
open the service cover or access panel to the indoor or outdoor units without turning OFF the main
power supply.
Ɣ $IWHUFHDVLQJRSHUDWLRQEHVXUHWRZDLWDWOHDVW¿YHPLQXWHVEHIRUHWXUQLQJRIIWKHPDLQSRZHU
switch. Otherwise, water leakage or electrical breakdown may result. Disconnect the power source
completely before attempting any maintenance for electrical parts. Check to ensure that no residual
voltage is present after disconnecting the power source.
Ɣ Do not clean with, or pour water into, the controller as it could cause electric shock and/or damage the
unit. Do not use strong detergent such as a solvent. Clean with a soft cloth.
Ɣ Check that the ground wire is securely connected. Do not connect ground wiring to gas piping, water
piping, lighting conductor, or telephone ground wiring.
Ɣ If a circuit breaker or fuse is frequently activated, shut down the system and contact your service
contractor.
Ɣ Perform all electrical work in accordance with this manual and in compliance with all regulations and
safety standards.
Ɣ 'RQRWRSHQDVHUYLFHDFFHVVFRYHURUSDQHORIDQLQGRRURURXWGRRUXQLWZLWKRXW¿UVWWXUQLQJ2))WKH
power at the main power supply.
Ɣ Residual voltage can cause electric shock. At all times, check for residual voltage after disconnecting
from the power source before starting work on the unit.
Ɣ Use a Ground Fault Circuit Interrupter (GFCI) to reduce the chance of an electric shock.
viii
SM-16007
SM-16007
ix
- Table of Contents -
1. Installation ..............................................................................................................................1-1
1.1 Outdoor Unit ....................................................................................................................................1-2
1.2 Optional Parts..................................................................................................................................1-75
1.2.1 For Outdoor Unit ....................................................................................................................1-75
1.2.1.1 Drain Adaptor ....................................................................................................................1-76
1.2.1.2 Protection Net ...................................................................................................................1-78
1.2.1.3 Snow Protection Hood ......................................................................................................1-87
1.2.1.4 Topping Prevention Tool ....................................................................................................1-113
1.2.1.5 Seismic Kit ........................................................................................................................1-115
1.2.2 Piping Kit ................................................................................................................................1-119
1.2.2.1 Piping Connection Kit ........................................................................................................1-120
1.2.2.2 Multi-Kit (Line Branch) ......................................................................................................1-130
1.2.2.3 Multi-Kit (Header Branch) .................................................................................................1-139
2. Operation ............................................................................................................................... 2-1
3. Troubleshooting .....................................................................................................................3-1
3.1 Initial Troubleshooting .....................................................................................................................3-2
3.1.1 Checking Electrical Wiring and Power Source .......................................................................3-2
3.1.2 Location of Printed Circuit Boards (PCBs) .............................................................................3-6
3.1.3 Checking Rotary Switch and DIP Switch Settings .................................................................3-10
3.1.4 Checking Wired Controller .....................................................................................................3-13
3.1.5 Checking Using 7-Segment Display.......................................................................................3-20
3.1.6 Checking Alarm Code History ................................................................................................3-26
3.1.7 Emergency Operation ............................................................................................................3-33
3.2 Troubleshooting Procedures ...........................................................................................................3-38
3.2.1 Alarm Code Table ...................................................................................................................3-38
3.2.2 Troubleshooting Using Alarm Codes ......................................................................................3-39
3.2.3 Abnormalities of Devices ........................................................................................................3-106
3.3 Procedures for Checking .................................................................................................................3-110
3.3.1 Self-Checking of PCBs using Wired Controller ......................................................................3-110
3.3.2 Self-Checking of Wired Controller ..........................................................................................3-110
3.4 Test Run ..........................................................................................................................................3-111
3.4.1 Test Run Using Wired Controller ............................................................................................3-112
3.4.2 Test Run from Outdoor Unit Side ...........................................................................................3-114
3.4.3 Checking the Test Run ...........................................................................................................3-116
3.4.4 Checklist for Refrigerant System ............................................................................................3-117
3.4.5 Reset for Accumulated Operation Time of Compressor 1-2 (cUJ1-cUJ2)..............................3-119
x
SM-16007
- Table of Contents -
4. Maintenance ..........................................................................................................................4-1
4.1 Maintenance of Outdoor Unit ..........................................................................................................4-2
4.1.1 Removing Front Service Cover ..............................................................................................4-2
4.1.2 Attaching Front Service Cover ...............................................................................................4-3
4.1.3 Removing Top Cover and Upper Cover .................................................................................4-4
4.1.4 Removing Protection Net .......................................................................................................4-6
4.1.5 Removing Electrical Box Cover ..............................................................................................4-7
4.1.6 Removing Electrical Box ........................................................................................................4-8
4.1.7 Removing Electrical Box Support and Reinforcement Support..............................................4-9
4.1.8 Removing Transformer Box Cover .........................................................................................4-10
4.1.9 Removing Transformer Box ...................................................................................................4-11
4.1.10 Removing Air Grille ................................................................................................................4-12
4.1.11 Removing Outdoor Fan Motor ................................................................................................4-13
4.1.12 Removing Compressor ..........................................................................................................4-15
4.1.13 Replacing Refrigerant Oil ......................................................................................................4-24
4.1.14 Removing Coils ......................................................................................................................4-28
4.1.15 Removing Stop Valve .............................................................................................................4-34
4.1.16 Removing High Pressure Switch, High Pressure Sensor, Low Pressure Sensor
and Thermistor .......................................................................................................................4-35
4.1.17 Removing Thermistor for Liquid Pipe .....................................................................................4-37
4.1.18 Removing Thermistor for Ambient Temperature ...................................................................4-38
4.1.19 Removing Other Electrical Components ................................................................................4-39
4.1.20 Removing Transformer ...........................................................................................................4-47
4.2 Main Parts .......................................................................................................................................4-48
4.2.1 for Outdoor Unit ......................................................................................................................4-48
4.2.1.1 Inverter ..............................................................................................................................4-48
4.2.1.2 Printed Circuit Board .........................................................................................................4-56
4.2.1.3 Scroll Compressor ............................................................................................................4-58
4.2.1.4 Fan Motor ..........................................................................................................................4-62
4.2.1.5 Thermistor .........................................................................................................................4-63
4.2.1.6 Electronic Expansion Valve ...............................................................................................4-65
4.2.1.7 Pressure Sensor ...............................................................................................................4-68
4.2.1.8 High Pressure Protection Device ......................................................................................4-69
4.2.1.9 Electrical Coil Parts ...........................................................................................................4-70
4.2.1.10 Noise Filter (NF1, NF2) .....................................................................................................4-71
4.2.1.11 Capacitor (CB, CB1, CB2, CB3) .......................................................................................4-74
4.2.1.12 Reactor (DCL, DCL1, DCL2) ............................................................................................4-75
SM-16007
xi
- Table of Contents -
5. External Input/Output and Function Setting ...........................................................................5-1
5.1 DIP Switch Settings of Outdoor Unit ...............................................................................................5-2
5.2 High Static Pressure Setting (DSW5-No.5: ON) .............................................................................5-3
5.3 External Input/Output and Function Setting Mode for Outdoor Unit ................................................5-5
5.3.1 External Input and Output Settings ........................................................................................5-6
5.3.2 Function Setting .....................................................................................................................5-15
5.3.2.1 Function Setting Item ........................................................................................................5-16
5.3.2.2 Description of Function Setting Item .................................................................................5-19
5.4 Power Saving Functions from Wired Controller ..............................................................................5-27
5.4.1 Power Saving Guide ..............................................................................................................5-27
5.4.2 Outdoor Unit Capacity Control ...............................................................................................5-27
5.4.3 Rotation Control Function ......................................................................................................5-28
5.4.4 Intermittent Control Function ..................................................................................................5-28
5.4.5 Power Saving Schedule Function ..........................................................................................5-29
5.4.6 Operation Noise Reduction Schedule Function .....................................................................5-29
5.4.7 Power Consumption Display Function ...................................................................................5-29
6. Field Work Instructions ..........................................................................................................6-1
6.1 Caution for Refrigerant Leakage .....................................................................................................6-2
6.2 Modifications of Charging Refrigerants Other than Those Specified by Johnson Controls .............6-3
6.3 Maintenance Work ..........................................................................................................................6-4
6.4 Service and Maintenance Record by 7-Segment Display ...............................................................6-5
6.5 Service and Maintenance Record by Wired Controller ...................................................................6-6
6.6 Service and Maintenance Record ...................................................................................................6-8
6.7 Saturation Curve for Refrigerant .....................................................................................................6-9
6.8 Mollier Chart for R410A ...................................................................................................................6-10
7. Service Parts List ...................................................................................................................7-1
SM-16007
1-1
INSTALLATION
1. Installation
1-2
SM-16007
INSTALLATION
- Table of Contents -
1.1 Outdoor Unit
1. Introduction ....................................................................................................................................................1-3
2. Important Safety Instructions .........................................................................................................................1-3
3. Before Installation ..........................................................................................................................................1-8
3.1 Factory-Supplied Accessories ...............................................................................................................1-8
3.2 Necessary Tools and Instrument List for Installation .............................................................................1-9
3.3 Flaring and Joint ....................................................................................................................................1-11
3.4 Line-Up of Outdoor Units .......................................................................................................................1-13
3.5 Combinations of Indoor Units and Outdoor Units ..................................................................................1-14
3.6 Caution about Outdoor Unit Installation ................................................................................................1-15
3.7 Piping Work between Outdoor Units .....................................................................................................1-15
4. Outdoor Unit Installation ................................................................................................................................1-16
4.1 Installation Location and Precautions ....................................................................................................1-16
4.2 Service Space .......................................................................................................................................1-17
5. Transportation and Installation Work .............................................................................................................1-20
5.1 Transportation .......................................................................................................................................1-20
5.2 Handling of Outdoor Unit .......................................................................................................................1-22
5.3 Installation Work ....................................................................................................................................1-23
5.3.1 Concrete Foundations .................................................................................................................1-23
5.3.2 Condensate Treatment ................................................................................................................1-25
6. Refrigerant Piping Work .................................................................................................................................1-26
6.1 Piping Materials .....................................................................................................................................1-27
6.2 Piping Connection Work ........................................................................................................................1-30
6.2.1 Stop Valve ...................................................................................................................................1-30
6.2.2 Piping Connection Method ...........................................................................................................1-31
6.3 Piping Work between Outdoor Units .....................................................................................................1-34
6.4 Piping Size between Outdoor Units .......................................................................................................1-37
6.5 Piping Size and Multi-Kit Selection ........................................................................................................1-39
6.6 Multi-Kit Connection ..............................................................................................................................1-45
7. Electrical Wiring .............................................................................................................................................1-46
7.1 General Check ......................................................................................................................................1-47
7.2 Electrical Wiring Connection .................................................................................................................1-47
7.3 Electrical Wiring for Outdoor Unit ..........................................................................................................1-50
7.4 Electrical Wiring Connections of Indoor Unit, and Outdoor Unit ............................................................1-51
7.5 DIP Switch Setting of Outdoor Unit .......................................................................................................1-54
8. Additional Refrigerant Charge ........................................................................................................................1-58
8.1 Airtight Test ............................................................................................................................................1-58
8.2 Vacuuming .............................................................................................................................................1-60
8.3 Charging Work ......................................................................................................................................1-60
8.4 Additional Refrigerant Charge Calculation ............................................................................................1-62
8.5 Automatic Simple Judgment System for Refrigerant Amount ...............................................................1-63
9. Test Run .........................................................................................................................................................1-66
9.1 Before Test Run .....................................................................................................................................1-66
9.2 Test Run ................................................................................................................................................1-68
10. Safety and Control Device Setting .................................................................................................................1-74
SM-16007
1-3
INSTALLATION
1. Introduction
2. Important Safety Instructions
This manual should be considered as a permanent part of the air conditioning equipment and should
remain with the air conditioning equipment.
(Transportation/Installation Work) > (Refrigerant Piping Work) > (Electrical Wiring Work) > (Ref. Charge Work) > (Test
Run) > (User)
This manual concentrates on the Low Ambient VRF Heat Pump Outdoor Unit. Read this manual carefully
before installation. Read over the installation manual for the Indoor Unit also.
Signal Words
Indicates a hazardous situation that, if not avoided, could result in death or
serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or
moderate injury.
Indicates information considered important, but not hazard-related (for
example, messages relating to property damage).
General Precautions
To reduce the risk of serious injury or death, read these instructions thoroughly
and follow all warnings or cautions included in all manuals that accompanied
the product and are attached to the unit. Refer back to these safety
instructions as needed.
Ɣ 7KLVV\VWHPVKRXOGEHLQVWDOOHGE\SHUVRQQHOFHUWL¿HGE\-RKQVRQ&RQWUROV,QF3HUVRQQHOPXVWEH
TXDOL¿HGDFFRUGLQJWRORFDOVWDWHDQGQDWLRQDOEXLOGLQJDQGVDIHW\FRGHVDQGUHJXODWLRQV,QFRUUHFW
LQVWDOODWLRQFRXOGFDXVHOHDNVHOHFWULFVKRFN¿UHRUH[SORVLRQ,QDUHDVZKHUH6HLVPLFµ¶3HUIRUPDQFH
UHTXLUHPHQWVDUHVSHFL¿HGWKHDSSURSULDWHPHDVXUHVVKRXOGEHWDNHQGXULQJLQVWDOODWLRQWRJXDUG
against possible damage or injury that might occur in an earthquake if the unit is not installed correctly,
injuries may occur due to a falling unit.
Ɣ Use appropriate Personal Protective Equipment (PPE), such as gloves and protective goggles and,
where appropriate, have a gas mask nearby. Also use electrical protection equipment and tools suited
IRUHOHFWULFDORSHUDWLRQSXUSRVHV.HHSDTXHQFKLQJFORWKDQGD¿UHH[WLQJXLVKHUQHDUE\GXULQJEUD]LQJ
Use care in handling, rigging, and setting of bulky equipment.
Ɣ When transporting, be careful when picking up, moving and mounting these units. Although the unit may
be packed using plastic straps, do not use them for transporting the unit from one location to another. Do
not stand on or put any material on the unit. Get a partner to help, and bend with your knees when lifting
WRUHGXFHVWUDLQRQ\RXUEDFN6KDUSHGJHVRUWKLQDOXPLQXP¿QVRQWKHDLUFRQGLWLRQHUFDQFXW¿QJHUV
so wear protective gloves.
Ɣ Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features,
disengagement, and interlocks must be in place and functioning correctly before the equipment is put
into operation. If these devices are improperly adjusted or tampered with in any way, a serious accident
can occur. Never bypass or jump-out any safety device or switch.
Ɣ Johnson Controls will not assume any liability for injuries or damage caused by not following steps
RXWOLQHGRUGHVFULEHGLQWKLVPDQXDO8QDXWKRUL]HGPRGL¿FDWLRQVWR-RKQVRQ&RQWUROVSURGXFWVDUH
prohibited as they…
ƕ May create hazards which could result in death, serious injury or equipment damage;
ƕ Will void product warranties;
ƕ 0D\LQYDOLGDWHSURGXFWUHJXODWRU\FHUWL¿FDWLRQV
ƕ May violate OSHA standards;
1-4
SM-16007
INSTALLATION
Take the following precautions to reduce the risk of property damage.
Ɣ Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant cycle during
installation work. Foreign matter could damage internal components or cause blockages.
Ɣ ,IDLU¿OWHUVDUHUHTXLUHGRQWKLVXQLWGRQRWRSHUDWHWKHXQLWZLWKRXWWKHDLU¿OWHUVHWLQSODFH,IWKHDLU
¿OWHULVQRWLQVWDOOHGGXVWPD\DFFXPXODWHDQGEUHDNGRZQPD\UHVXOW
Ɣ Do not install this unit in any place where silicon gases can coalesce. If the silicon gas molecules
DWWDFKWKHPVHOYHVWRWKHVXUIDFHRIWKHKHDWH[FKDQJHUWKH¿QQHGVXUIDFHVZLOOUHSHOZDWHU$VD
UHVXOWDQ\DPRXQWRIGUDLQDJHPRLVWXUHFRQGHQVDWHFDQRYHUÀRZIURPWKHGUDLQFRQGHQVDWHSDQDQG
could run inside of the electrical box, possibly causing electrical failures.
Ɣ When installing the unit in a hospital or other facility where electromagnetic waves are generated
from nearby medical and/or electronic devices, be prepared for noise and electronic interference
Electromagnetic Interference (EMI). Do not install where the waves can directly radiate into the
electrical box, controller cable, or controller. Inverters, appliances, high-frequency medical equipment,
and radio communications equipment may cause the unit to malfunction. The operation of the unit
may also adversely affect these same devices. Install the unit at least 10 ft. (approximately 3m) away
from such devices.
Ɣ When a wireless controller is used, locate at a distance of at least 3.3 ft. (approximately 1 meter)
EHWZHHQWKHLQGRRUXQLWDQGHOHFWULFOLJKWLQJ,IQRWWKHUHFHLYHUSDUWRIWKHXQLWPD\KDYHGLI¿FXOW\
receiving operation commands.
Ɣ Do not install the unit in any location where animals and plants can come into direct contact with the
outlet air stream. Exposure could adversely affect the animals and plants.
Ɣ Do not install the unit with any downward slope to the side of the drain adaptor. If you do, you may
KDYHGUDLQZDWHUÀRZLQJEDFNZKLFKPD\FDXVHOHDNV
Ɣ Be sure the drain hose discharges water properly. If connected incorrectly, it may cause leaks.
Ɣ Do not install the unit in any place where oil can seep onto the units, such as table or seating areas in
restaurants, and so forth. For these locations or social venues, use specialized units with oil-resistant
features built into them. In addition, use a specialized ceiling fan designed for restaurant use. These
specialized oil-resistant units can be ordered for such applications. However, in places where large
quantities of oil can splash onto the unit, such as a factory, even the specialized units cannot be used.
These products should not be installed in such locations.
Installation Precautions
To reduce the risk of serious injury or death, the following installation
precautions must be followed.
Ɣ When installing the unit into…
Ɠ A wall: Make sure the wall is strong enough to hold the unit’s weight. It may be necessary to
construct a strong wood or metal frame to provide added support.
Ɠ A room: Properly insulate any refrigerant tubing run inside a room to prevent “sweating” that can
FDXVHGULSSLQJDQGZDWHUGDPDJHWRZDOODQGÀRRUV
Ɠ Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the unit to prevent water damage and abnormal vibration.
Ɠ An area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame.
3URYLGHDVXLWDEOHDLUEDIÀH
Ɠ A snowy area: Install the outdoor unit on a raised platform that is higher than drifting snow. Provide
snow vents.
Ɣ 'RQRWLQVWDOOWKHXQLWLQWKHIROORZLQJSODFHV'RLQJVRFDQUHVXOWLQDQH[SORVLRQ¿UHGHIRUPDWLRQ
corrosion, or product failure.
Ɠ ([SORVLYHRUÀDPPDEOHDWPRVSKHUH
Ɠ :KHUH¿UHRLOVWHDPRUSRZGHUFDQGLUHFWO\HQWHUWKHXQLWVXFKDVLQFORVHSUR[LPLW\RUGLUHFWO\
above a kitchen stove.
Ɠ Where oil (including machinery oil) may be present.
Ɠ :KHUHFRUURVLYHJDVHVVXFKDVFKORULQHEURPLQHRUVXO¿GHFDQDFFXPXODWHVXFKDVQHDUDKRW
tub or hot spring.
Ɠ :KHUHGHQVHVDOWODGHQDLUÀRZLVKHDY\VXFKDVLQFRDVWDOUHJLRQV
Ɠ Where the air quality is of high acidity.
Ɠ Where harmful gases can be generated from decomposition.
SM-16007
1-5
INSTALLATION
Ɣ Do not position the drain pipe for the indoor unit near any sanitary sewers where corrosive gases
may be present. If you do, toxic gases can seep into breathable air spaces and can cause respiratory
LQMXULHV,IWKHGUDLQSLSHLVLQVWDOOHGLQFRUUHFWO\ZDWHUOHDNDJHDQGGDPDJHWRWKHFHLOLQJÀRRU
furniture, or other possessions may result. If condensate piping becomes clogged, moisture can back
up and can drip from the indoor unit. Do not install the indoor unit where such dripping can cause
moisture damage or uneven locations: Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the unit to prevent water damage and abnormal vibration.
Ɣ %HIRUHSHUIRUPLQJDQ\EUD]LQJZRUNEHVXUHWKDWWKHUHDUHQRÀDPPDEOHPDWHULDOVRURSHQÀDPHV
nearby.
Ɣ Perform a test run to ensure normal operation. Safety guards, shields, barriers, covers, and protective
GHYLFHVPXVWEHLQSODFHZKLOHWKHFRPSUHVVRUXQLWLVRSHUDWLQJ'XULQJWKHWHVWUXQNHHS¿QJHUVDQG
clothing away from any moving parts.
Ɣ &OHDQXSWKHVLWHZKHQ¿QLVKHGUHPHPEHULQJWRFKHFNWKDWQRPHWDOVFUDSVRUELWVRIZLULQJKDYH
been left inside the unit being installed.
Ɣ During transportation, do not allow the backrest of the forklift make contact with the unit, otherwise,
it may cause damage to the heat exchanger and also may cause injury when stopped or started
suddenly.
Ɣ 5HPRYHJDVLQVLGHWKHFORVLQJSLSHZKHQWKHEUD]LQJZRUNLVSHUIRUPHG,IWKHEUD]LQJ¿OOHUPHWDOLV
melted with remaining gas inside, the pipes will be blown off and it may cause injury.
Ɣ Be sure to use nitrogen gas for an airtight test. If other gases such as oxygen gas, acetylene gas or
ÀXRURFDUERQJDVDUHDFFLGHQWDOO\XVHGLWPD\FDXVHH[SORVLRQRUJDVLQWR[LFDWLRQ
After installation work for the system has been completed, explain the “Safety Precautions,” the proper use
and maintenance of the unit to the customer according to the information in all manuals that came with the
system. All manuals and warranty information must be given to the user or left near the Indoor Unit.
Refrigerant Precautions
To reduce the risk of serious injury or death, the following refrigerant
precautions must be followed.
Ɣ As originally manufactured, this unit contains refrigerant installed by Johnson Controls. Johnson
Controls uses only refrigerants that have been approved for use in the unit’s intended home country
or market. Johnson Controls distributors similarly are only authorized to provide refrigerants that
have been approved for use in the countries or markets they serve. The refrigerant used in this unit
LVLGHQWL¿HGRQWKHXQLW¶VIDFHSODWHDQGRULQWKHDVVRFLDWHGPDQXDOV$Q\DGGLWLRQVRIUHIULJHUDQWLQWR
this unit must comply with the country’s requirements with regard to refrigerant use and should be
obtained from Johnson Controls distributors. Use of any non-approved refrigerant substitutes will void
the warranty and will increase the potential risk of injury or death.
Ɣ If installed in a small room, take measures to prevent the refrigerant from exceeding the maximum
allowable concentration in the event that refrigerant gases should escape. Refrigerant gases can
cause asphyxiation (0.026
lbs/ft
3
(0.42 kg/m
3
) based on ISO 5149 for R410A). Consult with your
distributor for countermeasures (ventilation system and so on). If refrigerant gas has leaked during the
installation work, ventilate the room immediately.
Ɣ Check the design pressure for this product is 601 psi (4.15MPa). The pressure of the refrigerant
R410A is 1.4 times higher than that of the refrigerant R22. Therefore, the refrigerant piping for
5$VKDOOEHWKLFNHUWKDQWKDWIRU50DNHVXUHWRXVHWKHVSHFL¿HGUHIULJHUDQWSLSLQJ,IQRWWKH
refrigerant piping may rapture due to an excessive refrigerant pressure. Besides, pay attention to
the piping thickness when using copper refrigerant piping. The thickness of copper refrigerant piping
differs depending on its material.
Ɣ The refrigerant R410A is adopted. The refrigerant oil tends to be affected by foreign matters such
DVPRLVWXUHR[LGH¿OPRUIDW3HUIRUPWKHLQVWDOODWLRQZRUNZLWKFDUHWRSUHYHQWPRLVWXUHGXVWRU
different refrigerant from entering the refrigerant cycle. Foreign matter can be introduced into the
cycle from such parts as expansion valve and the operation may be unavailable.
Ɣ To avoid the possibility of different refrigerant or refrigerant oil being introduced into the cycle, the
sizes of the charging connections have been changed from R407C type and R22 type. It is necessary
to prepare the following tools listed in Section 3 before performing the installation work.
Ɣ Use refrigerant pipes and joints which are approved for use with R410A.
Ɣ A compressor/unit comprises a pressurized system. Never loosen threaded joints while the system is
under pressure and never open pressurized system parts.
1-6
SM-16007
INSTALLATION
Ɣ Before installation is complete, make sure that the refrigerant leak test has been performed. If
UHIULJHUDQWJDVHVHVFDSHLQWRWKHDLUWXUQ2))WKHPDLQVZLWFKH[WLQJXLVKDQ\RSHQÀDPHVDQG
contact your service contractor. Refrigerant (Fluorocarbon) for this unit is odorless. If the refrigerant
VKRXOGOHDNDQGFRPHLQWRFRQWDFWZLWKRSHQÀDPHVWR[LFJDVFRXOGEHJHQHUDWHG$OVREHFDXVHWKH
ÀXRURFDUERQVDUHKHDYLHUWKDQDLUWKH\VHWWOHWRWKHÀRRUZKLFKFRXOGFDXVHDVSK\[LDWLRQ
Ɣ When installing the unit, and connecting refrigerant piping, keep all piping runs as short as possible,
and make sure to securely connect the refrigerant piping before the compressor starts operating. If
the refrigerant piping is not connected and the compressor activates with the stop valve opened, the
refrigerant cycle will become subjected to extremely high pressure, which can cause an explosion or
¿UH
Ɣ 7LJKWHQWKHÀDUHQXWZLWKDWRUTXHZUHQFKLQWKHVSHFL¿HGPDQQHU'RQRWDSSO\H[FHVVLYHIRUFHWRWKH
ÀDUHQXWZKHQWLJKWHQLQJ,I\RXGRWKHÀDUHQXWFDQFUDFNDQGUHIULJHUDQWOHDNDJHPD\RFFXU
Ɣ When maintaining, relocating, and disposing of the unit, dismantle the refrigerant piping after the
compressor stops.
Ɣ When pipes are removed out from under the piping cover, after the insulation work is completed,
FRYHUWKHJDSEHWZHHQWKHSLSLQJFRYHUDQGSLSHVE\DSDFNLQJ¿HOGVXSSOLHG,IWKHJDSLVQRW
covered, the unit may be damaged if snow, rain water or small animals enter the unit.
Ɣ Do not apply an excessive force to the spindle valve at the end of opening. Otherwise, the spindle
YDOYHÀLHVRXWGXHWRUHIULJHUDQWSUHVVXUH$WWKHWHVWUXQIXOO\RSHQWKHJDVDQGOLTXLGYDOYHV
otherwise, these devices will be damaged. (It is closed before shipment.)
Ɣ ,IWKHDUUDQJHPHQWIRURXWGRRUXQLWVLVLQFRUUHFWLWPD\FDXVHÀRZEDFNRIWKHUHIULJHUDQWDQGUHVXOWLQ
failure of the outdoor unit.
Ɣ The refrigerant system may be damaged if the slope of the piping connection kit exceeds +15
o
.
Electrical Precautions
7DNHWKHIROORZLQJSUHFDXWLRQVWRUHGXFHWKHULVNRIHOHFWULFVKRFN¿UHRU
explosion resulting in serious injury or death.
Ɣ Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and
these instructions when wiring. Improper connections and inadequate grounding can cause serious
injury or death.
Ɣ Perform all electrical work in strict accordance with this manual and all the relevant regulatory
standards.
Ɣ Before servicing, open and tag all disconnect switches. Never assume electrical power is
disconnected. Check with meter and equipment.
Ɣ Only use electrical protection equipment and tools suited for this installation.
Ɣ 8VHVSHFL¿HGFDEOHVEHWZHHQXQLWV
Ɣ The new air conditioner may not function normally in the following instances:
Ɠ If electrical power for the new air conditioner is supplied from the same transformer as the device*
referred to below.
Ɠ If the power source cables for this device* and the new air conditioner unit are located in close
proximity to each other.
'HYLFH([DPSOH$OLIWFRQWDLQHUFUDQHUHFWL¿HUIRUHOHFWULFUDLOZD\LQYHUWHUSRZHU
device, arc furnace, electric furnace, large-sized induction motor and large-sized switch.
Regarding the cases mentioned above, surge voltage may be inducted into the power supply
cables for the packaged air conditioner due to a rapid change in power consumption of the
device and an activation of a switch.
&KHFN¿HOGUHJXODWLRQVDQGVWDQGDUGVEHIRUHSHUIRUPLQJHOHFWULFDOZRUNLQRUGHUWRSURWHFWWKH
power supply for the new air conditioner unit.
Ɣ Communication cabling shall be a minimum of AWG18 (0.82mm
2
), 2-Conductor, Stranded Copper.
Shielded cable must be considered for applications and routing in areas of high EMI and other
sources of potentially excessive electrical noise to reduce the potential for communication errors.
When shielded cabling is applied, proper bonding and termination of the cable shield is required
as per Johnson Controls guidelines. Plenum and riser ratings for communication cables must be
considered per application and local code requirements.
Ɣ Use an exclusive power supply for the air conditioner at the unit’s rated voltage.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298
  • Page 299 299
  • Page 300 300
  • Page 301 301
  • Page 302 302
  • Page 303 303
  • Page 304 304
  • Page 305 305
  • Page 306 306
  • Page 307 307
  • Page 308 308
  • Page 309 309
  • Page 310 310
  • Page 311 311
  • Page 312 312
  • Page 313 313
  • Page 314 314
  • Page 315 315
  • Page 316 316
  • Page 317 317
  • Page 318 318
  • Page 319 319
  • Page 320 320
  • Page 321 321
  • Page 322 322
  • Page 323 323
  • Page 324 324
  • Page 325 325
  • Page 326 326
  • Page 327 327
  • Page 328 328
  • Page 329 329
  • Page 330 330
  • Page 331 331
  • Page 332 332
  • Page 333 333
  • Page 334 334
  • Page 335 335
  • Page 336 336
  • Page 337 337
  • Page 338 338
  • Page 339 339
  • Page 340 340
  • Page 341 341
  • Page 342 342
  • Page 343 343
  • Page 344 344
  • Page 345 345
  • Page 346 346
  • Page 347 347
  • Page 348 348
  • Page 349 349
  • Page 350 350
  • Page 351 351
  • Page 352 352
  • Page 353 353
  • Page 354 354
  • Page 355 355
  • Page 356 356
  • Page 357 357
  • Page 358 358
  • Page 359 359
  • Page 360 360
  • Page 361 361
  • Page 362 362
  • Page 363 363
  • Page 364 364
  • Page 365 365
  • Page 366 366
  • Page 367 367
  • Page 368 368
  • Page 369 369
  • Page 370 370
  • Page 371 371
  • Page 372 372
  • Page 373 373
  • Page 374 374
  • Page 375 375
  • Page 376 376
  • Page 377 377
  • Page 378 378
  • Page 379 379
  • Page 380 380
  • Page 381 381
  • Page 382 382
  • Page 383 383
  • Page 384 384
  • Page 385 385
  • Page 386 386
  • Page 387 387
  • Page 388 388
  • Page 389 389
  • Page 390 390
  • Page 391 391
  • Page 392 392
  • Page 393 393
  • Page 394 394
  • Page 395 395
  • Page 396 396
  • Page 397 397
  • Page 398 398
  • Page 399 399
  • Page 400 400
  • Page 401 401
  • Page 402 402
  • Page 403 403
  • Page 404 404
  • Page 405 405
  • Page 406 406
  • Page 407 407
  • Page 408 408
  • Page 409 409
  • Page 410 410
  • Page 411 411
  • Page 412 412
  • Page 413 413
  • Page 414 414
  • Page 415 415
  • Page 416 416

York VRF Low Ambient Heat Pump Outdoor Unit 208/230V User manual

Category
Split-system air conditioners
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI