Simplicity 071027-0 User manual

Category
Power generators
Type
User manual

This manual is also suitable for

Models 071026 & 071027
202212GS Rev. - (1/11/2007)
100 Amp / 200 Amp
Automatic Transfer Switch
Installation and Operator’s Manual
TS100A and TS200A
Questions?
Help is just a moment away!
Call: Transfer Switch Helpline
(877) 369-9400 M-F 8-5 CT
Rheem Sales Company
Randleman, NC 27317
(877) 369-9400
Copyright © 2007 Rheem Sales Company. All rights
reserved. No part of this material may be reproduced or
transmitted in any form by any means without the express
written permission of Rheem Sales Company.
Thank you for your purchase of this Rheem/Ruud Automatic Transfer Switch. This product is intended for use with Rheem
and Ruud Home Standby Generator sets ONLY. This is an optional home standby system which provides an alternate source
of electric power and to serve loads such as a gas furnace, refrigeration and communication systems that, when stopped
during any power outage, could cause discomfort, or the like.
This manual contains safety information to make you aware of the hazards and risks associated with transfer switches and
how to avoid them. Rheem has made every effort to provide for a safe, streamlined and cost-effective installation. Each
installation is unique, it is impossible to know of and advise of all conceivable procedures and methods by which installation
might be achieved. We do not know all possible hazards and/or the results of each method or procedure. Save these
instructions for future reference.
This transfer switch requires installation before use. Refer to the Installation section of this manual for instructions on
installation procedures. Only licensed electrical contractors should install transfer switches. Installations must strictly
comply with all applicable federal, state and local codes, standards and regulations.
Where to Find Us
You never have to look far to find support and service for your transfer switch. Consult your Yellow Pages. There are many
Rheem and Ruud authorized service dealers who provide quality service. You can also contact Rheem/Ruud Customer Service
by phone at (877) 369-9400.
Transfer Switch
Model Number
Revision
Serial Number
Date Purchased
1
FrançaisEspañol
Important Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Owner Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installer Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Equipment Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mounting Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Power Wiring Interconnections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Supervisory Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
System Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Testing the Automatic Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Schematic & Wiring Diagram, Models TS100A and TS200A . . . . . . . . 10-11
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table of Contents
2
Important Safety Instructions
This is the safety alert symbol. It is used to alert
you to potential personal injury hazards. Obey all
safety messages that follow this symbol to avoid
possible injury or death.
The safety alert symbol ( ) is used with a signal word
(DANGER, CAUTION, WARNING), a pictorial and/or a safety
message to alert you to hazards. DANGER indicates a hazard
which, if not avoided, will result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury. CAUTION indicates a hazard
which, if not avoided, might result in minor or moderate
injury. NOTICE indicates a situation that could result in
equipment damage. Follow safety messages to avoid or
reduce the risk of injury or death.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others. You must also make sure that the
procedure, work method or operating technique that you
choose does not render the transfer switch unsafe.
Save These Instructions
Use transfer switch only for intended uses.
If you have questions about intended use, ask dealer or contact
Rheem.
Do not expose transfer switch to excessive moisture, dust, dirt,
or corrosive vapors.
Remain alert at all times while working on this equipment. Never
work on the equipment when you are physically or mentally
fatigued.
If connected devices overheat, turn them off and turn off their
circuit breaker/fuse.
NOTICE
Improper treatment of transfer switch can damage it and
shorten its life.
Do not touch bare wires.
Do not use transfer switch with worn, frayed, bare or otherwise
damaged wiring.
Do not handle electrical cords while standing in water, while
barefoot, or while hands or feet are wet.
If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce shock hazard.
Do not allow unqualified persons or children to operate or
service transfer switch.
In case of an accident caused by electrical shock, immediately
shut down all sources of electrical power and contact local
authorities. Avoid direct contact with the victim.
WARNING
Failure to properly ground transfer switch can
result in electrocution.
Despite the safe design of the transfer switch, operating this
equipment imprudently, neglecting its maintenance or being
careless can cause possible injury or death.
WARNING
Transfer switch contains high voltage that can
cause personal injury or death.
Failure to follow above warning could cause personal injury,
damage and/or malfunction of equipment.
WARNING
Low voltage wire cannot be installed in same
conduit as power voltage wiring.
WARNING
Only qualified electricians should attempt installation of
this system, which must strictly comply with applicable
codes, standards and regulations.
3
Introduction
Your Rheem Transfer Switch is supplied with this combined
“Installation and Operator’s Manual”. This is an important
document and should be retained by the owner after the
installation has been completed.
Every effort has been expended to make sure that the
information in this manual is both accurate and current.
However, the manufacturer reserves the right to change, alter
or otherwise improve the system at any time without prior
notice.
For the Home Owner
To help you make informed choices and communicate
effectively with your installation contractor(s),
Read and understand the Owner Orientation Section
of this manual BEFORE contracting or starting your
transfer switch installation.
To arrange for proper installation, contact the store at which
you purchased your Rheem Transfer Switch, your dealer, or
your utility power provider.
The Transfer Switch Warranty is VOID
unless the system is installed by a
licensed electrical professional.
Owner Orientation
The illustrations are for typical circumstances and are meant
to familiarize you with the installation options available with
your transfer switch.
Local codes, appearance, and distances are the factors that
must be considered when negotiating with an installation
professional. As the distance from the existing electrical
service increases, compensation in wiring materials must be
allowed for. This is necessary to comply with local codes and
overcome electrical voltage drops.
The factors mentioned above will have a direct effect
on the overall price of your transfer switch installation.
NOTE: Your installer must check local codes AND obtain
permits before installing the system.
Read and follow the instructions given in this manual.
Follow a regular schedule in caring for and using your
transfer switch, as specified in the manual.
Installer Responsibilities
Read and observe the safety rules.
Read and follow the instructions given in this manual.
Check federal, state and local codes and authority
having jurisdiction, for questions on installation.
Ensure generator is not overloaded with selected loads.
If you need more information about the transfer switch, call
(877) 369-9400, between 8:00 AM and 5:00 PM CT.
Equipment Description
These transfer switches are intended to transfer the entire
electrical load of normal residential installations when used
with the supervisory contacts provided. The load is
connected either to utility power (normal) or home standby
power (generator). The transfer switch monitors utility and
generator voltages and will automatically connect to the
appropriate source of power.
Major components of the transfer switch are a 2 pole double
throw transfer switch, control circuit board, fused utility
terminals and interconnecting wiring. The control board also
has two inputs for current transformers used to sense
generator current.
The transfer switch is solenoid-operated from utility or
generator inputs and contains suitable mechanical and
electrical interlock switches to eliminate the possibility of
connecting the utility service to the generator output. It has
ratings capable of switching full utility power into the
residence. In addition, a manual override lever is provided
for the transfer function.
The control circuit board has active circuits sensing utility
and generator voltages. It creates a signal for the generator
start-up, switch transfer, and retransfer when utility is
restored. The control board also contains red and green
LED’s indicating the power sources available and two relay
operated contacts that provide supervisory control of
external loads.
4
Installation
Unpacking
Delivery Inspection
After removing the carton, carefully inspect the transfer
switch components for any damage that may have occurred
during shipment.
IMPORTANT: If loss or damage is noted at time of delivery,
have the person(s) making delivery note all damage on the
freight bill and affix his signature under the consignor's
memo of loss or damage. If loss or damage is noted after
delivery, contact the carrier for claim procedures. Missing or
damaged parts are not warranted.
Shipment Contents
Automatic Power Transfer Switch
Two Current Transformers
Installation and Operator’s Manual
Mounting Guidelines
The Automatic Transfer Switch is enclosed in NEMA Type 3R
enclosures suitable for indoor or indoor/outdoor use.
Guidelines for mounting the Automatic Transfer Switch
include:
Install the switch on a firm, sturdy supporting
structure.
The switch must be installed with minimum NEMA 3R
hardware for conduit connections.
To prevent switch contact distortion, level and plumb
the enclosure. This can be done by placing washers
between the switch enclosure and the mounting
surface.
Never install the switch where any corrosive substance
might drip onto the enclosure.
Protect the switch at all times against excessive
moisture, dust, dirt, lint, construction grit and corrosive
vapors.
A typical installation of the Automatic Power Transfer Switch
for Models TS100A and TS200A is depicted in Figure 1. An
alternative installation of the Automatic Power Transfer
Switch is depicted in Figure 2.
It is best if the transfer switch is mounted near the utility
watt-hour meter, either inside or outside. Discuss layout
suggestions/changes with the owner before beginning the
system installation process.
5
Main
Circuit
Breaker
Panel
Transfer
Switch
Hot Water
Heater
Air
Conditioner
Contactor
Generator
Watt -
Hourmeter
Branch Circuits
— — — — — — Control Wiring
Disconnect Switch
Service
Disconnect
Main
Circuit
Breaker
Panel
Transfer
Switch
Hot Water
Heater
Air
Conditioner
Contactor
Disconnect Switch
Generator
Watt -
Hourmeter
Branch
Circuits
Emergency
Branch
Circuits
— — — — — — Control Wiring
Emergency
Load Center
Figure 1 - Typical Transfer Switch Mounting for Models TS100A and TS200A
Figure 2 - Alternate Transfer Switch Mounting
6
Power Wiring Interconnections
All wiring must be the proper size, properly supported and
protected by conduit.
Complete the following connections between the transfer
switch, main distribution panel, utility power and generator,
as shown in Figure 3.
1. Ensure utility power is turned OFF. Connect utility
feeder conductors to transfer switch terminals marked
“UTILITY CONNECTION”.
2. Connect utility Neutral conductor to the transfer switch
“NEUTRAL” terminal.
3. Connect main breaker panel feeder conductors to
transfer switch terminals marked “LOAD
CONNECTION”.
4. Connect main breaker panel Neutral conductor to
transfer switch “NEUTRAL” terminal.
5. Connect main breaker panel Ground conductor to the
transfer switch “GND” terminal.
NOTE: Assure grounding electrode conductor is connected
and bonded per applicable federal, state and local codes,
standards and regulations.
6. Connect generator feeder conductors from the
generator control panel to transfer switch terminals
marked “GENERATOR CONNECTION” Each conductor
should pass through hole of current transformer before
making connection.
7. Plug in current transformer leads into “CT1” and “CT2”
on control module.
Failure to follow above warning could cause personal injury,
damage and/or malfunction of equipment.
WARNING
Low voltage wire cannot be installed in same
conduit as power voltage wiring.
Figure 3 - Typical Installation Diagram for Model TS100A & TS200A Transfer Switches
Main
Main Breaker Panel
Ground Bus
Neutral
Bus
To Generator
Neutral
Terminal
To Utility Meter
Supervisory
Contacts
Load
Connection
Ground
Terminal
Generator
Connection
Utility
Connection
7
8. Connect Neutral conductor from the generator control
panel to the transfer switch “NEUTRAL” terminal.
9. Connect generator Ground conductor from the control
panel to the transfer switch “GND” terminal.
NOTE: Assure generator equipment grounding conductor is
connected per applicable federal, state and local codes,
standards and regulations.
10. Connect generator “UTILITY 240 VAC” terminals to
transfer switch “UTILITY 240 VAC” terminals. Use
minimum #14 AWG conductors.
11. Tighten all wire connections/fasteners to proper torque.
See inside transfer switch enclosure for proper torque
values.
Supervisory Control Wiring
1. Terminal strip on control module in transfer switch has
four connections for customer use. There are two sets
of “Normally Closed” contacts available. They will be
activated when generator power is required. These can
be used for supervisory control of large connected
loads on generator. Loads will be allowed to operate if
there is enough generator power available.
NOTE: There are two wireways provided to keep the
supervisory loads separated from each other.
2. Terminals “A-A” on control module are rated for 24 VAC
and air conditioner contactor control. Contacts are
connected in series with the air conditioner contactor
control circuit (Figure 4).
3. Terminals “B-B” on control module are rated for 1 Amp
125 VAC and installer supplied contactor to control a
large load. Example: electric hot water heater. Contacts
are connected in series with the contactor control
circuit (Figure 5).
4. Tighten all wire connections/fasteners to proper torque.
See inside transfer switch enclosure for proper torque
values.
System Setup
You must perform the following on the control module
before operating the system:
If generator is installed in an area regularly subjected to
temperatures below 40°F (4°C), select a 50 second
warm up time by moving jumper installed on JP2
(Figure 6) from ‘20’ position to ‘50’ position.
Place 2 position switch (Figure 6) in ‘NG’ or ‘LP’
position, whichever is appropriate for your system.
Place 3 position switch (Figure 6) to match KW rating
of installed generator.
Controls
Other than a Manual Override lever, there are no operator
controls because this is an automatic transfer switch. The
manual override is to be used only by licensed professionals.
Figure 5 — Terminals “B-B”
B
B
Figure 4 — Terminals “A-A”
Contactor
Neutral
120 VAC
Air Conditioner Contactor
24 VAC
A
A
Figure 6 — Control Module
2 Position
Switch
3 Position
Switch
JP2
CT1 & CT2
Connectors
Supervisory
Contacts
8
Operation
To select automatic transfer operation, do the following:
1. For models TS100A & TS200A, set disconnect switch
that sends utility power to transfer switch to “On
position. This switch is probably located in the main
breaker panel.
2. Set generator main circuit breaker to its “On” position.
3. Install 15 Amp fuse in generator control panel.
4A. If generator is equipped with a system ON/OFF switch,
set switch to “On” position.
4B. If generator is equipped with a AUTO/OFF/MANUAL
switch, set switch to “AUTO” position.
The system will now be in automatic operation mode.
When the generator is providing power to the transfer
switch, the control module is constantly monitoring
generator power. If the air conditioner is called to run, and
there is sufficient generator power available, the control
module will close contacts “A-A” to air conditioner contactor.
Contacts “B-B” will open before contacts A-A close. If loads
are too great for generator, contacts A-A and/or B-B will
open. When air conditioning is not needed, A-A will open. If
enough power is available, B-B will close.
Testing the Automatic Transfer Switch
Turn the disconnect switch feeding the transfer switch
contactor to the “Off” position. The Automatic Sequence of
the system will follow. To go back to utility power, turn the
disconnect to the “On” position.
Automatic Sequence
Utility Fail
The Home Standby Generator set senses when utility voltage
is below 70 percent of nominal. Engine start sequence is
initiated after 6 second time delay.
Engine Warm-Up
Time delay to allow for engine warm-up before transfer fixed
at 20 seconds or 50 seconds with removal of jumper on
control board (see System Setup).
Transfer
Transfer from utility to generator supply occurs after voltage
is above set levels. Minimum engine run time is 5 minutes
after transfer.
Utility Pickup
Voltage pickup level is 80 percent of nominal voltage.
Retransfer
Retransfer from generator to utility supply is approximately
10 seconds after utility voltage supply is above utility pickup
level and minimum run time is completed.
Engine Cool Down
Engine will run for 60 seconds after retransfer.
9
Maintenance
The transfer switch is designed to be maintenance free under
normal usage. However, inspection and maintenance checks
should be made on a regular basis. Maintenance will consist
mainly of keeping the transfer switch clean.
Visual inspections should be done at least once a month.
Access to transfer switch must not be obstructed. Keep
3 feet (1 m) clearance around transfer switch. Check for an
accumulation of dirt, moisture and/or corrosion on and
around the enclosure, loose parts/hardware, cracks and/or
discoloration to insulation, and damaged or discolored
components.
Exercise the transfer switch at least once every three months
as described in section Testing the Automatic Transfer
Switch unless a power outage occurs and home generator
system has gone through an automatic sequence. Allow
generator to run for at least 30 minutes.
Contact a licensed electrical professional to inspect and clean
the inside of your transfer switch at least once a year.
Specifications
UL® 1008 Listed Transfer Switch
Model TS100A
Maximum Load Current . . . . . . . . . . . . . . . . . . . . .100 Amps
Rated AC Voltage . . . . . . . . . . . . . . . . . . . . . . . . . .250 Volts
Poles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50/60 Hz
Fault Current Rating . . . .22,000 RMS Symmetrical Amperes
Supervisory Contacts Rating:
A-A Terminals . . . . . . . . . . . . . . . . . . . . . . . . . .24 Volt AC
B-B Terminals . . . . . . . . . .1 Amp, 125 Volt AC, Pilot Duty
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21 lbs.
Model TS200A
Maximum Load Current . . . . . . . . . . . . . . . . . . . . .200 Amps
Rated AC Voltage . . . . . . . . . . . . . . . . . . . . . . . . . .250 Volts
Poles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50/60 Hz
Fault Current Rating . . . .25,000 RMS Symmetrical Amperes
Supervisory Contacts Rating:
A-A Terminals . . . . . . . . . . . . . . . . . . . . . . . . . .24 Volt AC
B-B Terminals . . . . . . . . . .1 Amp, 125 Volt AC, Pilot Duty
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 lbs.
11
Wiring Diagram, Models TS100A and TS200A
12
Troubleshooting
Problem Cause Correction
Automatic transfer switch does not
transfer to generator
1. Generator breaker open.
2. Generator voltage not acceptable.
1. Reset generator circuit breaker.
2. Refer to generator manual.
Automatic transfer switch does not
transfer to utility
1. Service disconnect breaker open.
2. Utility voltage not acceptable.
1. Reset service disconnect breaker.
2. Wait for utility voltage to return to
normal.
Generator is still running after switch
transfers to utility power
Engine cool down period. Engine should stop after 1 minute.
Supervised loads (air conditioner, etc.)
are not operating when generator is
supplying power
1. A-A or B-B contacts not operating
correctly.
2. Too much load on generator.
3. Current transformer not connected.
4. Broken current transformer.
1. Check A-A or B-B contacts for
proper operation and/or check
control wiring to external load.
2. Decrease load to generator.
3. Plug CT connectors into control
board.
4. Contact local service center.
Generator is still running after utility
power is restored
1. Minimum engine run time has not
elapsed.
2. Fuse(s) in transfer switch is
defective.
1. Wait five minutes for transfer switch
to retransfer to utility power.
2. Check fuse(s) and replace if
necessary.
Warranty
13
PROTECH™ Residential Standby Generators
Models: GEN12S GEN15S GEN20B GEN25B GEN30B
SCOPE of WARRANTY:
· This Limited Warranty provides that a replacement will be furnished for any part of the product which fails in normal use and service during the
Applicable Warranty Period specified, in accordance with the warranty’s terms. The replacement part is warranted for only the unexpired portion of the
original Applicable Warranty Period.
EXCEPTIONS:
· Commercial applications are not covered.
· Units installed as prime power source are not covered.
· Installations for the purpose of life support situations are not covered.
EFFECTIVE DATE of WARRANTY COVERAGE:
The Effective Date is the date of installation if properly documented; otherwise it is the date of manufacture plus six (6) months.
APPLICABLE WARRANTY PERIODS for VARIOUS PARTS:
All Residential Standby Generator Parts are warranted for an Applicable Warranty Period of Four (4) YEARS or 1500 operating hours, whichever occurs
first, after the Effective Date, except for the following specified product parts.
Transfer Switches - Transfer Switches (TS-100 and TS-200) carry a 3 year warranty for all parts.
Engine - The Briggs & Stratton engine warranty is covered by the manufacturer. Refer to Vanguard manual MS-3235
STANDARD PROVISIONS and CONDITIONS:
EXCLUSIONS - THIS WARRANTY WILL NOT APPLY: a) to damages, malfunctions or failures resulting from failure to properly install, operate or maintain the
unit in accordance with the manufacturer’s instructions provided; b) to damages, malfunctions or failures resulting from abuse, accident, fire, flood and
the like; c) to parts used in connection with normal maintenance, such as adjustments, fuel system cleaning and obstruction due to chemical, dirt,
carbon, lime and so forth; d) to units which are not installed in the United States of America or Canada; e) to units which are not installed in accordance
with applicable local codes, ordinances and good trade practices; f) to damages, malfunctions or failures caused by the use of any attachment,
accessory or component not authorized by the manufacturer; g) to wear items such as oil gauges, o-rings, filters fuses, or spark plugs etc.
SHIPPING COSTS: This Warranty does NOT cover shipping costs. You will be responsible for the cost of shipping warranty replacement parts from our factory
to our distributor and from the distributor to the location of your product. You also are responsible for any shipping cost of returning the failed part to
the distributor.
SERVICE LABOR RESPONSIBILITY: This Warranty does NOT cover any labor expenses for service, NOR for removing or reinstalling parts. All such expenses
are your responsibility, unless a service labor agreement exists between you and your contractor.
HOW TO OBTAIN WARRANTY PERFORMANCE: You must promptly report any failure covered by this warranty to the installing contractor or distributor.
Normally, the installing contractor from whom the unit was purchased will be able to take the necessary corrective action by obtaining through his
distributor any replacement parts. If the contractor is not available, simply contact any other local contractor handling RHEEM, RUUD or PROTECH air
conditioning products. The name and location of a local contractor can usually be found in your telephone directory or by contacting a RHEEM, RUUD
or PROTECH air conditioning distributor. If necessary, the following office can advise you of the nearest distributor:
4744 Island Ford Road, Randleman, NC 27317
HOWEVER, ANY REPLACEMENTS ARE MADE SUBJECT TO VALIDATION OF IN-WARRANTY COVERAGE. An item to be replaced must be made available
in exchange for the replacement.
EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY:
This Limited Warranty is the ONLY warranty for the unit given by the manufacturer. No one is authorized to make any warranties on their behalf. ANY
IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, SHALL NOT EXTEND BEYOND THE
APPLICABLE WARRANTY PERIODS SPECIFIED ABOVE. RHEEM’S SOLE LIABILITY WITH RESPECT TO DEFECTIVE PARTS OR FAILURES SHALL BE AS
SET FORTH IN THIS LIMITED WARRANTY, AND ANY CLAIMS FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARE EXPRESSLY EXCLUDED. Some
states do not allow limitations on how long an implied warranty lasts, or for the exclusion of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Limited Warranty gives you specific legal rights, and you may also have other rights which vary from
state to state.
202249E, Rev. -, 1/3/2007
RHEEM SALES COMPANY
Randleman NC
“In the spirit of continuous improvement, we reserve the right to make changes without notice.”
Rheem Sales Company
Randleman, NC 27317
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Simplicity 071027-0 User manual

Category
Power generators
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI