INSTALLATION INSTRUCTIONS
SERIES NS4 FOUR WIRE APPLIANCES
(WALL MOUNT VERSIONS)
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s Series NS4 Horn Strobe Appliances are designed to provide independent operation for the horn appliance, when the
strobe circuit is powered. They are the ideal choice for retrofit applications as well as new installations. The NS4 Appliances are UL
Listed under Standard 1971 for Signaling Devices for the Hearing Impaired and UL Standard 464 for Audible Signal Appliances. The
1575W candela wall mounted strobes are listed at 15 candela under UL Standard 1971 and meet 75 candela intensity on axis with low
current draw. They are listed for indoor use only
and equipped with a NS Mounting Plate (NSMP) that can be mounted to single-
gang, double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox (See Mounting Options). These appliances are
Listed for wall mounting only
. The NS4 Appliances use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan
lens to provide maximum visibility and reliability for effective visible signaling.
The horn portion of the NS4 Appliances can be field set to provide either Continuous Horn or Code 3 Horn. The sound output can be
field set for High (HI) or Low (LO) dBA.
The NS4 Horn Strobe can also be used with a Sync Module (SM) or Dual Sync Module (DSM) to provide synchronized strobe and
synchronized Code 3 signal.
These strobe models are designed for use with either filtered DC (VDC) or unfiltered Full-Wave-Rectified (VRMS) input voltage.
All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE
TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN
IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY
SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
SPECIFICATIONS:
Table 1: UL Ratings
Models Nominal Rated Strobe
Voltage Voltage Range Candela
(VDC/VRMS) (VDC/VRMS) (cd)
NS4-2415W 24 20.0-31.0 15
NS4-241575W* 24 20.0-31.0 15
NS4-2430W 24 20.0-31.0 30
NS4-2475W 24 20.0-31.0 75
NS4-24110W 24 20.0-31.0 110
NS4-1215W 12 10.5-15.6 15
NS4-121575W* 12 10.5-15.6 15
* 1575W models are UL Listed for 15cd and meet 75cd on axis.
Copyright 1997, 1998 Wheelock, Inc. All rights reserved.
P83601 F
Sheet 2 of 11
Table 2: dBA Sound Output for 24VDC
Description Volume Reverberant Per UL 464 Anechoic dBA
20VDC 24VDC 31VDC 20VDC 24VDC 31VDC
Low 79 82 82 88 90 92
Continuous Horn High 85 88 88 93 95 97
Low 75 75 75 88 90 92
Code 3 Horn High 79 82 82 93 95 97
Table 2A: dBA Sound Output for 12VDC
Description Volume Reverberant Per UL 464 Anechoic dBA
10.5VDC 12VDC 15.6VDC 10.5VDC 12VDC 15.6VDC
Low 73* 76 76 82 84 86
Continuous Horn High 82 82 85 87 89 91
Low 67* 70* 70* 82 84 86
Code 3 Horn High 76 76 79 87 89 91
WARNING: NS4 AUDIBLE APPLIANCES SET ON LOW dBA DO NOT MEET THE 75dBA MINIMUM UL
REVERBERANT SOUND LEVEL REQUIRED FOR PUBLIC MODE FIRE PROTECTION SERVICE (NOTED BY * IN
TABLE 1). THIS SETTING IS ACCEPTABLE ONLY FOR GENERAL SIGNALING (NON-FIRE ALARM) USE. USE
THE “HIGH” dBA SETTING WITH THIS TONE FOR PUBLIC MODE SERVICE.
NOTES:
1. Strobes will produce 1 flash per second over the listed voltage range.
2. Anechoic dBA is measured on axis in a non-reflective (free field) test room using fast meter response. For peak dBA (measured
with peak meter response), add 5dBA to anechoic values as shown in Table 2. Reverberant dBA is a minimum UL rating based
on sound pressure measurements in a reverberant test room.
3. All models are UL Listed for indoor use with a temperature range of +32
o
F to +120
o
F (0
o
C to +49
o
C) and maximum humidity of
85% RH.
Check the minimum and maximum output of the power supply and standby battery and subtract the voltage drop from the circuit
wiring resistance to determine the applied voltage to the signaling appliance.
WARNING: ALTHOUGH UL TESTING HAS VERIFIED THAT THESE PRODUCTS FUNCTION EVEN AT 80% OF
THEIR MINIMUM RATING AND 110% OF THEIR MAXIMUM RATING, WHEELOCK STRONGLY RECOMMENDS
THAT THE VOLTAGE APPLIED TO THESE PRODUCTS BE WITHIN THEIR RATED VOLTAGE RANGE. THE
APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE
PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
P83601 F
Sheet 3 of 11
Table 3: Strobe Current Ratings (AMPS)
Rated Average Current
Voltage NS4-2415W NS4-241575W NS4-2430W NS4-2475W NS4-24110W
20.0VDC 0.067 0.084 0.100 0.165 0.209
24.0VDC 0.057 0.072 0.085 0.140 0.169
31.0VDC 0.049 0.059 0.069 0.114 0.138
20.0VRMS 0.087 0.109 0.131 0.217 0.274
24.0VRMS 0.080 0.101 0.121 0.200 0.241
31.0VRMS 0.073 0.088 0.105 0.176 0.217
Voltage NS4-1215W NS4-121575W ------ ------ ------
10.5VDC 0.156 0.199 ------ ------ ------
12.0VDC 0.133 0.170 ------ ------ ------
15.6VDC 0.107 0.137 ------ ------ ------
10.5VRMS 0.202 0.258 ------ ------ ------
12.0 VRMS 0.187 0.238 ------ ------ ------
15.6 VRMS 0.162 0.206 ------ ------ ------
Rated Peak Current *
Voltage NS4-2415W NS4-241575W NS4-2430W NS4-2475W NS4-24110W
20.0VDC 0.169 0.205 0.240 0.400 0.495
24.0VDC 0.173 0.210 0.250 0.400 0.510
31.0VDC 0.178 0.215 0.255 0.425 0.525
20.0VRMS 0.173 0.210 0.250 0.410 0.510
24.0VRMS 0.178 0.215 0.255 0.410 0.525
31.0VRMS 0.182 0.220 0.265 0.435 0.535
Voltage NS4-1215W NS4-121575W ------ ------ ------
10.5VDC 0.405 0.510 ------ ------ ------
12.0VDC 0.410 0.520 ------ ------ ------
15.6VDC 0.415 0.530 ------ ------ ------
10.5VRMS 0.410 0.520 ------ ------ ------
12.0 VRMS 0.415 0.530 ------ ------ ------
15.6 VRMS 0.420 0.540 ------ ------ ------
Rated Inrush Current **
Voltage NS4-2415W NS4-241575W NS4-2430W NS4-2475W NS4-24110W
20.0VDC 0.135 0.135 0.135 0.135 0.135
24.0VDC 0.165 0.165 0.165 0.165 0.165
31.0VDC 0.210 0.210 0.210 0.210 0.210
20.0VRMS 0.175 0.175 0.175 0.175 0.175
24.0VRMS 0.210 0.210 0.210 0.210 0.210
31.0VRMS 0.275 0.275 0.275 0.275 0.275
Voltage NS4-1215W NS4-121575W ------ ------ ------
10.5VDC 0.225 0.225 ------ ------ ------
12.0VDC 0.255 0.255 ------ ------ ------
15.6VDC 0.340 0.340 ------ ------ ------
10.5VRMS 0.320 0.320 ------ ------ ------
12.0 VRMS 0.370 0.370 ------ ------ ------
15.6 VRMS 0.485 0.485 ------ ------ ------
* The time duration for the peak current is 100 microseconds.
** The time duration for the inrush current is 4 milliseconds.
P83601 F
Sheet 4 of 11
Table 3A: Horn Current Ratings (AMPS) for Wall Models
High dBA
Voltage NS4-2415W NS4-241575W NS4-2430W NS4-2475W NS4-24110W
20.0VDC 0.024 0.024 0.024 0.024 0.024
24.0VDC 0.028 0.028 0.028 0.028 0.028
31.0VDC 0.036 0.036 0.036 0.036 0.036
20.0VRMS 0.034 0.034 0.034 0.034 0.034
24.0VRMS 0.044 0.044 0.044 0.044 0.044
31.0VRMS 0.057 0.057 0.057 0.057 0.057
Voltage NS4-1215W NS4-121575W ------ ------ ------
10.5VDC 0.014 0.014 ------ ------ ------
12.0VDC 0.015 0.015 ------ ------ ------
15.6VDC 0.021 0.021 ------ ------ ------
10.5VRMS 0.021 0.021 ------ ------ ------
12.0 VRMS 0.025 0.025 ------ ------ ------
15.6 VRMS 0.030 0.030 ------ ------ ------
Low dBA
Voltage NS4-2415W NS4-241575W NS4-2430W NS4-2475W NS4-24110W
20.0VDC 0.017 0.017 0.017 0.017 0.017
24.0VDC 0.022 0.022 0.022 0.022 0.022
31.0VDC 0.027 0.027 0.027 0.027 0.027
20.0VRMS 0.022 0.022 0.022 0.022 0.022
24.0VRMS 0.033 0.033 0.033 0.033 0.033
31.0VRMS 0.043 0.043 0.043 0.043 0.043
Voltage NS4-1215W NS4-121575W ------ ------ ------
10.5VDC 0.008 0.008 ------ ------ ------
12.0VDC 0.009 0.009 ------ ------ ------
15.6VDC 0.011 0.011 ------ ------ ------
10.5VRMS 0.010 0.010 ------ ------ ------
12.0 VRMS 0.011 0.011 ------ ------ ------
15.6 VRMS 0.015 0.015 ------ ------ ------
WARNING: MAKE SURE THAT THE TOTAL AVERAGE CURRENT, TOTAL PEAK CURRENT AND TOTAL
INRUSH CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY
AND SECONDARY POWER SOURCES, SIGNALING CIRCUITS, SM AND DSM SYNC MODULES DO NOT EXCEED
THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO
WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS
COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH
COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total average, peak and inrush currents: Use Table 3 and 3A to determine the highest value of “Rated Average
Current” for an individual strobe (across the expected operating voltage range of the strobe), and use Table 3 to determine the highest
value of “Rated Inrush Current” or “Rated Peak Current” (whichever is higher) of an individual strobe (across the expected voltage
range of the strobe), then multiply these values by the total number of strobes; be sure to add the currents for any other appliances,
including audible signaling appliances, powered by the same source and include any required safety factors.
If the inrush current or peak current exceeds the power supplies’ inrush capacity, the output voltage provided by the power supplies
may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of
power supplies. For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or
lack of battery backup across the output) may exhibit this characteristic.
CAUTION: Series NS4 are not designed to be used on coded systems in which the applied voltage is cycled on and off.
P83601 F
Sheet 5 of 11
LIGHT DISTRIBUTION PER UL 1971:
Table 4: Horizontal Plane
Horizontal 15cd 1575cd* 30cd 75cd 110cd
Angle (in deg.) UL Min. Typ. 15cd Typ. 1575cd UL Min. Typ. 30cd UL Min. Typ. 75cd UL Min. Typ. 110cd
0 15.0 24 94 30.0 46 75.0 103 110.0 149
5 13.5 24 93 27.0 46 67.5 103 99.0 152
10 13.5 24 88 27.0 45 67.5 104 99.0 151
15 13.5 24 87 27.0 46 67.5 100 99.0 151
20 13.5 23 85 27.0 43 67.5 101 99.0 148
25 13.5 23 80 27.0 43 67.5 98 99.0 140
30 11.3 21 75 22.5 41 56.3 94 82.5 135
35 11.3 20 71 22.5 40 56.3 89 82.5 129
40 11.3 14 62 22.5 39 56.3 83 82.5 124
45 11.3 18 52 22.5 41 56.3 81 82.5 133
50 8.3 18 35 16.5 36 41.3 77 60.5 121
55 6.8 12 32 13.5 27 33.8 60 49.5 85
60 6.0 11 34 12.0 30 30.0 59 44.0 95
65 5.3 13 27 10.5 35 26.3 71 38.5 113
70 5.3 17 19 10.5 29 26.3 73 38.5 81
75 4.5 13 11 9.0 22 22.5 53 33.0 72
80 4.5 8 9 9.0 17 22.5 35 33.0 50
85 3.8 7 10 7.5 15 18.8 30 27.5 38
90 3.8 6 10 7.5 15 18.8 30 27.5 43
Table 4A: Vertical Plane
Vertical 15cd 1575cd* 30cd 75cd 110cd
Angle (in deg.) UL Min. Typ. 15cd Typ. 1575cd UL Min. Typ. 30cd UL Min. Typ. 75cd UL Min. Typ. 110cd
0 15.0 24 94 30.0 46 75.0 103 110.0 149
5 13.5 24 83 27.0 46 67.5 103 99.0 149
10 13.5 24 30 27.0 46 67.5 103 99.0 137
15 13.5 24 19 27.0 45 67.5 102 99.0 120
20 13.5 24 17 27.0 41 67.5 104 99.0 110
25 13.5 21 16 27.0 48 67.5 89 99.0 129
30 13.5 23 15 27.0 40 67.5 96 99.0 114
35 9.8 22 12 19.5 45 48.8 91 71.5 119
40 6.9 13 11 13.8 39 34.3 57 50.6 109
45 5.1 9 10 10.2 24 25.5 36 37.4 66
50 4.0 9 9 8.1 16 20.0 33 29.7 45
55 3.3 8 9 6.6 15 16.3 31 24.2 43
60 2.7 8 9 5.4 15 13.5 31 19.8 40
65 2.4 8 9 4.8 14 12.0 31 17.6 40
70 2.3 8 10 4.5 15 11.3 31 16.5 39
75 2.0 8 10 4.0 14 10.0 31 14.3 39
80 1.8 8 9 3.6 13 9.0 27 13.2 36
85 1.8 7 9 3.6 13 9.0 27 13.2 37
90 1.8 3 9 3.6 9 9.0 12 13.2 28
* 1575W models are UL Listed for 15cd and meet 75cd on axis.
WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING
PARTITIONS OR OTHER VIEWING OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE
LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT CAN BE SEEN BY ALL INTENDED
VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE
THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S
ORIENTATION. FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR
DEATH TO YOU AND/OR OTHERS.
P83601 F
Sheet 6 of 11
WARNING: THE NS4 APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL
BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE
INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SOUND OUTPUT (SPL) SETTINGS:
NOTE: The Code 3 Horn incorporates the temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second
on, 1-1/2 off and repeat) specified by ANSI/NFPA for standard emergency evacuation signaling. The Code 3 Horn should be used
only for fire evacuation signaling and not for any other purpose.
Figure 1: Showing Location of Jumper Plug
JUMPER
PLUGS
CANDELA
SELECTOR
Factory setting is on High dB and Code 3
Figure 2: Jumper plug settings for High dB and Code 3. Figure 3: Jumper plug settings for Low dB and Continuous Horn.
SHOWN
SET ON
HI dB
CENTER PIN
IS NOT USED
SHOWN
SET ON
CODE3
SHOWN
SET ON
LOW dB
SHOWN
SET ON
CONT HORN
CENTER PI N
IS NOT USED
Figure 4: Jumper plug settings for Low dB and Code 3.
Figure 5: Jumper plug settings for High dB and Continuous Horn.
CENTER PIN
IS NOT USED
SHOWN
SET ON
LOW dB
SHOWN
SET ON
CODE 3
(Use needle nose pliers to pull and properly set the jumper
plugs.)
CENTER PIN
IS NOT USED
SHOWN
SET ON
CONT' HORN
SHOWN
SET ON
HI dB
No jumper plugs are needed for Continuous Horn and low dB settings.
However, it is recommended that the jumper plug be retained in the unit
for future use (if needed) as shown in Figure 3, 4 and 5.
Note: The NS4 must be set for Code 3 horn when used with the sync module.
P83601 F
Sheet 7 of 11
WIRING INFORMATION:
Figure 6: Audible signal and strobe operate independently.
FROM FIRE ALARM
CONTROL PANEL (FACP).
PRECEDING APPLIANCE
OR SYNC MODULE *
FROM FACP OR
PRECEDING APPLIANCE
TO NEXT APPLIANCE
OR EOLR
TO NEXT APPLIANCE
OR END-OF-LINE
RESISTOR (EOLR).
STROBE
AUDIBLE
Figure 6A: Audible signal and strobe operate in unison . Red and black shunt wires are supplied.
+
-
-
+
+
-
-
+
FROM FACP
PRECEDING APPLIANCE
OR SYNC MODULE *
BLACK SHUNT WIRE
RED SHUNT WIRE
TO NEXT APPLIANCE
OR EOLR
STROBE
AUDIBLE
* When the sync module is used, the audible tone will be Code 3 sound only. Refer to Sync Module Installation Instruction sheets
SM (P83123) and DSM (P83177) for additional information. Audible will operate only with power applied to both strobe and
audible.
Figure 7.
1) NS4 Appliances have in-out wiring terminals that accepts two #12 to 18 American Wire Gauge (AWG)
wires at each screw terminal. Strip leads 3/8” inches for connection to screw terminals.
2) Break all in-out wire runs on supervised circuit supervision as shown in Figure 7. The polarity shown in
the wiring diagrams is for the operation of the appliances. The polarity is reversed by the FACP during
supervision.
P83601 F
Sheet 8 of 11
MOUNTING OPTIONS:
CAUTION: The following figures show the maximum number of field wires (conductors) that can enter the backbox used with
each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires
and stresses from the wires could damage the product.
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends use of
the largest backbox option shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room
for easy installation and minimum stress on the product from wiring.
C
A
B
D
FLUSH MOUNTING
STD. SINGLE-GANG
BACKBOX
#6-32 X 7/8"
SCREWS
NS MOUNTING PLATE
(NSMP)
NS BEAUTY PLATE (SUPPLIED)
MAXIMUM NUMBER OF CONDUCTORS
BACKBOX
DEPTH
AWG #18 AWG#16 AWG#14 AWG#12
2-1/2" 8 4 4 4
3-1/8" 8 8 8 8
NS MOUNTING PLATE
(NSMP)
NS MOUNTING PLATE
(NSMP)
NS MOUNTING PLATE
(NSMP)
NS BEAUTY PLATE (SUPPLIED)
NS BEAUTY PLATE (SUPPLIED)
NS BEAUTY PLATE (SUPPLIED)
#6-32 X 7/8"
SCREWS
#8-32 X 7/8"
SCREWS
#8-32 X 7/8"
SCREWS
4" SQ. X 1-1/2" DEEP BACKBOX
OR 100mm X 37.5mm
EUROPEAN BACKBOX
FLUSH OR SURFACE MOUNT
SURFACE MOUNT
FLUSH OR SURFACE MOUNTING
DOUBLE-GANG X 2-1/4"
DEEP BACKBOX
5" SQ. X 1-9/16" DEEP
SHBB BACKBOX
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG # 12
8 8 8 8
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG # 12
8 8 8 8
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG # 12
8 8 8 8
P83601 F
Sheet 9 of 11
MOUNTING PROCEDURES:
CAUTION: Check that the installed product will have sufficient clearance and wiring
room prior to installing backboxes and conduit, especially if sheathed multiconductor
cable or 3/4" conduit fittings are used.
1. NS4 models have an integrated NS Mounting Plate (NSMP).
2. The NS Mounting Plate (NSMP) must be oriented correctly when it is mounted to the
backbox. Turn the NSMP so that the arrow below the word ‘‘Top’’ points to the top
side of the NSMP.
3 . NS4 models can be flush mounted to a standard single-gang backbox (Figure A), 4” or
100mm backbox (Figure B) or double-gang backbox (Figure C). NS4 models can also be
surface mounted to a 4’’ or 100mm backbox (Figure B), double-gang backbox (Figure C)
or the SHBB (Figure D).
4. Mount the NSMP first to the backbox. Next slide the Beauty Plate over the NSMP
until the 2 side snaps of the NS Beauty Plate engage with the NSMP.
5. The NS Beauty Plate can be removed from the strobe assembly once engaged. First,
gently insert a screwdriver into one of the slots located on the side edges of the NS
Beauty Plate. Second, gently pull away from the wall with the inserted screwdriver to
disengage the snap. Third, repeat the first and second steps for the second slot.
Finally, gently lift the Beauty Plate away from the NSMP.
6. Mounting hardware for each mounting option is supplied.
7. Conduit entrances to the backbox should be selected to provide sufficient wiring
clearance for the installed product.
8. When terminating field wires, do not use more lead length than required. Excess
lead length could result in insufficient wiring space for the signaling appliance.
9. Use care and proper techniques to position the field wires in the backbox so that
they use minimum space and produce minimum stress on the product. This is especially
important for stiff, heavy gauge wires and wires with thick insulation or sheathing.
10. Do not pass additional wires (used for other than the signaling appliances) through
the backbox. Such additional wires could result in insufficient wiring space for the
signaling appliance.
P83601 F
Sheet 10 of 11
CAUTION: If these appliances are operated within 15 inches of a person's ear, they can produce a sound pressure level that
exceeds the maximum 120dBA permitted by ADA and OSHA rules. Exposure to such sound levels can result in damage to a person's
hearing.
NS4-24110W strobe models are Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate NFPA
Standards and the Authority Having Jurisdiction.
WARNING: INSTALLATION OF WHEELOCK 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS
SHOULD BE WALL MOUNTED AT LEAST 24" BELOW THE CEILING AS FOLLOWS: (1) THE ON AXIS
(DIRECTLY IN FRONT OF LENS) LIGHT OUTPUT SHOULD BE DIRECTED AT THE EYE-LIDS OF THE SLEEPING
PERSON, E.G. PILLOW END OF BED, BED HEAD; (2) NO PART OF THE BED SHALL BE MORE THAN SIXTEEN
(16) FEET FROM THE STROBE NOTIFICATION APPLIANCE. INSTALLERS MUST ADVISE OWNERS AND
OPERATORS OF BUILDINGS WITH SLEEPING OCCUPANTS, E.G. HOTELS AND MOTELS, TO WARN GUESTS,
RESIDENTS AND EMPLOYEES TO NOT MOVE THE BED LOCATION TO A POSITION VIOLATING POINTS (1)
AND (2) ABOVE OR SERIOUS INJURY AND/OR LOSS OF LIFE MAY OCCUR DURING A FIRE EMERGENCY.
WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S
FIELD OF VIEW, UNDER CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN
PERSONS WITH EPILEPSY. STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO
INDUCE SUCH A RESPONSE. TO MINIMIZE THIS POSSIBLE HAZARD, WHEELOCK STRONGLY RECOMMENDS
THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW
WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES. WHEELOCK ALSO
STRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES
COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, STANDARDS, REGULATIONS, CODES AND
GUIDELINES.
NOTE: NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within
the same protected area.
CAUTION: Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or
restrictions on wiring and/or locating Notification Appliance Circuits (NAC) and notification appliances. Some system
communication circuits and/or audio circuits, for example, may require special precautions to assure electrical noise immunity (e.g.
audio crosstalk).
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital appliance, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installation. This
equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions,
may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
1) Reorient or relocate the receiving antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the
equipment into an outlet on a circuit different from that to which the receiver is connected, and 4) Consult the dealer or an
experienced radio/TV technician for help.
The Series NS4 products and these instructions are copyrighted by Wheelock and the Series NS4 products contain proprietary,
confidential and trade secrets of Wheelock. No part of the Series NS4 products and these instructions may be photocopied, printed or
reproduced in any form or modified, adapted, changed or enhanced, or converted to another programming language, or used to create
updated, related or derivative works, without the prior written consent of Wheelock. No part of the Series NS4 products shall be
decomposed, disassembled or reverse engineered.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER
DOCUMENTS DESCRIBING THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR
ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT'S APPLICATION, OPERATION, INSTALLATION
AND TESTING IS USED AT THE SOLE RISK OF THE USER AND WHEELOCK WILL NOT HAVE ANY LIABILITY
FOR SUCH USE.
IMPORTANT: READ SEPARATE "GENERAL INFORMATION" SHEET FOR INFORMATION ON THE
PLACEMENT, LIMITATIONS, INSTALLATION, FINAL CHECKOUT, AND PERIODIC TESTING OF NOTIFICATION
APPLIANCES.
P83601 F
Sheet 11 of 11
Limited Warranty
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated,
maintained and operationally tested in accordance with these instructions at the time of installation and at least twice a year or more
often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation,
maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National
Fire Protection Association (NFPA), Underwriters' Laboratories (UL), Underwriters’ Laboratories of Canada (ULC), National
Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and
other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and
amendments and the requirements of the local authority having jurisdiction (AHJ). Wheelock products when properly specified,
applied, installed, operated, maintained and operationally tested as provided above are warranted against mechanical and electrical
defects for a period of three years from date of manufacture (as determined by date code). Correction of defects by repair or
replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all obligations under this warranty. THE
FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED
BY WHEELOCK IS INSTALLED IN THE PRODUCT. THE FOREGOING LIMITED WARRANTY SPECIFICALLY
EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT. WHEELOCK
MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY
WHETHER AS TO MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER'S
PURPOSES, OR WHETHER IT WILL ACHIEVE THE USER'S INTENDED RESULTS. THERE IS NO WARRANTY AGAINST
DAMAGE RESULTING FROM MISAPPLICATION, IMPROPER SPECIFICATION, ABUSE, ACCIDENT OR OTHER
OPERATING CONDITIONS BEYOND WHEELOCK'S CONTROL.
SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE. WITH RESPECT TO THOSE PRODUCTS, WHEELOCK DOES
NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR-FREE OR
THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE, OR THAT THE FUNCTIONS OR
PERFORMANCE OF THE SOFTWARE WILL MEET THE USER'S REQUIREMENTS. WHEELOCK SHALL NOT BE LIABLE
FOR ANY DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS
IN THE USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE.
THE LIABILITY OF WHEELOCK ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER ON
WARRANTIES, NEGLIGENCE, OR OTHERWISE, SHALL NOT IN ANY CASE EXCEED THE COST OF CORRECTING
DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON EXPIRATION OF THE WARRANTY PERIOD ALL
SUCH LIABILITY SHALL TERMINATE. WHEELOCK IS NOT LIABLE FOR LABOR COSTS INCURRED IN REMOVAL,
REINSTALLATION OR REPAIR OF THE PRODUCT BY ANYONE OTHER THAN WHEELOCK OR FOR DAMAGE OF ANY
TYPE WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL OR CONSEQUENTIAL
DAMAGES. THE FOREGOING SHALL CONSTITUTE THE SOLE REMEDY OF THE PURCHASER AND THE EXCLUSIVE
LIABILITY OF WHEELOCK.
IN NO CASE WILL WHEELOCK'S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT.
Limitation of Liability
WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF
WARRANTY, FOR ANY LOSS OR DAMAGE RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH THIS
CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE, REPAIR OR USE OF ANY PRODUCT
COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART
THEREOF WHICH GIVES RISE TO THE CLAIM. WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND
SHALL CEASE IMMEDIATELY UPON THE INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY
WHEELOCK. IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY CLAIM OF ANY KIND UNLESS IT IS
PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING
IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL OR
CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL
OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION MAY NOT APPLY TO ALL PURCHASERS.
9/98
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11

Wheelock NS4-121575W* User manual

Category
Smoke detectors
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI