Generac 48kW RD04833ADAL User manual

Type
User manual
4 3 2 1
4 3 1
A
B
A
B
1625 [64.0]
TYP
173 [6.8]
888 [35.0]
OVERALL WIDTH 2424 [95.4]
OVERALL LENGTH
182 [7.2]
TYP
1691 [66.6]
OVERALL
HEIGHT
897 [35.3]
DOOR WIDTH
TYP
608 [23.9]
EXHAUST OUTLET
581
[22.9]
998
[39.3]
CENTER OF GRAVITY
SEE NOTE 5
SERVICE ITEM D3.3L
OIL FILL CAP LEFT
OIL DIP STICK LEFT
OIL FILTER LEFT
OIL DRAIN HOSE RIGHT
RADIATOR DRAIN HOSE RIGHT
COOLANT RECOVERY BOTTLE RIGHT
RADIATOR FILL CAP ACCESS ROOF
AIR CLEANER ELEMENT RIGHT
MUFFLER FRONT
FAN BELT EITHER
BATTERY RIGHT
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 5)
GENERATOR AS SHOWN 1102 [2429]
WITH WOODEN SHIPPING SKID 1147 [2529]
TITLE
INSTALL PROTECTOR D3.3L G2
132 GAL TANK
ISSUE DATE: 02/06/17
SIZE CAGE NO DWG NO
10000031343
REV
BN/A
B
SCALE
0.040 WT-KG 19715.692 SHEET
1 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
SH
1/2 REV B
WINDCHILL VERSION
B.3
RADIATOR/EXHAUST
DISCHARGE AIR
AIR INTAKE
(BOTH SIDES)
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
REFERENCE OWNERS MANUAL FOR
PERIODIC REPLACEMENT PART LISTINGS
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2718 (107") LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT
FOR CONCRETE PAD GUIDELINES
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF
GENERATOR
4. REMOVE THE REAR TANK AND REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTIONS INCLUDING TRANSFER SWITCH CONTROL WIRES
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. ENGINE SERVICE CONNECTIONS
OIL DRAIN: 3/8" NPT
EXHAUST OUTLET: 2" O.D.
7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
AND RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
9. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
WEIGHT: KG [LBS]
DIMENSIONS: MM [INCH]
REAR VIEW
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
CIRCUIT BREAKER
SEE NOTE 3
CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS,
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
REMOVABLE
STUB-UP
COVER
SEE NOTE 4
RIGHT SIDE VIEW
LIFTING PROVISION (4 PLACES)
SEE NOTES 5, 8 AND CENTER
OF GRAVITY DIMENSIONS
VISE ACTION LATCH, ONE
PER DOOR, ONE LIFT-OFF
DOOR ON FRONT, RIGHT
AND LEFT SIDES
LIFT-OFF DOOR PROVIDES ACCESS TO: FUEL
FILL, FUEL LEVEL GAUGE, NORMAL VENT,
INNER TANK EMERGENCY VENT, OUTER TANK
EMERGENCY VENT, OPTIONAL 90% ALARM
ASSEMBLY, OPTIONAL 5 GALLON SPILL BOX
LEFT SIDE VIEW
EXHAUST MUFFLER
ENCLOSED WITHIN
GENERATOR ENCLOSURE
OPEN PUNCHED
LOUVERS TYPICAL ON
BOTH SIDES OF FUEL
TANK VENTILATION
DUCT TO PROVIDE
ADEQUATE CROSS-FLOW
OF AIR VENTILATION
FUEL TANK
VENTILATION
DUCT
TOP VIEW
BATTERY 12 VOLT
NEGATIVE GROUND
REMOVE PANEL TO
ALLOW TANK VENTS
TO TERMINATE OUTSIDE
OF THE GENERATOR
ENCLOSURE (CHECK
LOCAL AND STATE
CODE FOR
APPLICABILITY)
INTERNAL DIVIDER PANEL SEPARATES
FUEL TANK VENTILATION DUCT FROM
THE ENGINE, ALTERNATOR AND
EXHAUST SYSTEM
REMOVE COVER FOR
ACCESS TO RADIATOR
FILL CAP
4 3 2 1
4 3 1
A
B
A
B
850 [33.5]
786 [30.9]
125 [4.9]
*STUB-UP
AREA
125 [4.9]
*STUB-UP
AREA
38 [1.5]
51 [2.0]
253
[10.0]
62 [2.5]
2088 [82.2]
247 [9.7]
314 [12.4]
1308 [51.5] TYP
1419 [55.9] TYP
715 [28.1]
2089 [82.2]
TYP
264 [10.4]
TYP
280 [11.0]
485 [19.1]
658 [25.9]
TYP
117 [4.6]
249
[9.8]
377 [14.8]
529 [20.8]
FUEL TANK
HEIGHT
110 [4.3]
TYP
690 [27.2]
TYP
1216 [47.9]
TYP
1769 [69.6]
TYP
2322 [91.4]
TYP
2422 [95.4]
888 [35.0]
632 [24.9]
167 [6.6]
18.5 TYP
[.73]
851
[33.5]
MOUNTING CENTERS TYP
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
TITLE
INSTALL PROTECTOR D3.3L G2
132 GAL TANK
ISSUE DATE: 02/06/17
SIZE CAGE NO DWG NO
10000031343
REV
BN/A
B
SCALE
0.050 WT-KG SEE ABOVE SHEET
2 of 2
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
SH
2/2 REV B
WINDCHILL VERSION
B.3
FUEL TANK
TOTAL CAPACITY 524 [138.5]
USABLE CAPACITY 500 [132]
REMOVABLE
STUB-UP
COVER
SEE NOTE 4
CAPACITY: LITER [GALLONS]
DIMENSIONS: MM [INCH]
THIS TANK IS LISTED TO UL142 AND ULC5601
*NOTE: STUB-UP AREA FOR HIGH
AND LOW VOLTAGE CONNECTIONS,
CIRCUIT BREAKER, NEUTRAL AND
CUSTOMER CONNECTION OPENING.
REAR VIEW
16.7 [0.66]
MOUNTING HOLES
(10 PLACES) SEE
NOTE 9
LEFT SIDE VIEW
TOP VIEW
HIGH AND LOW
VOLTAGE STUB-UP
AREA
INNER TANK EMERGENCY VENT
(2" NPT FEMALE)
INNER TANK NORMAL VENT
(2" NPT FEMALE)
FUEL LEVEL
GAUGE/SENDER
FUEL FILL
(2" NPT FEMALE)
OUTER TANK
LEAK DETECTOR
OUTER TANK EMERGENCY VENT
(2" NPT FEMALE)
FUEL SUPPLY
CUSTOMER OPTION
(2" NPT FEMALE)
FUEL RETURN
  • Page 1 1
  • Page 2 2

Generac 48kW RD04833ADAL User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI