Legrand V700 Installation guide

Type
Installation guide
5791
5700 1/2" EMT Connector
INSTALLATION
INSTRUCTIONS
Wiremold Electrical Systems conform with, and
should be installed and properly grounded in
compliance with requirements of the current
National Electrical Code or codes administered by
local authorities. All electrical products may rep-
resent a possible shock or fire hazard if improp-
erly installed or used. Wiremold electrical prod-
ucts are UL listed, made for interior use and
should be installed by qualified electrical people
in conformance with current and local codes
and/or the National Electrical Code.
U
L
®
U
L
®
C
1. Mount base to wall in
desired location.
2. Attach 5791 to base
tongue.
3. Remove cover twistout
completely.
4. Mount cover to base.
5. Deburr end of 1/2" EMT,
insert 1/2" EMT into 5791
and tighten screw.
Fitting Wire Capacities
for Power (40% Fill)
Wire Size Capacity
#14 12
#12 9
#10 5
©1997 The Wiremold Company • 60 Woodlawn St. • West Hartford, CT 06110 41289 797
1
2
5
3
4
  • Page 1 1