11 Intrinsically safe installation instructions
11.1 Product marking
Fig 11.1 Product marking
IECEx Hazardous or Classified Location
Certificate : IECEx DEK 16.0032X
- Intrinsically safe
Ex ia IIC T4 Ga
Ex ia IIIC T80°C Da
ATEX Hazardous or Classified Location
Certificate : DEKRA 16ATEX0064 X
- Intrinsically safe
II 1 G Ex ia IIC T4 Ga
II 1 D Ex ia IIIC T80°C Da
FM Hazardous or Classified Location
- Intrinsically safe, Class I, II, III Div.1,
Groups ABCDEFG, T4
- Class 1, Zone 0, AEx ia IIC T4 Ga
Zone 20 AEx ia IIIC T80C Da
CSA Hazardous of Classified location
Certificate : CSA 17CA70167494X
- Intrinsically safe
Class I, Division 1, Groups A, B, C and D T4;
Class I, Division 2, Groups A, B, C and D, T4;
Class II, Division 1, Group E, F and G, T80°C;
Class III, Division 1, T80°C
Ex ia IIC T4 Ga
Ex ia IIIC T80°C Da
Ex ic IIC T4 Gc
Ambient temperature:
T4 @ Ta = -20°C...+50°C IP66
Control Module
Type Label
Terminal
compartment
Lockable
Module cover
11.2 ATEX / IECEx Intended use
The Control Module QC54..P1.. of the
FieldQ pneumatic actuator is a Group II category 1
(ATEX) equipment with protection level Ga (IECEx)
and intended for use in areas in which explosive
atmospheres caused by mixtures of air and gases,
vapours, mists or by air/dusts are likely to occur.
The FieldQ pneumatic actuators is a Group II category
2 equipment and intended for use in areas in which
explosive atmospheres caused by mixtures of air and
gases, vapours, mists or by air/dusts are likely
to occur.
Therefore it may be used in hazardous area classified
Zones 1, 2 (Gasses) and/or 21, 22 (Dust).
11.3 Safety instructions
WARNING
• Personal injury or property damage caused
by fire or explosion may occur if the module
is opened in any area which contains a
potentially explosive atmosphere or has been
classified as hazardous.
• The material for the Control Module
housing is an aluminium alloy. When the unit
is used in a potentiality explosive
atmosphere, requiring EPL Ga, the unit must
be installed in such a way, that even in the
event of rare incidents, an ignition source due
to impact or friction between the enclosure
and iron/steel is prevented.
• For applications in explosive atmospheres
caused by air/dust mixtures and where
equipment with EPL Da is required, the
surface temperature has been determined
for a dust layer with a thickness of 5 mm
maximum.
• Potential electrostatic charging hazard, clean
only with a damp cloth - danger of
propagating discharge.
• The apparatus shall be installed in such a way
that the risk from electrostatic discharges
and propagating brush discharges caused by
rapid flow of dust is avoided.
• Precaution shall be taken to avoid danger of
ignition due to electrostatic charges on the
marking plate of the enclosure.
• Substitution of electronics cartridge, switch
cartridge, pilot valve cartridge, pneumatic
cartridge, enclosure and seals must be with
parts from Emerson else the suitability for
Division 2 will be impaired.
!