
Technical Support, Controls Info no.:0179-096
E-mail : CG-EUR-DK-SupportControls@jci.com
Web: www.sabroe.com
Revision: 1.1 - Updated: 10-10-2017 Author: IVH Page 16 of 19
Compressor control and surveillance
The various types of screw compressors start in different ways. Some types have
prelubrication whereas others start directly. Some compressors have an oil flow switch or an
oil level switch and others do not have any switch at all. If no switch is present, it is
necessary to mount a jumper in the digital input no. 5 (terminal X3, 9-10) In the Unisab III.
The function of the solenoid valves for decreasing and increasing the capacity and Vi slide
positions also depends of the specific compressor.
For Sabroe compressors SAB 110, 128, 163 and 202 the solenoid valves for decreasing the
capacity slide (and the Vi slide position if Automatic volume ratio) are Normal Open (NO).
The solenoid valves for increasing the capacity slide and the Vi slide position are Normal
Close (NC).
For all other compressor types the solenoid valves for decreasing and increasing the
capacity (and Vi slide position if Automatic volume ratio) are usually all Normal Close (NC).
The oil pressure shown on the Unisab III is for most compressor types calculated as
measured oil pressure (after oil filter) – measured suction pressure. However, for SAB 80
the oil pressure is calculated as measured oil pressure (after oil pump) – suction pressure.
For VMY Mk2-2.5 the oil pressure is calculated as measured oil pressure (after oil filter) –
measured discharge pressure.
The differential pressure across the oil filter is for most compressor types calculated as
measured oil pressure before filter – measured oil pressure after filter. However, for SAB 80
and Stal compressors the differential pressure is calculated as discharge pressure – oil
pressure after filter. The shown differential pressure will thus be 0.1 to 0.7 bar higher than
the actual pressure loss across the filter due to the pressure loss across the oil separator
and the oil cooler.
Starting sequence
For a description of the starting sequence for the specific compressor type please see the
Unisab III Engineering Manual section 3 “Compressor control and surveillance”.
Alarm surveillance
During start, the following alarms are delayed. The timer settings depend on the specific
compressor type.
High filter differential Pressure
The delayed alarms are described in section 6.4 “TIMERS” in the Unisab III Engineering
manual. For additional info on the alarms see section 2 “Alarms and shutdowns” in the
Unisab III Engineering manual.