Reznor CAUA Operating instructions

Type
Operating instructions

Reznor CAUA is a reliable and efficient ignition control system designed to enhance the performance of your heating equipment. With its advanced features and compatibility with various heating systems, it offers a range of benefits for users seeking optimal heating solutions.

Reznor CAUA is a reliable and efficient ignition control system designed to enhance the performance of your heating equipment. With its advanced features and compatibility with various heating systems, it offers a range of benefits for users seeking optimal heating solutions.

Form CP-CAUA-IGN CNTRL, Mfg #178435R6, Page 1
Replacement Kit Instructions
Applies to: Model CAUA
Form CP-CAUA-IGN CNTRL (04-15)
Obsoletes Form CP-CAUA-IGN CNTRL (03-15)
Instructions for DSI Controller Replacement Kit, P/N 258251
Convert from a RAM 3MC4-06 (Serial No. Code 76) or J/C G822KCC-5401D
(Serial No. Code 77) Controller to UTEC 1097-211 (Serial No. Code 78)
Installation Instructions
Kit Components
Kit P/N 258251, Ignition Conversion FROM DSI Controller RAM 3MC4-06 or
J/C G822KCC-5401D TO DSI Controller UTEC 1097-211
Qty P/N Description
1 195573 DSI Control Board, Heat Only,
UTEC 1097-211
(Labeled UTEC ID Code 417)
1 257666 9-Pin Wire Harness Assembly (identied as P1 on the wiring diagram)
1 257675 5-Pin Wire Harness Assembly (identied as P3 on the wiring diagram)
1 257013 Drill Template See Instructions, STEP 3.
1 257665 18” Ignition Cable See Instructions, STEP 4.
7 142860 1/4" Quick Connect Terminal (Red)
Use as needed to make wire connections.1 1350 Spade Terminal
2 22573 Crimp Terminal
1 129869
24" Red Wire Assembly with one
Terminal
Used to connect ame rollout switch to high limit control
- See Instructions, STEP 5, and Limit Switch operation.
6 20913 Cable Ties Use as needed for excess wire length.
1 203058 Circuit Board Notice Label
See Instructions, STEP 6.
1 258250 Wiring and LED Code Label
Replacement
DSI Control
Board,
UTEC Model
1097-211,
P/N 195573
Spark
Transformer
1
2
3
4
5
6
7
8
9
9-Pin
Harness
Plug P1
1
2
3
4
5
5-Pin Harness
Plug P3
1. Turn off gas supply and disconnect the electric
power to the heater.
2. Remove the DSI control. - Open the control
compartment and locate the ignition control module.
Disconnect the wiring including the spark ignitor lead
from the DSI control. Remove the four screws and the
controller.
3. Attach the replacement DSI control. - In the kit,
locate the drill template (P/N 257013). Position the
template with the painted side facing up and align it
over the mounting holes. Justify the holes for the new
DSI toward the bottom of the panel. Mark the new
hole locations. Drill four 3/16” holes. Position the new
DSI control so that the spark transformer is located
nearest to the spark electrode on the burner. Snap the
controller into the holes.
4. Install the ignition wire. - Locate the spark electrode
(ignitor) on the burner. Remove the existing ignitor wire
and replace it with the new one in the kit. Connect the
other end to the spark transformer on the new DSI
board.
5. Connect the wires according to the new wiring
diagram label.
a) Connect the terminals from the 5-pin connector
(identied as P3 on the diagram) to the appropriate
terminals on the thermostat terminal strip.
b) Make connections from the 9-pin connector
(identied as P1) according to the wiring diagram. As
a wire is connected, it may be cut to a shorter length.
Attach terminals as needed.
c) Connect existing wires to the new DSI board wire
terminals as shown on the diagram. If the terminal on
the line voltage wire is 3/16”, cut the terminal off, strip
the wire, and add one of the 1/4” quick connects from
the kit. Connect to Terminal “L1”. Use cable ties as
needed for routing and excess length.
Wire
Terminals
WARNING
To ensure safe and proper operation, read and follow the installation instructions. Failure
to do so could result in property damage, personal injury, and/or death.
Form CP-CAUA-IGN CNTRL, Mfg #178435 R6, Page 2
Installation
Instructions
(cont’d)
Circuit Board
Notice Label,
P/N 203058
Old Board New Board
ACC EAC/BLO
24 VAC HOT SEC
Ground COM
LINE VAC HOT L1
CMB BLWR IND
Wiring for CAUA - DSI Board
Replacement
(Label, P/N 258250)
NOTE: To cover all
applications, connections
are shown for single-stage
(AG1) and two-stage (AG2)
controls and for both direct
and belt drive motors.
Make the connections that
apply to the options on the
unit being serviced.
d) Connect the 24” red wire assembly to the rollout
switch (located on the burner box top) and the high limit
switch wire lead. Use one of the crimp nuts to make the
connection to the limit control wire.
Note there are ve terminals with different terminology
between the two boards; see cross reference:
6. Apply new Labels. (See illustrations below.)
Wiring Diagram - On the left panel inside the burner compartment, adhere the
wiring diagram label.
Circuit Board Notice Label - Apply below the new wiring diagram label.
7. Turn on the power and gas. Start the heater and check for proper operation.
3
3
TERMINAL
STRIP
THERMOSTAT
C
Y1
Y2
W1
W2
G
FAN RELAY
COIL
Y
7
R
RELAY COIL
7
CONTACTOR COIL
MOTOR
W
BK
BK
BK
FAN
RELAY CONTACTS
2
4
6
BK
R
W
G
Y
P3-4
P3-3
P3-2
R
G
W
C
Y1
Y2
W1
W2
P3-1
Y
P3-5
BR
G
FAN RELAY
COIL
Y
8 7
BR
7
R
C
BR
RELAY COIL
CUSTOMER'S COOL
7
W2
TERMINAL STRIP
THERMOSTAT
L1
L2
BK
W
24V
R
LINE VOLT
Y
Y
R
BL
BK
PLUG PILOT OPENING
HONEYWELL TWO STAGE
REDUNDANT GAS VALVE
PILOT
PV
HI
HIGH
STG
LOW
STG
C
MV
R
BR
GAS VALVE
HONEYWELL
MV
MV
BL
BR
ACB HEAT
ACB COOL
BK
BK
L2
CONTACTOR COIL
W
HEAT SPEED
CONTACTOR COIL
COOL SPEED
Y
BK
BK W
VENTER MOTOR
LED
DSI CONTROL
SW1
FAN OFF DELAY
TIME
90
120
160
180
OFF
OFF
ON
ON
ON
OFF
OFF
ON
1
2
S W 1
IND
BK OR BL
NEUTRAL
BK OR BR
(SEE NOTES)
LED
OKFLAME
GY
NEUTRAL
LIMIT
CONTROL
R
R
R
P1-8
P1-3
BK OR BL
P1-2
P1-4
BL
BK
L1NEUTRAL
L1
SEC
ATO OR ATC
3.0 AMP
TEST
FUSE
FLAME
ROLLOUT SWITCH
ACB HEAT
ACB COOL
W
L1
L2
W
L2
COM
1
O
BR
FLAME
ELECTRODE
FLAME
GROUND
P1-7
P1-9
PRESSURE SWITCH
Y
Y
P1-6
P1-5
W
3
SPARK GAP
SPARK
TRANSFORMER
BL
BK
BR
TRANSFORMER
40 VA
BR
BL
BK
R
BL
DOOR
SWITCH
BKBKBK
DSI BOARD
REPLACEMENT
Option AG2
Option AG1
BELT DRIVE
DIRECT DRIVE
NEUTRAL
L1
W W
L2
BK
CAUA
WD #275047
R R
GREEN LED
FAST FLASH
1 FLASH
2 FLASH
3 FLASH
4 FLASH
STEADY OFF
LED FLASH CODES
NORMAL OPERATION CALL FOR HEAT
IN LOCKOUT FROM FAILED IGNITIONS OR FLAME
LOSSES
P1-8 TO P1-3 JUMPER OPEN CIRCUIT
PRESSURE SWITCH IS CLOSED BEFORE VENTER IS
ENERGIZED
INTERNAL CONTROL FAULT OR NO POWER
YELLOW LED
FLAME SENSEDSTEADY ON
SLOW FLASH WEAK FLAME
UNDESIRED FLAME (VALVE OPEN & NO CALL FOR
HEAT)
FAST FLASH
PRESSURE SWITCH DOES NOT CLOSE WITHIN
30 SECONDS
OF VENTER ENERGIZED
NORMAL OPERATION NO CALL FOR HEATSTEADY ON
NOTICE
BEFORE REPLACING CIRCUIT BOARD:
Check Fuse on Circuit Board
Check 24 VAC Supply
Check LED Flash Codes
Replacing circuit board will not correct
prob lems that are external to the board.
203058 Rev. 1
1) Call for Heat - The heating/cooling system
controller calls for heat. The ignition system cir-
cuit board checks to see that the limit switch is
closed and the pressure switch is open. If the
limit switch is open, the circuit board responds
as dened in the “Abnormal Heat Cycle, Limit
Switch Operation”. If the pressure switch is
closed, the circuit board will do four ashes
on the green LED and wait indenitely for the
pressure switch to open. If the pressure switch
is open, the circuit board proceeds to prepurge.
2) Prepurge - The circuit board energizes the
venter motor and waits for the pressure switch
to close. If the pressure switch does not close
within 30 seconds of the venter motor ener-
gizing, the circuit board will do two ashes on
the green LED. The circuit board will leave the
venter motor energized indenitely as long
as the call for heat remains and the pressure
switch is open.
When the pressure switch is proven closed,
the circuit board begins the prepurge time. If
ame is present any time while in prepurge,
the prepurge time is restarted. If ame is pres-
ent long enough to cause lockout, the circuit
board responds as dened in “Fault Modes,
Undesired Flame”.
The ignition system circuit board runs the ven-
ter motor for a 20 second prepurge time, then
proceeds to the ignition trial period.
3) Ignition Trial Period - The ignition system
circuit board energizes the spark and main gas
valve. The venter remains energized. If ame
is sensed during the rst 16 seconds, the spark
Normal Heat Cycle
Operating Sequence
Operating and
Service Information
for Replacement
DSI Controller
Form CP-CAUA-IGN CNTRL, Mfg #178435R6, Page 3
Abnormal Heat Cycle
Functions
Interrupted Call for Heat - If the system con-
troller call for heat is removed before the ame
is recognized, the circuit board will run the
venter motor for the post purge period and de-
energize all outputs.
If the call for heat is removed after successful
ignition, the circuit board will de-energize the
gas valve and run the venter motor through
post purge.
Ignition Retry - If ame is not established on
the rst trial for ignition period, the ignition sys-
tem circuit board de-energizes the gas valve,
and the venter motor remains energized for an
inter-purge period of 10 seconds. The spark
and gas valve are then re-energized, and the
circuit board initiates another trial for ignition.
If ame is not established on the second trial
for ignition, the circuit board de-energizes the
gas valve and venter motor remains energized.
The spark and gas valve are re-energized and
the circuit board initiates another trial for igni-
tion.
If ame is not established on the third trial for
ignition period, the circuit board de-energizes
the gas valve, and the venter motor remains
energized for an inter-purge period of 10 sec-
onds. The circuit board then re-energizes the
gas valve and spark and initiates another trial
for ignition.
If ame is not established on the fourth trial
for ignition (initial try plus 3 re-tries), the circuit
board de-energizes the gas valve and goes
into lockout. The circuit board goes to one
ash on the green LED to indicate ignition fail-
ure lockout.
Limit Switch Operation - The limit switch is
ignored unless a call for heat is present (W
energized). If the limit switch is open and a call
for heat is present, the control de-energizes
the gas valve, runs the blower motor on heat
speed, and runs the induced draft (venter)
motor. The control will be in soft lockout and
ashing fault code “3”, before returning to nor-
mal operation.
When the limit switch re-closes or the call for
heat is lost, the control runs the induced draft
motor through post purge and runs the blower
through the selected fan off delay.
Pressure Switch - If the pressure switch
opens before the trial for ignition period, the
venter motor will run through the pressure
switch recognition delay (2 seconds), the gas
valve will be de-energized, and the venter
motor will run through the postpurge time. The
ignition system circuit board will re-start the
heat cycle at the pressure switch proving state
if the call for heat still exists.
Pressure switch opening for less than 2 sec-
onds during the trial for ignition period shall
not interrupt the heat cycle. (Gas valve will de-
energize while the pressure switch is open.)
If the pressure switch opens after a success-
ful ignition, the circuit board will de-energize
the gas valve. If ame is lost before the end
of the 2 second pressure switch recognition
delay, the circuit board will respond to the loss
of ame. If the pressure switch remains open
for 2 seconds and the ame remains, the cir-
cuit board de-energizes the gas valve and the
venter motor runs through postpurge.
Power interruptions of less than 80mS shall
not cause the circuit board to change operat-
ing states. Power interruptions greater than
80mS may cause the circuit board to interrupt
the current operating cycle and re-start.
is de-energized. If ame has not been sensed during the rst 16
seconds, the control de-energizes the spark output and keeps
the gas valve energized for an additional one second ame prov-
ing period. If ame is not present after the ame proving period,
the control de-energizes the gas valve and proceeds with ignition
re-tries as specied in “Abnormal Heat Cycle, Ignition Retry”. If
ame is present, the circuit board proceeds to steady heat.
4) Steady Heat - Circuit board inputs are continuously monitored
to ensure limit and pressure switches are closed, ame is estab-
lished (sensor on both burner sections), and the system con-
troller call for heat remains. When the call for heat is removed,
the ignition system circuit board de-energizes the gas valve and
begins postpurge timing.
5) Post Purge - The venter motor output remains on for a 45
second postpurge period after the system controller is satised.
Undesired Flame - If ame is sensed longer
than 20 seconds while the gas valve is de-
energized, the circuit board shall energize the
venter motor. When ame is no longer sensed,
the venter motor will run through postpurge.
The circuit board will do a soft lockout, but
will still respond to open limit and ame. The
FLAME (yellow) LED shall ash rapidly when
lockout is due to undesired ame.
Gas Valve Relay Fault - If the circuit board
senses the gas valve as energized for more
than one second when the circuit board is not
attempting to energize the gas valve, or the
gas valve is sensed as not energized when
it is supposed to be energized, then the cir-
cuit board will lockout with the green LED off.
The control assumes either the contacts of the
relay driving the gas valve have welded shut,
or the sensing circuit has failed. The venter
motor is forced off to open the pressure switch
to stop gas ow unless ame is present.
If the gas valve was sensed as closed when
it should be open, and has not de-energized
after the venter motor was shutoff for 15 sec-
onds, then the venter motor is re-energized to
vent the unburned gas.
Soft Lockout - The circuit board shall not initi-
ate a call for heat while in lockout. The circuit
board will still respond to an open limit and
undesired ame. Lockout shall auto matically
reset after one hour. Lockout may be manually
reset by removing power from the circuit board
for more than one second or removing the call
for heat for more than one and less than 20
seconds.
Ignition System Fault
Modes
Form CP-CAUA-IGN CNTRL, Mfg #178435 R6, Page 4
IMPORTANT: When using a multimeter to troubleshoot the 24 volt circuit, place the meter’s test leads into the 5 or 9 pin connectors
located on the ignition control. Do not remove connectors or terminals from the electrical components. Doing so can result in
misinterpreted readings due to the ignition control board’s fault mode monitoring circuits.
Trial for Ignition - Call for Heat
Is there a
spark across gap at
ignitor?
Does gas
ignite?
Is there minimum
flame current at the
flame sensor?
Is there
minimum flame current
at the control
module?
Replace control
module.
Check connections to flame
sensor and/or moisture in the
burner assembly.
Is the flame
sensor corroded?
Clean flame
sensor.
Is the sensor
located in flame
correctly?
Replace flame
sesnsor.
Reposition
flame sensor.
Is gas
flowing?
Is the ignitor
position correct in the
gas flow?
Check gas pressure
and supply voltage.
If either are low,
correct and repeat
startup.
Reposition
spark ignitor.
Is there
24VAC at the gas
valve?
Is there 24VAC
from gas valve output on
control module to
chassis?
Check wiring and
connections to
gas valve.
Replace
ignition
control
module.
Replace gas
valve.
Is there
spark voltage at
control?
Check high
voltage wire
continuity.
Is there 24V P1-2
to power control?
Replace
control
module.
Check wiring
and/or 24VAC
transformer output.
YES NO
YES NO
YES NO
YES
NO
YES
NO
YES
NO
YES NO
YES
NO
NO
YES
YES NO
YES
NO
YES
NO
DSI Integrated Control Module (Circuit
Board) Trial Troubleshooting Flowchart
The integrated circuit board monitors the operation of the heater and includes two LED signal
lights that indicate normal operation and various abnormal conditions. If the heater fails to oper-
ate properly, check this signal to determine the cause and/or to eliminate certain causes. Open
the door panel to view the LED lights.
Lights
Check the Ignition Control Module - The integrated ignition control module monitors the oper-
ation of the heater and includes LED signals that indicate normal operation and various abnor-
mal conditions. If the heater fails to operate properly, check this signal to determine the cause
and/or to eliminate certain causes.
Operating and
Service Information
(cont’d)
The direct spark integrated circuit board is polarity sensitive. If burners cycle on and off, try
switching the power supply leads. The supply connection made to "L1" on the circuit board must
be the "hot" wire.
The only replaceable component of the control module is the 3 amp Type ATC or ATO fuse. Do
not attempt to repair the DSI integrated control module.
Troubleshooting
and Service
Hard Lockout - If the circuit board detects a
fault on the board, the status LED will be de-
energized, and the circuit board will lockout as
long as the fault remains. A hard lockout will
automatically reset if the hardware fault clears.
Power Interruption - During a momentary
power interruption or at voltage levels below
the minimum operating voltage (line voltage
or low voltage) the ignition system will self-
recover without lockout when voltage returns
to the operating range.
Power interruptions of less than 80mS shall
not cause the circuit board to change operat-
ing states. Power interruptions greater than
80mS may cause the circuit board to interrupt
the current operating cycle and re-start.
Ignition System Fault
Modes (cont’d)
Control Status - Green LED Codes
Steady ON .......Normal Operation, No call for heat
Fast Flash ........ Normal Operation, Call for heat
1 Flash ............. System Lockout, Failed to detect or sustain ame
2 Flashes .........Pressure Switch Did Not Close within 30 Seconds of Venter Motor
3 Flashes .........High Limit Switch Open
4 Flashes .........Pressure switch is closed before venter motor is energized
Steady OFF .....Blown Fuse, No Power, or Defective Board
Flame Status - Yellow LED Codes
Steady ON .......Flame is sensed
Slow Flash .......Weak ame (current
below 1.0 microamps
±50%)
Fast Flash ........ Undesired Flame (valve
open and no call for heat)
Specications & illustrations subject to change without notice and without incurring obligations.
© Nortek Global HVAC LLC 2015. All rights reserved.
All trademarks are the property of their respective owners.
Printed in the U.S.A. (04/15)
Form CP-CAUA-CNTRL (04-15)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Reznor CAUA Operating instructions

Type
Operating instructions

Reznor CAUA is a reliable and efficient ignition control system designed to enhance the performance of your heating equipment. With its advanced features and compatibility with various heating systems, it offers a range of benefits for users seeking optimal heating solutions.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI