Meinberg IMS-M1000-S User manual

Category
Networking
Type
User manual

This manual is also suitable for

MANUAL
IMS-M1000-S
Modular Sync. System and
NTP Server
6th September 2017
Meinberg Radio Clocks GmbH & Co. KG
Front view (Frontansicht) IMS-M1000-S
DEUTSCH
1. Netzteil: 100 - 240 V AC (50-60Hz) / 100 - 240 V DC,
Netzteil: 20 - 72 V DC oder 1
2. GNSS Zeitcode Empfänger (GPS / GLONASS ...)
3.
0 - 36 V DC
LAN-CPU mit USB Schnittstelle, LAN 0 - RJ45 Buchse
4. ACM - Active Cooling Module
ENGLISCH
1. Power Supply: 100 - 240 V AC (50-60Hz) / 100 - 240 V DC,
Power Supply: 20 - 72 V DC or
2. GNSS timecode receiver (GPS / GLONASS ...)
3.
10 - 36 V DC
LAN-CPU with USB interface, LAN 0 - RJ45 jack
4. ACM - Active Cooling Module
ACM
GPS 180
Antenna
Init
Nav Solved
Ant Fail
Fail
COM
234
CPU C05F1
R T N A
0
CONSOLE
38400 / 8N1
1
Fan
Table of Contents
1 Imprint 1
2 Safety instructions for building-in equipment 2
2.1 Additional Safety Hints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.2 Supply Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.3 Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 Safety Hints Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.5 Replacing the Lithium Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.6 Grounding connection M1000-S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 LANTIME S-Chassis: Putting in Operation 6
4 The Modular System LANTIME 7
5 Network Timeserver with GNSS synchronized time base 8
6 Mounting the GPS Antenna 9
6.1 Example: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6.2 Antenna Assembly with Surge Voltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
6.3 Antenna Short-Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7 Booting the GNSS receiver 12
8 Booting the Single Board Computer 13
9 Configuration User Interface 14
10 The graphical user interfaces 15
11 Attachment: Technical Information 17
11.1 Technical Specifications M1000-S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
11.2 ACM - Active Cooling Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
11.3 Available Modules and Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
11.4 TERMINAL (Console) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
11.5 USB Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
11.6 IMS Module Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
11.6.1 IMS M1000 Slot Assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
11.6.2 Power Supply 100-240 V AC/DC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
11.6.3 Power Supply 20-72 V DC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
11.6.4 GPS Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.6.5 GNSS Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
11.6.6 PZF Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
11.6.7 TCR Clock - Time Code Reader and Generator . . . . . . . . . . . . . . . . . . . . . . . . . 28
11.6.8 RSC Switch Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11.6.9 LAN-CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
11.6.10 MRI - Standard Reference Input Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
11.6.11 ESI - Telecom Synchronisation References . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11.6.12 LNE-GbE: Network Expansion with Gigabit Support and SFP Option . . . . . . . . . . . 41
11.6.13 HPS-100: PTP / SyncE / Hardware NTP Interface . . . . . . . . . . . . . . . . . . . . . . 47
11.6.14 TSU V3: IEEE-1588 Time Stamp Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
11.6.15 CPE and BPE Output Modules (Frontend - Backend, Eurocard) . . . . . . . . . . . . . . 51
11.6.16 LIU - Line Interface Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
11.6.17 LNO - 10MHz Sinus Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
11.6.18 FDM - Frequency Deviation Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
0
11.6.19 REL1000: Error Relay Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
11.6.20 SCG-U Studio Clock Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
11.6.21 VSG - Video Sync Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
12 Declaration of Conformity 76
Date: 6th September 2017 IMS-M1000-S
1 Imprint
1 Imprint
Meinberg Funkuhren GmbH & Co. KG
Lange Wand 9, 31812 Bad Pyrmont / Germany
Phone: + 49 (0) 52 81 / 93 09 - 0
Fax: + 49 (0) 52 81 / 93 09 - 30
Internet: http://www.meinberg.de
Date: 2017-09-06
IMS-M1000-S Date: 6th September 2017 1
2 Safety instructions for building-in equipment
This building-in equipment has been designed and
tested in accordance with the requirements of Stan-
dard IEC60950-1 "Safety of Information Technology
Equipment, including Electrical Business Equipment".
During installation of the building-in equipment in
an end application (i.e. rack) additional requirements
in accordance with Standard IEC60950-1 have to be
taken into account.
NOTE: First attach the case to protective earth -
before you connect the M1000-S with the power line
(see chapter Grounding connection M1000-S).
General Safety instructions
The building-in equipment has been evaluated for use in office environment (pollution degree 2) and
may be only used in this environment. For use in rooms with a higher pollution degree more stringent
requirements are applicable.
The equipment/building-in equipment was evaluated for use in a maximum ambient temperature of 40
C.
The building-in equipment may not be opened.
Protection against fire must be assured in the end application.
The ventilation opening may not be covered.
For AC Supply 100-240 V AC
The building-in equipment is a class 1 - equipment and must be connected to an earthed outlet
(TN Power System).
For safe operation the building-in equipment must be protected by max 16 A fuse in the power installation
system.
Disconnection of the equipment from mains is done by pulling the mains plug at the outlet. Don’t use the
connector at the module for disconnection from mains.
For DC Supply 100-240 V DC
The device can be disconnected outside the unit in accordance with the regulations as in IEC 60950-1
(e.g. through primary side line protection).
Assembling and disassembling of the power connector is only allowed if the device is disconnected from
power supply (e.g. trough primary side line protection).
All feed lines are sufficiently protected and dimensioned.
Fuse: T2.5A
Connector Diameter: 1mm
2
- 2,5mm
2
/ 17AWG - 13AWG
2 Date: 6th September 2017 IMS-M1000-S
2 Safety instructions for building-in equipment
2.1 Additional Safety Hints
This manual contains important information for the installation and operation of this device as well as for your
safety. Make sure to read carefully before installing and commissioning the device.
Certain operating conditions may require the observance of additional safety regulations not covered by this
manual. Nonobservance of this manual will lead to a significant abatement of the security provided by this
device. Security of the facility where this product is integrated lies in the responsibility of the installer.
The device must be used only for purpose named in this manual, any other use especially opteration above the
limits specified in this document is considered as improper use.
Keep all documents provided with the device for later reference.
This manual is exclusively for qualified electricians or by a qualified electrician trained personnel who are
familiar with the applicable national standards and specifications, in particular for the construction of high
voltage devices.
2.2 Supply Voltage
WARNING!
This device is powered by a dangerous voltage. Nonobservance of the safety instructions of this manual may
lead to serious damage to persons and property and to danger to life! Installtion, commissioning, maintenance
and operation of this device are to be carried out by qualified personnel only.
The general safety instructions and standards ( e.g. IEC, DIN, VDE, EN ) for installation and work with
high voltage equipment as well as the respective national standards and laws must be observed.
NONOBSERVANCE MAY LEAD TO SERIOUS DAMAGE TO PERSONS AND PROPERTY AND TO DAN-
GER TO LIFE!
The device may not be opened. Repair services may only be carried out by the manufaturer.
Supply lines for this decice must be equipped via an appropriate switch that must be mounted close to the
device and must be marked as a mains switch for the device.
To ensure safe operation supply mains connected to this decice must be equipped with a fuse and a fault-
current circuit breaker according to the applicable national standards for safe operation.
The device must be connected to a protective earth with low grounding resistance according to the applicable
national rules.
IMS-M1000-S Date: 6th September 2017 3
2.3 Cabling
WARNING!
DANGER TO LIFE BY ELECTRICAL SHOCK! NO LIVE WORKING!
Wiring or any other work done the connectors particularly when connectors are opened may never be carried out
when the installation is energized. All connectors must be covered to prevent from accidental contact to life parts.
ALWAYS ENSURE A PROPER INSTALLATION!
2.4 Safety Hints Antenna
WARNING!
DANGER TO LIFE BY ELECTRICAL SHOCK!
Make sure to comply with the occupational health and safety standards when installing the antenna. Never
work without a proper fall protection device!
Do not carry out any installation or maintenance work on the antenna system or cabling when there is a
potential risk of lightning.
Surge Voltage Protector
Due to extremely high currents associated with lightning no surge protection device can provide absolute safety
from the impacts caused by lightning!
4 Date: 6th September 2017 IMS-M1000-S
2 Safety instructions for building-in equipment
2.5 Replacing the Lithium Battery
Skilled/Service-Personnel only: Replacing the Lithium Battery
The life time of the lithium battery on the receiver boards is at least 10 years. If the need arises to replace the
battery, the following should be noted:
There is a Danger of explosion if the lithium battery is replaced incorrectly. Only identical batteries or
batteries recommended by the manufacturer must be used for replacement.
The waste battery has to be disposed as proposed by the manufacturer of the battery.
2.6 Grounding connection M1000-S
To ensure a safe operation and to fulfil the requirements in accordance with DIN EN 90650, the system must
be correctly connected to an equipotential grounding bus. On the side of the chassis there is a grounding
connector. The mounting components (without a cable) are included.
1: Screw M4x6
2: Tooth washer M4
3: Plain washer M4
4: Ring or fork lug
5: Nomel washer
Note:
Use a grounding cable with >= 1,5mm
2
Please ensure a correct crimp-connection!
IMS-M1000-S Date: 6th September 2017 5
3 LANTIME S-Chassis: Putting in Operation
Initial Configuration Wizard
After the boot-phase of the device, you have to establish a serial connection with the LAN-CPU. Via the terminal
connection it is possible to configure parameters with a command line interface. Use a NULL-Modem cable or
a CAB-CONSOLE-RJ45 cable to connect your PC or Laptop. You can use for example the standard Hypert-
erminal program, shipped with your Windows operating system. Configure your terminal program with 38400
Baud, 8 Databits, no parity and 1 Stopbit. The terminal emulation has to be set to VT100. After connecting
the LANTIME the login message appears (press RETURN for initial connection):
After the connection is successfully established use your login credentials in the welcome screen to enter
a console.
Welcome to Meinberg LANTIME
login: _
Default settings are:
Login: root
Password: timeserver
(It may be the case to press a RETURN button again).
After successful registration change the current path to /wizard/. Start now the LANTIME Basic Configu-
ration Wizard with “start wizard”.
The following Wizard Welcome screen is now displayed:
Confirm with "y" to start the configuration for all the following settings.
At the end please confirm your configuration.
6 Date: 6th September 2017 IMS-M1000-S
4 The Modular System LANTIME
4 The Modular System LANTIME
The basic-system M1000-S is a set of equipment, composed of a reference clock (e.g.: GNSS satellite controlled
clock, long wave radio clock or IRIG/AFNOR time code reader), a single-board computer SBC LX800 500 MHz
with integrated network card and a power supply unit, all installed in a metal desktop case and ready to operate.
The implemented NTPD distributes the reference time from the used receiver cyclic in the network. Infor-
mation on the NTPD can be monitored via the net work.
The installation of a LANTIME Server is very easy for the system/network administrator. The network ad-
dress, the netmask and the default gateway have to be configured (see chapter "Sarting of Operation"). The
network address or the equivalent name of LANTIME has to be shown to all NTP clients in the TCP/IP network.
As well as NTP the Linux system also supports a number of further network protocols: HTTP(S), FTP, SSH and
Telnet. Because of this remote configuration or status requests can come from any WEB browser. This access
via the network can be deactivated. Changes in the receiver status, errors or other important events are logged
either on the local Linux system or on an external SYSLOG-Server. In addition messages can be sent to a data
center via SNMP traps or automatically generated e-mails where they can be recorded. Furthermore all alarm
messages can be displayed by a large display which is accessed via network connection (e.g. VP100/20/NET).
In order to avoid a service interruption several LANTIME NTP servers can be installed in the same network to
obtain redundancy.
IMS-M1000-S Date: 6th September 2017 7
5 Network Timeserver with GNSS synchronized
time base
The LANTIME (Local Area Network Time Server) provides a high precision time base to a TCP/IP network
(Stratum-1-Server). The NTP (Network Time Protocol) is used to synchronize all NTP clients with the ref-
erence. The several LANTIME variants differ from each other by the time reference and output configuration.
A GNSS receiver (GPS, GLONASS, Galileo or BeiDou), a long wave receiver (like DCF77, MSF or WWVB)
or an IRIG time code receiver can be integrated as an internal reference as well as a combination of these
references ( hybrid system). External references are also possible.
The LANTIME system is a set of equipment composed of a internal receiver, a single-board computer and
a power supply, all installed in a metal 19 inch modular chassis and ready to operate. A simplified LINUX
operating system is installed on the single-board computers flash disk. Eight push buttons and a display can
be used to configure and monitor the time server.
After the net work connection has been established the time server can also be configured and monitored
remotely from a workstation via TELNET or FTP. An integrated web server enables access to the LANTIME by
using an ordinary web browser.
8 Date: 6th September 2017 IMS-M1000-S
6 Mounting the GPS Antenna
6 Mounting the GPS Antenna
The GPS satellites are not stationary, but circle round the globe with a period of about 12 hours. They can only
be received if no building is in the line-of-sight from the antenna to the satellite, so the antenna/downconverter
unit must be installed in a location that has as clear a view of the sky as possible. The best reception is
achieved when the antenna has a free view of 8
angular elevation above the horizon. If this is not possible, the
antenna should be installed with the clearest free view to the equator, because the satellite orbits are located
between latitudes 55
North and 55
South. If this is not possible, you may experience difficulty receiving the
four satellites necessary to complete the receivers position solution.
The antenna/converter unit can be mounted on a wall, or on a pole up to 60 mm in diameter. A 50 cm
plastic tube, two wall-mount brackets, and clamps for pole mounting are included. A standard RG58 coaxial
cable should be used to connect the antenna/downconverter unit to the receiver. The maximum length of cable
between antenna and receiver depends on the attenuation factor of the coaxial cable.
Up to four GNSS receivers can be run with one antenna/downconverter unit by using an optional antenna
splitter. The total length of an antenna line from antenna to receiver must not be longer than the max. length
shown in the table below. The position of the splitter in the antenna line does not matter.
The optional delivered MBG S-PRO protection kit can also be used for outdoor installation (degree of protec-
tion: IP55). However, we recommend an indoor installation, as close as possible to the wall where the antenna
cable is entering, to minimize the risk of overvoltage damage, for example by lightning.
6.1 Example:
Type of cable diameter Ø Attenuation at 100MHz max lenght.
[mm] [dB]/100m [m]
RG58/CU 5mm 17 300 (1)
RG213 10.5mm 7 700 (1)
(1)This specifications are made for antenna/converter units produced after January, 2005
The values are typically ones; the exact ones are to find out from the data sheet of the used cable
IMS-M1000-S Date: 6th September 2017 9
6.2 Antenna Assembly with Surge Voltage Protection
Optional a surge voltage protector for coaxial lines is available. The shield has to be connected to earth as
short as possible by using the included mounting bracket. Normally you connect the antenna converter directly
with the antenna cable to the system.
GPS Antenna
free view to the sky!
Cable Slot
N-Norm female
N-Norm male
N-Norm male
N-Norm female
N-Norm female
N-Norm male
Meinberg GPS
N-Norm male female
or BNC male female
as short as possible
Ground lead to PE rail
(Protective Earth)
Cable ca. 1,5 mm Ø
fastened at the surge protector
10 Date: 6th September 2017 IMS-M1000-S
6 Mounting the GPS Antenna
6.3 Antenna Short-Circuit
(systems with front di splay only)
In case of an antenna line short-circuit the following message appears in the display:
ANTENNA
SHORT-CIRCUIT
DISCONNECT POWER
! ! !
If this message appears the clock has to be disconnected from the mains and the defect eliminated. After that
the clock can be powered-up again. The antenna supply voltage must be 15VDC .
IMS-M1000-S Date: 6th September 2017 11
7 Booting the GNSS receiver
If both the antenna and the power supply have been connected, the system is ready to operate. About 2 minutes
after power-up the receivers oscillator has warmed up and operates with the required accuracy. If the receiver
finds valid almanac and ephemeris data in its battery buffered memory and the receivers position has not
changed significantly since its last operation, the receiver can determine which satellites are presently in view.
Only a single satellite must be received to synchronize and generate output pulses, so synchronization can be
achieved within one minute after power-up.
If the receiver position has changed by more than one hundred kilometers since last operation, the satel-
lites’ real elevation and Doppler might not match those values expected by the receiver, and this will force the
receiver to start scanning for satellites. This mode is called Warm Boot because the receiver can obtain ID
numbers of existing satellites from the valid almanac. When the receiver has found four satellites in view it can
update its new position and switch to Normal Operation. If the almanac has been lost (because the battery
has been disconnected) the receiver has to scan for a satellite and read in the current almanac. This mode is
called Cold Boot. It takes 12 minutes until the new almanac is complete and the system switches to Warm Boot
mode, scanning for other satellites.
12 Date: 6th September 2017 IMS-M1000-S
8 Booting the Single Board Computer
8 Booting the Single Board Computer
The LINUX operating system is loaded from a packed file on the flash disk of the single board computer to a
RAM disk. All files of the flash disk are stored in the RAM disk after booting. This guarantees that the file
system is in a defined condition after restart. This boot process takes approximately two minutes. During this
time the following message appears on the display:
NORMAL OPERATION
NTP: not sync
Thu, 01.01.2008
UTC 12:00:00
NORMAL OPERATION
NTP:sync to local
Thu, 01.01.2008
UTC 12:00:00
After starting the LINUX system, the network function is initiated and the communication program with the
receiver and the NTPD (NTP daemon) is started. Then NTPD starts synchronization with the reference clocks
(usually the hardware clock of the single board computer and the integrated receiver clock). The message "NTP:
sync to local" is displayed until synchronization is complete.
For the synchronization of the NTPD with the time reference it is necessary that the receiver is synchronous
with the incoming time signal. In this case the following message is monitored on the display:
NORMAL OPERATION
NTP: Offs. 2ms
Thu, 01.01.2008
UTC 12:00:00
The second line shows the user that the NTPD is synchronized with the receiver with an offset of 2ms (Figure).
Because of the internal time of the NTP which is adjusted by a software PLL (phase locked loop) it takes a
certain time to optimise this offset. The NTPD tries to keep the offset below +-128 ms; if the offset becomes
too large, the system time is set with the receivers time. Typically values for the offset are +-5 ms after the
NTPD has already synchronized.
IMS-M1000-S Date: 6th September 2017 13
9 Configuration User Interface
There are several ways to configure the LANTIME parameters:
Command Line Interface (CLI) via TELNET
Command Line Interface via SSH
Command Line Interface via serial terminal (38400/8N1/VT100)
HTTP Interface
Secure HTTP Inter face (HTTPS)
SNMP Management
A startup wizard is available for the initial operation of the LANTIME. Once a connection to the system has been
established with an SSH session (network) or via the LANTIME serial interface, this command-line based tool
can be used for initial configuration (see also chapter "LANTIME S-Chassis: Putting in Operation"). Once the
IPv4 address, net mask and IPv4 GATEWAY have been set up or the network interface has been automatically
configured with DHCP/Autoconf, further configuration changes can be done via a network connection:
To set up a TELNET connection the following commands are entered (replace 198.168.10.10 with the IP of
your LANTIME):
telnet 198.168.10.10 // LANTIME IP address
user: root
password: timeserver
With “setup” the configuration program is started.
To set up a SSH connection the following commands are entered:
ssh [email protected] // LANTIME IP address
password: timeserver
With “setup” the configuration program is started.
To set up a HTTP connection the following address is to enter in a web browser:
http://198.168.10.10 // LANTIME IP address
password: timeserver
To set up a Secure HTTP (HTTPS) connection the following address is entered in a web browser:
https://198.168.10.10 // LANTIME IP address
password: timeserver
14 Date: 6th September 2017 IMS-M1000-S
10 The graphical user interfaces
10 The graphical user interfaces
The LANTIME offers two different options for configuration and status management: An extensive and powerful
web interface and SNMP. In order to use the SNMP features of your LANTIME, you need special software
like management systems or SNMP clients. In order to use the web interface, all you need is a web browser
(LANTIME supports a broad range of browsers, we recommend Mozilla Firefox).
The WEB Interface
The web interface can be used by more than one user in parallel, but the two or more running sessions may
influence each other. We explicitly do not recommend the parallel usage of the configuration interfaces.
Connect to the web interface by entering the following address into the address field of your web browser:
http://198.168.10.10 (You need to replace 198.168.10.10 with the IP address of your LANTIME).
Default Login
User: root
Password: timeserver
IMS-M1000-S Date: 6th September 2017 15
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82