04/24/00 Document 15452, Revision D
Removable Pipe Plug (3/4-14 THD)
(Use on top or bottom.)
Four dimples provided as hole starters
for mounting backbox to wall
(Hardware supplied by customer)
Outdoor
Backbox
(WP-10)
Gasket
Pull Station
Hardware to fasten
the pull station to the
backbox (Supplied
with the WP-10)
BG10out1.wmf
Installation Procedure
1. Mount outdoor backbox to
conduit pipe (top or bottom).
2. Remove paper backing from
gasket and secure to backbox.
3. Connect wires from conduit to
pull station terminal block.
4. Attach pull station using
hardware supplied with WP-10.
BG10out1.wmf
Use With Rear-access Conduit
If the installation requires running conduit through
the rear of the backbox, drill a new access hole and
plug the unused holes on top & bottom. Use UL
Listed plugs or ones similar to the one supplied.
Per UL requirements, this hole must be located
where the raised lettering will not be damaged.
There is a space of 1.875 in. (47.625 mm) avail-
able between the lettering and the lower edge of
the backbox.
Only UL Listed Liquid-Tight Flexible Metal
Conduit Fittings (Category Control Number
DWTT) are suitable for use with these backboxes.
Correct location for rear-access hole
(Max size 1.875 in., 47.625 mm)
BG-10WP Outdoor Pull Station
PRODUCT INSTALLATION DRAWING