GrandAire JT4BF User manual

Category
Heat pumps
Type
User manual
Outdoor Heat Pump
Two Stage R-410A Split System
User’s Manual / Installation Instructions
Please read this information thoroughly and become familiar with the capabilities
and use of your appliance before attempting to operate or maintain this unit.
Keep this literature where you have easy access to it in the future. If a problem
occurs, check the instructions and follow recommendations given. If these
suggestions don’t eliminate your problem, call your NORDYNE Servicing
Contractor (Service PRO).
These instructions are primarily intended to assist qualifi ed individuals
experienced in the proper installation of this appliance. Some local codes
require licensed installation/service personnel for this type of equipment.
Please read all instructions carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
Premium Model Shown
2
3
Safety Information ........................................6
Pressures Within the System .....................6
Labels, Tags, and Precautions ....................6
Brazing Operations .....................................6
General Information ..................................... 7
Outdoor Unit ...............................................7
Liquid and Suction Lines ............................7
Field Connections for Electrical Power
Supply.........................................................7
Site Preparation ............................................7
Unpacking the Equipment ..........................7
Inspect for Damage ....................................7
Preferred Location of the Outdoor Unit ....... 7
Facility Prerequisites ..................................7
Minimum Circuit Ampacity ..........................7
Maximum Fuse / Circuit Breaker Size ........ 7
Installing the Indoor Unit ............................. 7
Installing the Outdoor Unit .......................... 7
Slab Mount ................................................7
Cantilever Mount ........................................7
Roof Mount ................................................8
Connecting Refrigerant Tubing Between
the Indoor and Outdoor Unit ....................... 8
General Information ....................................8
Filter Drier Installation ................................8
Optional Equipment ....................................8
Electrical Connections .................................8
Pre - Electrical Checklist.............................8
Wiring Diagram / Schematic .......................8
Line Voltage ................................................8
Outdoor Unit Connections ..........................9
Control Circuit Wiring ..................................9
Thermostat Connections ............................9
Grounding ................................................... 9
Low Pressure Switch ..................................9
High Pressure Switch .................................9
Comfort Alert
TM
Diagnostics Module .........10
24VAC Power Wiring ............................10
Thermostat Demand Wiring .................10
Interpreting the Diagnostic LED’s .........10
LED Description ...................................10
Two - Speed Outdoor Fan Motor ..............11
Optional Equipment ..................................11
Transformer Upgrade Kit ......................11
Startup & Adjustments...............................11
Pre - Start Checklist .................................11
Thermostat ...............................................11
Outdoor Unit .............................................11
Functional Checkouts ................................11
Cooling .....................................................11
Heating .....................................................11
Indoor Blower ...........................................12
Short Cycle Protection ..............................12
Defrost Cycle Control ...............................12
Defrost Test Procedure .............................12
Anti Short Cycle Timer Test ......................13
Heating Mode .......................................13
Cooling Mode .......................................13
Optional Equipment ..................................13
Adjustment of Refrigerant Charge ............13
Charging R-410A Unit in AC Mode ..........13
Charging R-410A Unit in Heat Mode .......13
Cooling Charging Charts ...........................14
Heating Charging Chart .............................16
Troubleshooting ..........................................17
USER INFORMATION
INSTALLER INFORMATION
Safety Information ........................................4
About the Heat Pump ...................................4
Operating Instructions .................................4
Cooling Operation .......................................4
Heating Operation ......................................4
Emergency Heat .........................................4
Defrost Operation .......................................4
Operating the Heat Pump for Automatic
Cooling and Heating ...................................5
Oper. the Indoor Blower Continuously ........5
Shutting the Heat Pump Off........................5
System Maintenance ....................................5
Regular Cleaning ........................................5
Before You Call a Technician ......................5
Troubleshooting ............................................5
Warranty Information ...................................5
4
ABOUT THE HEAT PUMP
Your heat pump is a unique, all weather comfort-
control appliance that will heat and cool your
home year round and provide energy saving
comfort. It’s an unknown fact that heat is always
in the air, even when the outside temperature is
below freezing. The heat pump uses this basic
law of physics to provide energy saving heat
during the winter months. For example, If the
outdoor temperature is 47° F (8° C), your heat
pump can deliver approximately 3.5 units of
heat energy per each unit of electrical energy
used, as compared to a maximum of only 1
unit of heat energy produced with conventional
heating systems.
In colder temperatures, the heat pump performs
like an air conditioner run in reverse. Available
heat energy outside the home is absorbed by
the refrigerant and exhausted inside the home.
This effi cient process means you only pay for
“moving” the heat from the outdoors to the indoor
area. You do not pay to generate the heat, as
with more traditional furnace designs.
During summer, the heat pump reverses the fl ow
of the heat-absorbing refrigerant to become an
energy-effi cient, central air conditioner. Excess
heat energy inside the home is absorbed by the
refrigerant and exhausted outside the home.
OPERATING INSTRUCTIONS
Please refer to the thermostat manufacturer’s
User manual for detailed programming
instructions.
Cooling Operation Only
1. Set the thermostat’s system mode to COOL
or AUTO and change the fan mode to AUTO.
See Figure 1
2. Set the temperature selector to the desired
temperature level. The outdoor fan,
compressor, and blower motor will all cycle
on and off to maintain the indoor temperature
at the desired cooling level.
NOTE: If the temperature level is re-adjusted, or
the system mode is reset, the fan and compressor
in the outdoor unit may not start immediately. A
protective timer circuit holds the compressor
and the outdoor fan off for approximately three
minutes following a previous operation or the
interruption of the main electrical power.
Heating Operation Only
1. Set the thermostat’s system mode to HEAT
or AUTO and change the fan mode to AUTO.
See Figure 1.
2. Set the temperature selector to the desired
temperature level. The compressor, outdoor
fan, and blower motor will cycle on and off to
maintain the indoor temperature at the desired
heating level.
NOTE: If the temperature level is re-adjusted, or
the system mode is reset, the fan and compressor
in the outdoor unit may not start immediately. A
protective timer circuit holds the compressor
and the outdoor fan off for approximately three
minutes following a previous operation or the
interruption of the main electrical power.
Emergency Heat
Some thermostats may include a system mode
called EM HT or AUX HT, etc. This is a back-
up heating mode that should only be used if a
problem is suspected. With the mode set to EM
HT, etc., the compressor and outdoor fan will
be locked off and supplemental heat (electric
resistance heating) will be used as a source of
heat. Sustained use of electric resistance heat in
place of the heat pump will result in an increase
in electric utility costs.
Defrost Operation
During cold weather heating operation, the
outdoor unit will develop a coating of snow
and ice on the heat transfer coil. This is normal
USER INFORMATION
SAFETY INFORMATION
IMPORTANT: Safety markings are used
frequently throughout this manual to designate
a degree or level of seriousness and should not
be ignored. WARNING indicates a potentially
hazardous situation that if not avoided, could
result in personal injury or death. CAUTION
indicates a potentially hazardous situation that
if not avoided, may result in minor or moderate
injury or property damage.
Figure 1. Digital Thermostat
Fan
Mode
Temperature
Selector
System
Mode
5
SYSTEM MAINTENANCE
CAUTION:
Shut off all electrical power to the unit
before performing any maintenance or
service on the system. Failure to comply
may result in personal injury or death.
Proper maintenance is most important to achieve
the best performance from the appliance and
should be performed by a qualifi ed service
technician at least once a year. Follow the
maintenance schedule and the instructions below
for years of safe, trouble free operation.
Regular Cleaning
Clean or replace the indoor air fi lter at the
start of each heating and cooling season,
and when an accumulation of dust and dirt
is visible on the air fi lter.
Remove any leaves and grass clippings from
the coil in the outdoor unit, being careful not
to damage the aluminum fi ns.
Check for obstructions, such as twigs, sticks,
etc.
TROUBLESHOOTING
If the unit fails to operate, check the following:
The thermostat is properly set. See Cooling
Operation for air conditioning or Heating
Operation for furnace or air handler.
The unit disconnect fuses are in good condition
and the electrical power to the unit is turned
on.
Operating the Heat Pump for Automatic
Cooling and Heating
1. Set the thermostat system switch to AUTO
and the thermostat fan switch to AUTO. See
Figure 1.
Note: Thermostats will vary. Some models will
not include the AUTO mode, and others will have
the AUTO in place of the HEAT and COOL, and
some will include all three.
2. Set the thermostat temperature to the desired
heating and cooling temperature level(s). The
outdoor unit and the indoor blower will then
cycle on and off in either the heating or cooling
mode of operation as required to automatically
maintain the indoor temperature within the
desired limits.
Operating the Indoor Blower Continuously
The continuous indoor blower operation is
typically used to circulate the indoor air to
equalize a temperature unbalance due to a sun
load, cooking, or fi replace operation.
Set the thermostat fan mode to ON (Figure 1). The
indoor blower starts immediately, and will run
continually until the fan mode is reset to AUTO.
The continuous indoor blower operation can be
obtained with the thermostat system mode set
in any position, including OFF.
Shutting the Heat Pump Off
Change the thermostat’s system mode to OFF
and the fan mode to AUTO. See Figure 1.
NOTE: The system will not operate, regardless
of the temperature selector setting.
and the unit will defrost itself. This unit features
Adaptive Demand Defrost that monitors ambient
and coil temperatures to regulate the defrost
function accordingly.
At the beginning of the defrost cycle, both the
outdoor condenser fan and compressor will
turn off. After approximately 30 seconds, the
compressor will turn on and begin to heat the
outdoor coil causing the ice and snow to melt.
NOTE: While the ice and snow is melting, some
steam may rise from the outdoor unit as the warm
coil causes the melting frost to evaporate. When
defrost is completed, the outdoor fan motor will
start, and the compressor will turn off again. In
approximately 30 seconds the compressor will
start up again and continue normal operation.
WARRANTY INFORMATION
A warranty certificate with full details is
included with the heat pump. Carefully review
these responsibilities with your dealer or
service company. The manufacturer will not be
responsible for any costs found necessary to
correct problems due to improper setup, improper
installation, adjustments, improper operating
procedure on the part of the user, etc. Some
specifi c examples of service calls which are not
included in the limited warranty are:
Correcting wiring problems in the electrical
circuit supplying the heat pump.
Resetting circuit breakers or other switches.
Adjusting or calibrating of thermostat.
USER INFORMATION
6
INSTALLER INFORMATION
SAFETY INFORMATION
IMPORTANT: Safety markings are used
frequently throughout this manual to designate
a degree or level of seriousness and should not
be ignored. WARNING indicates a potentially
hazardous situation that if not avoided, could
result in personal injury or death. CAUTION
indicates a potentially hazardous situation that
if not avoided, may result in minor or moderate
injury or property damage.
Read the following instructions completely
before performing the installation. Unqualifi ed
individuals should not attempt to interpret
these instructions or install this equipment.
The installer should comply with all local
codes and regulations which govern the
installation of this type of equipment. Local
codes and regulations take precedence over
any recommendations contained in these
instructions. Consult local building codes and the
National Electrical Code (ANSI CI) for special
installation requirements.
WARNING:
These units are fully charged with
R-410A refrigerant and ready for
installation. When a system is installed
according to these instructions, no
refrigerant charging is required.
If repairs make it necessary for
evacuation and charging, it should
only be attempted by qualifi ed, trained
personnel thoroughly familiar with this
equipment. Some local codes require
licensed installation service personnel
to service this type of equipment.
Under no circumstances should the
homeowner attempt to install and/
or service this equipment. Failure to
comply with this warning could result
in equipment damage, personal injury,
or death.
CAUTION:
This unit uses refrigerant R-410A. DO
NOT under any circumstances use any
other refrigerant in this unit. Use of
another refrigerant will damage the unit.
Pressures within the System
This equipment contains liquid and gaseous
refrigerant under high pressure. Installation or
servicing should only be performed by qualifi ed
trained personnel thoroughly familiar with this
type equipment and related system components.
Under no circumstances should the Homeowner
attempt to install and/or service the equipment.
Labels, Tags, and Precautions
When working with this equipment, follow all
precautions in the literature, on tags, and on
labels provided with the equipment. Read and
thoroughly understand the instructions provided
with the equipment prior to performing the
installation and operational checkout of the
equipment.
Brazing Operations
Installation of equipment may require brazing
operations. Safety codes must be complied
with. Safety equipment (safety glasses, work
gloves, fi re extinguisher, etc.) must be used
when performing brazing operations.
WARNING:
Verify all electrical power to the unit is
off prior to installing or servicing the
equipment. Failure to shut off power
may cause personal injury or death.
7
SITE PREPARATION
Unpacking the Equipment
Remove the shipping carton and User’s Manual
from the equipment. Take care not to damage the
tubing connections when removing the carton.
Inspect for Damage
Inspect the equipment for damage prior to
installing the equipment at the job site. Verify
coil fi ns are straight. If necessary, comb fi ns to
remove fl attened or bent fi ns.
Preferred Location of the Outdoor Unit
Survey the job site to determine the best
location for mounting the outdoor unit. Overhead
obstructions, poorly ventilated areas, and areas
subject to accumulation of debris should be
avoided. The outdoor unit should be installed
no closer than 18 inches from the outside walls
of the facility and in an area free from overhead
obstructions to ensure unrestricted airflow
through the outdoor unit.
Facility Prerequisites
Electrical power supplied to the unit must be
adequate for proper operation of the equipment.
The system must be wired and provided with
circuit protection in accordance with local
building codes.
Minimum Circuit Ampacity
Electrical wiring to the equipment must be
compatible and in compliance with the minimum
circuit ampacity listed on the outdoor unit data
label.
Maximum Fuse / Circuit Breaker Size
Circuit protection for the outdoor unit must be
compatible with the maximum fuse/circuit breaker
size listed on the outdoor unit data label.
INSTALLING THE INDOOR UNIT
The indoor unit (air handler, furnace, etc.) should
be installed prior to the routing of refrigerant
piping. Consult the Installation Instructions of
the indoor unit for installation details.
INSTALLING THE OUTDOOR UNIT
Slab Mount
The site selected for a slab mount installation
requires a stable foundation and not subject to
erosion. The slab should be level and anchored
(if necessary) prior to installation on the slab.
Cantilever Mount
The cantilever mount should be designed with
adequate safety factor to support the weight of the
equipment, and for loads subjected to the mount
during operation. Installed equipment should
be adequately secured to the cantilever mount
and levelled prior to operation of the equipment.
GENERAL INFORMATION
Split System Heat Pump units are designed for
use with a wide variety of fossil fuel furnaces,
electric furnaces, air handlers, and evaporator
coil combinations equipped with variable speed
blowers.
This unit has been designed and tested for
capacity and effi ciency in accordance with A.R.I.
Standards. This unit will provide many years of
safe and dependable comfort, providing it is
properly installed and maintained. With regular
maintenance, this unit will operate satisfactorily
year after year. Abuse, improper use, and/or
improper maintenance can shorten the life of the
appliance and create unsafe hazards.
To achieve optimum performance and minimize
equipment failure, it is recommended that periodic
maintenance be performed on this unit. The
ability to properly perform maintenance on this
equipment requires certain mechanical skills
and tools.
Please consult your dealer for maintenance
information and availability of maintenance
contracts. Please read all instructions before
installing the unit.
Outdoor Unit
Each outdoor unit is shipped with a refrigerant
charge adequate to operate the outdoor section
with an indoor matching coil or air handler. These
units include the proper amount of refrigerant for
an additional 15 ft. of refrigerant lines the same
size as the valve fi ttings.
NOTE: DO NOT USE ANY PORTION OF THE
CHARGE FOR PURGING OR LEAK TESTING.
Matching coils and air handlers may be shipped
with a small holding charge to pressurize them to
keep out contaminants. To release the pressure,
read the indoor section installation instructions
carefully.
Liquid and Suction Lines
Refrigerant grade copper tubing should be used
when installing the system. Refrigerant suction
line tubing should be fully insulated.
Field Connections for Electrical Power Supply
All wiring must comply with current provisions
of the “National Electrical Code” (ANSI/NFPA
70) and with applicable local codes having
jurisdiction. The minimum size of electrical
conductors and circuit protection must be in
compliance with information listed on the outdoor
unit data label.
8
The maximum recommended interconnecting
refrigerant line length is 75 feet, and the vertical
elevation difference between the indoor and
outdoor sections should not exceed 20 feet.
If precise forming of refrigerant lines
is required, a copper tubing bender is
recommended. Avoid sharp bends and contact
of the refrigerant lines with metal surfaces.
Filter Drier Installation
A fi lter dryer is provided with the unit and must
be installed in the liquid line of the system. If the
installation replaces a system with a fi lter dryer
already present in the liquid line, the fi lter dryer
must be replaced with the one supplied with the
unit. The fi lter dryer must be installed in strict
accordance with the manufacturer’s installation
instructions.
Optional Equipment
Optional equipment such as liquid line solenoid
valves, twinning kit, low ambient, etc., should
be installed in strict accordance with the
manufacturer’s installation instructions.
Roof Mount
WARNING:
To avoid the risk of property damage,
personal injury, or death, it is the
installer’s responsibility to ensure that
whatever means are used to move or lift
the unit are safe and adequate:
Keep the unit in an upright position at
all times.
The method of mounting should be designed
so as not to overload roof structures or transmit
noise to the interior of the structure. Refrigerant
and electrical lines should be routed through
suitably waterproofed openings to prevent water
leaking into the structure.
CONNECTING REFRIGERANT TUBING
BETWEEN THE INDOOR & OUTDOOR UNIT
CAUTION:
This system uses R-410A refrigerant
with POE oil. When servicing, cover or
seal openings to minimize the exposure
of the refrigerant system to air to prevent
accumulation of moisture and other
contaminants.
General Information
After outdoor and indoor unit placement has been
determined, route refrigerant tubing between the
equipment in accordance with sound installation
practices.
When connecting refrigerant linesets together,
it is recommended that dry nitrogen be fl owing
through the joints during brazing. This will
prevent internal oxidation and scaling from
occurring.
Refrigerant tubing should be routed in a
manner that minimizes the length of tubing
and the number of bends in the tubing.
Refrigerant tubing should be supported in
a manner that the tubing will not vibrate or
abrade during system operation.
Tubing should be kept clean of foreign debris
during installation.
Every effort should be made by the installer
to ensure that the fi eld installed refrigerant
containing components of the system have
been installed in accordance with these
instructions and sound installation practices to
insure reliable system operation and longevity.
ELECTRICAL CONNECTIONS
WARNING:
Shut off all electrical power to the unit
before performing any maintenance or
service on the system. Failure to comply
may result in personal injury or death.
Pre-Electrical Checklist
Verify that the voltage, frequency and phase
of the supply source are the same as those
specifi ed on the unit rating plate.
Verify that the service provided by the utility is
suffi cient to handle the additional load imposed
by this equipment.
For minimum circuit ampacity and maximum
overcurrent protection, see unit rating plate.
Wiring Diagram / Schematic
A wiring diagram/schematic is located on the
inside cover of the electrical box of the outdoor
unit. The installer should become familiar with
the wiring diagram/schematic before making
any electrical connections to the outdoor unit.
Line Voltage
Electrical power wiring must comply with the
current provisions of the NEC (ANSI/NFPA
70) and with applicable local codes having
jurisdiction.
Provide power supply for the unit in accordance
with the unit wiring diagram, and the unit rating
plate.
9
COPPER WIRE SIZE — AWG
(1% Voltage Drop)
Supply Wire Length-Feet
Supply Circuit
Ampacity
200 150 100 50
6 8 10 14 15
46812 20
46810 25
44610 30
3468 35
3468 40
2346 45
2346 50
2346 55
1234 60
Wire Size based on N.E.C. for 60° type copper conductors.
Table 1. Copper Wire Size
Connect the line-voltage leads to the
terminals on the contactor inside the control
compartment.
Use only copper wire for the line voltage power
supply to this unit (Table 1). Use proper code
agency listed conduit and a conduit connector
for connecting the supply wires to the unit.
Use of rain tight conduit is recommended.
See the unit wiring label for proper high and low
voltage wiring. Make all electrical connections
in accordance with all applicable codes and
ordinances.
Use a separate branch electrical circuit for this
unit. A means of electrical disconnect must be
located within sight of and readily accessible
to the unit. This switch shall be capable of
electrically de-energizing the outdoor unit.
Overcurrent protection must be provided at the
branch circuit distribution panel and sized as
shown on the unit rating label and according
to applicable local codes.
Outdoor Unit Connections
The outdoor unit requires both power and control
circuit electrical connections. Refer to the unit
wiring diagram / schematic for identifi cation and
location of outdoor unit fi eld wiring interfaces.
Control Circuit Wiring
The outdoor unit is designed to operate from a
24 VAC Class II control circuit. The control circuit
wiring must comply with the current provisions
of the NEC (ANSI/NFPA 70) and with applicable
local codes having jurisdiction.
Thermostat Connections
Thermostat connections should be made in
accordance with the instructions supplied with
the thermostat, and with the instructions supplied
with the indoor equipment. A typical residential
installation with a heat pump thermostat and air
handler are shown in Figure 2.
Figure 2. Typical 2 - Stage Heat Pump w/
Optional Outdoor Thermostat and Variable
Speed Air Handler
G R W2 C E O Y1
Thermostat
OD
Stat
O
Y1
R
C
Air Handler
Heat Pum
p
OD
Section
W
2
E
W2
W1
O
Y/Y2
G
R
C
Y2
Y2
W1
W3
Y1
NOTE: Jumper
W1 & W2 together
for shorter staging
time.
Grounding
CAUTION:
The unit must have an uninterrupted or
unbroken electrical ground to minimize
personal injury if an electrical fault
should occur. This ground may consist of
electrical wire or approved conduit when
installed in accordance with national or
local codes.
Low-Pressure Switch
A low-pressure switch is factory installed and
located internally on the suction line of the
outdoor unit. The switch is designed to protect the
compressor from a loss of charge by interrupting
the thermostat inputs to the unit.
If the suction pressure falls below 5 psig, the
switch will open and de-energize the outdoor
unit. The switch will close again when the suction
pressure increases above 20 psig. NOTE: When
the switch opens and then closes, there is a 3
minute short cycling delay before the outdoor
unit will energize. Under normal conditions the
switch is closed.
High-Pressure Switch
A high-pressure switch is factory installed and
located internally on the compressor discharge
line of the outdoor unit. If the discharge pressure
rises above 650 psig, the switch will open and
de-energize the outdoor unit. The switch will close
10
again after the discharge pressure decreases to
460 psig. NOTE: When the switch opens and
then closes, there will be a 3 minute short cycling
delay before the outdoor unit will energize. Under
normal conditions the switch is closed.
Comfort Alert
TM
Diagnostics Module
The Comfort Alert
TM
Diagnostics Module is a
breakthrough innovation for troubleshooting
heat pump and air conditioning system failures.
The module installs easily in the electrical box of
the outdoor unit near the compressor contactor.
By monitoring and analyzing data from the
Copeland scroll compressor and the thermostat
demand, the module can accurately detect the
cause of electrical and system related failures
without any sensors. A fl ashing LED indicator
communicates the ALERT code and a diagnostic
key is also imprinted on the side of the module
to quickly direct the technician to the root cause
of a problem. See Figure 3.
NOTE: This module does not provide safety
protection! The Comfort Alert
TM
Diagnostics
Module is a monitoring device and cannot control
or shut down other devices.
24 VAC Power Wiring
The Comfort Alert
TM
module requires a constant
nominal 24 VAC power supply. The module cannot
be powered by the C terminal on a defrost board
or other control board without experiencing
nuisance alerts. NOTE: The wiring to the module’s
R & C terminals must be routed directly from the
indoor unit or thermostat.
If the constant 24 VAC (R wire) is not present in
the outdoor unit, use one of the spare wires in the
thermostat cable to bring power to the module.
Connect the other end of the spare wire to R at
the indoor unit or thermostat.
Thermostat Demand Wiring
The Comfort Alert
TM
module requires a
thermostat demand signal to operate properly.
The thermostat demand signal input (labeled Y
on the module), should always be connected to
the compressor contactor coil. NOTE: When the
coil is energized, the demand signal input is 24
VAC. When the coil is not energized, the demand
signal input should be less than 0.5 VAC.
NOTES:
Factory installed modules have different
thermostat demand signal wiring. Always
follow manufacturer wiring instructions when
replacing the module.
After the thermostat demand signal is
connected, verify that 24 VAC across Y & C
when demand is present.
Interpreting the Diagnostic LED’s
When an abnormal system condition occurs, the
Comfort Alert
TM
module displays the appropriate
ALERT and/or TRIP LED will fl ash a number of
times consecutively, pause and then repeat the
process. To identify a Flash Code number, count
the number of consecutive fl ashes.
Each time the module powers up, the last ALERT
Flash Code that occurred prior to shut down
is displayed for one minute. The module will
continue to display the LED until the condition
returns to normal or if 24 VAC power is removed
from the module.
LED Description
• POWER LED (Green): indicates voltage is
present at the power connection of the module.
ALERT LED (Yellow): communicates an
abnormal system condition through a unique
ash code. NOTE: The ALERT LED will fl ash
consecutively, pause and then repeat the
process. The number of consecutive fl ashes,
referred to as the Flash Code, correlates to
a particular abnormal condition. Detailed
descriptions of these ALERT Flash Codes
are listed in Table 4 (page 14).
TRIP LED (Red): indicates a demand signal
is received from the thermostat, but current
to the compressor is not detected by the
module. The TRIP LED typically indicates
if the compressor protector is open or the
compressor has no power.
The scroll compressor’s R (run), C (common),
and S (start) wires are routed through the holes in
the Comfort Alert
TM
module marked R, C, and S.
NOTE: The common wire does not need to be
routed through the module for it to operate.
Figure 3. Comfort Alert
TM
Diagnostics
Module
POWER LED
(Green)
TRIP LED
(Red)
ALERT LED
(Yellow)
Diagnostic
s
Key
11
FUNCTIONAL CHECKOUTS
CAUTION:
These units have a crankcase heater
factory installed. Wait 24 hours prior to
performing a function checkout to allow
for heating of the compressor crankcase.
Failure to comply may result in damage
and could cause premature failure of
the system.
Cooling
Gradually lower the thermostat temperature
setpoint below the actual room temperature
and observe that the outdoor unit and indoor
blower energize. Feel the air being circulated
by the indoor blower and verify that it is cooler
than ambient temperature. Listen for any unusual
noises. If unusual sounds occur, determine the
source of the noise and correct as necessary.
Heating
If heating equipment (furnace, air handler) is
provided with the system, lower the thermostat
setpoint temperature to the lowest temperature
setting and change the thermostat’s function
mode to HEAT. The outdoor unit should stop
running and the indoor blower will shut off after the
preprogrammed delay. Increase the thermostat’s
setpoint temperature to the maximum setting.
Verify the heating equipment and the indoor
blower energize after a short period of time. Feel
the air being circulated by the indoor blower and
verify that it is warmer than ambient temperature.
Listen for any unusual noises. If unusual sounds
occur, determine the source of the noise and
correct as necessary.
NOTE: Other sources for heating (electric
furnace, fossil fuel furnace, air handler with
electric heat options, etc.) that interface with
the heat pump should be functionally checked to
Outdoor Fan Motor
If unit utilizes a 2-speed condenser fan motor,
this motor will operate on low speed when in
low cooling, and on high speed when in high
cooling. A relay within the control area switches
the fan motor from low to high speed using the
call for high cooling as the trigger. Other models
that utilize BLDC fi xed torque variable speed fan
motors will not require a relay.
Optional Equipment
Optional equipment requiring connection to
the power or control circuits must be wired in
strict accordance with current provisions of the
NEC (ANSI/NFPA 70), with applicable local
codes having jurisdiction, and the installation
instructions provided with the equipment.
Optional Equipment (low ambient control,
hard start kits, etc.) should be installed in strict
accordance with the manufacturer’s installation
instructions
Transformer Upgrade Kit
If this 2-stage heat pump is installed in conjunction
with a gas furnace and fossil fuel kit, the furnace
transformer MUST be upgraded to one with a 60
VA rating or using the transformer upgrade kit
(904077). To upgrade the transformer:
Remove the existing transformer and install
the new 60 VA transformer.
Remove the 3 amp fuse on the furnace control
board and install the 5 amp fuse provided.
NOTE: The new transformer may be larger
than the existing transformer that is mounted in
the furnace. If this happens, mount the 60 VA
transformer using one of the mounting holes in
the furnace panel. On the other side either drill
a 0.149 hole in the panel and use the existing
fastener, or use a self-drilling fastener to secure
the other side of the transformer.
STARTUP AND ADJUSTMENTS
Pre-Start Checklist
The following check list should be observed prior
to starting the unit.
Is the unit level?
Is the wiring correct according to the wiring
diagram and electrical codes?
Inspect wiring for evidence of open, shorted,
and/or improperly wired circuits.
Are all the wiring connections tight? Check
the condenser fan to make sure it turns freely.
Is the overcurrent protection properly sized?
Is the thermostat wired correctly? Is it installed
in a proper location?
Verify air fi lters are clean and in place prior
to operating the equipment.
Verify the outdoor coil and top of the unit are
free from obstructions and debris, and all
equipment access/control panels are in place.
Thermostat
Set the thermostat’s system mode to OFF, the
fan mode to AUTO, and adjust the temperature
setpoint to its highest setting.
Outdoor Unit
Prior to applying electrical power to the outdoor
unit, verify that the unit has been properly and
securely grounded, and that power supply
connections have been made at both the facility
power interface and outdoor unit.
Verify the outdoor coil and top of the unit are free
from obstructions and debris, and all equipment
access/control panels are in place.
12
verify system operation and compatibility with the
heat pump. Refer to the installation instructions
for this equipment and perform a functional
checkout in accordance with the manufacturer’s
instructions.
Indoor Blower
1. Turn the fan mode to ON. Verify that the
indoor blower is operating and that airfl ow is
not restricted.
2. Set the fan mode back to AUTO. Blower will
operate at a decreased speed on continuous
fan.
Short Cycle Protection
1. With the system operating in COOLING mode,
record the setpoint temperature setting of the
thermostat.
2. Gradually raise the setpoint temperature
until the outdoor unit and indoor blower de-
energize.
3. Immediately lower the setpoint temperature of
the thermostat to its original setting and verify
that the indoor blower is energized and that
the outdoor unit remains de-energized.
4. After approximately 3 minutes, verify that the
outdoor unit energizes and the temperature
of the air supplied to the facility is cooler than
ambient temperature.
Defrost Cycle Control
The defrost cycle is controlled by an Adaptive
Demand Defrost algorithm that monitors coil
temperature and ambient temperature. Other
features of the of the demand defrost board
include:
4 Field selectable defrost termination
temperatures (50° F - 80° F coil temperature).
Field selectable compressor delay feature.
High pressure and low pressure switches.
Sensing of second stage compressor demand.
Test/speed up capability.
Anti short cycle timer (3 minutes) for
compressor protection.
On board diagnostics with fl ashing LED for
quicker troubleshooting. See Table 2.
Diagnostic Description LED Status
Control Fault (No Power) Off
Normal Operation On
ASCD Delay Active
(with compressor demand)
1 Flash
Low Pressure Switch Lockout 2 Flashes
High Pressure Switch Lockout 3 Flashes
Ambient Sensor Fault 4 Flashes
Coil Sensor Fault 5 Flashes
Table 2. Control Diagnostic
Control is uncalibrated when power is applied.
Calibration occurs after a defrost cycle. The
control initiates this sacrifi cial defrost after 34
minutes of accumulated compressor run time in
heating with coil temperature below 35° F. The
defrost cycle terminates if coil sensor reaches
selected termination temperature or after 14
minutes defrost.
Defrost function is disabled if coil temperature
is above 35° F. If Ambient sensor is detected as
open or shorted, demand defrost will not operate
and control will revert to time/temperature defrost
operation. If the outdoor coil sensor is detected
as open or shorted, the control will not perform
demand or time/temperature defrost operation.
NOTE: When the defrost cycle initiates, there
will be a 30 second compressor delay going into
and out of the defrost cycle. This delay may be
removed by removing P6 connector on the board.
This 2-stage unit will defrost in second stage
regardless of the stage called for by the
thermostat.
NOTE: All units are shipped from the factory with
the default termination temperature set at 70° F.
Defrost Test Procedure
1. Terminals R - C must have 18-30VAC present
between them in order for defrost sequences
to be initiated.
2 With heat mode thermostat demand (Y
connected to R), short and hold the TEST
pins together. This will energize reversing
valve to initiate a forced defrost. NOTE: This
will bypass the ASCD and allow the high stage
compressor to come on immediately (if the
REMOVE FOR NO DELAY jumper at P6 is
removed). If the REMOVE FOR NO DELAY
jumper at P6 is installed, the compressor will
energize immediately following a 30-second
delay.
3. Remove the short on the TEST pins.
If the Coil temperature is above the Terminate
Temperature selection setting, the defrost
cycle will be terminated (reversing valve will
de-energized).
If the coil temperature is below the Terminate
Temperature election setting, the defrost
cycle will continue for 14 minutes or until the
coil temperature rises above the Terminate
Temperature selection setting. NOTE: Short
the TEST pins for 1 second or more to force
the control out of defrost and back to heating
mode (reversing valve de-energized).
Compressor will turn on immediately (if
the REMOVE FOR NO DELAY jumper is
removed).
13
If the REMOVE FOR NO DELAY jumper
is installed, the compressor will energize
immediately following a 30-second delay.
Note: If the Y2 thermostat input is energized
(2 - stage system), the second stage will turn on.
If the above steps will not initiate a defrost, replace
the defrost board.
Anti Short Cycle Timer Test
The 3-minute time delay feature can be bypassed
by shorting the TEST pins together.
Heating Mode
When the TEST pins are shorted together for
more than 1-second, the control will switch
between defrost mode and heating mode (as
described in the Defrost Test Procedure section).
Cooling Mode
When the TEST pins are shorted together for
more than 1-second, the Anti Short Cycle Timer
will be bypassed.
Optional Equipment
A functional checkout should be performed
in accordance with the checkout procedures
supplied with the equipment.
Table 3. Split System
Heat Pump Charge
Tonnage
System Charge
R-410A oz.
2 Ton 185
3 Ton 272
4 Ton 272
5 Ton 272
ADJUSTMENT OF REFRIGERANT
CHARGE:
CAUTION:
Split system equipment contains
liquid and gaseous refrigerant under
pressure. Adjustment of refrigerant
charge should only be attempted by
qualifi ed, trained personnel thoroughly
familiar with the equipment. Under no
circumstances should the homeowner
attempt to install and/or service this
equipment. Failure to comply with this
warning could result in equipment
damage, personal injury, or death.
NOTES:
The unit must be charged while both fi rst and
second stages are operating.
To achieve rated capacity and effi ciency the
compressor must be exposed to refrigerant
for at least 24 hours prior to running and then
must be run for a minimum of 12 hours.
The following Refrigerant Charging Charts are
applicable to listed assemblies of equipment
and at listed airfl ows for the indoor coil.
Assemblies of indoor coils and outdoor units
not listed are not recommended.
Charging an R-410A Unit in AC Mode at
Outdoor Temperatures Above 65F.
1. With the system operating at steady-state,
measure the liquid refrigerant pressure in
psig at the service valve.
2. Measure the liquid refrigerant temperature in
Fahrenheit at the service valve.
3. For the temperature measured, determine the
required liquid refrigerant pressure from the
appropriate charging charts in Figures 4 - 7
(pages 14 & 15).
4. If the pressure measured in step 1 is greater
than the required liquid refrigerant pressure
determined in step 4, then there is too much
charge in the system. Remove refrigerant and
repeat steps 1 through 3 until the system is
correctly charged.
5. If the pressure measured in step 1 is less
than the required liquid refrigerant pressure
determined in step 4, then there is too little
charge in the system. Add refrigerant and
repeat steps 1 through 3 until the system is
correctly charged.
Charging an R-410A Unit in Heating Mode.
1. Evacuate the refrigerant system.
2. Weigh in the proper charge per Table 3, using
the Heating Charging Chart (Figure 8, page
16) as a guide. Unit charge MUST be verifi ed
in cooling season.
3. Verify the unit is operating properly as outlined
in the functional checkout (heating section) on
page 11.
14
Cooling Charging Charts
Figure 4. Charging Chart for 2 Ton Units
250
275
300
325
350
375
400
425
450
475
70 75 80 85 90 95 100 105 110 115 120 125
Liquid Temperature (° F)
Liquid Pressure (psig)
Remove refrigerant when above curve
Add refrigerant when below curve
Figure 5. Charging Chart for 3 Ton Units
Liquid Temperature (° F)
Liquid Pressure (psig)
250
275
300
325
350
375
400
425
450
475
500
70 75 80 85 90 95 100 105 110 115 120 125
Remove refrigerant when above curve
Add refrigerant when below curve
15
Cooling Charging Charts (continued)
Figure 6. Charging Chart for 4 Ton Units
Li
q
uid Tem
p
erature
(
° F
)
Liquid Pressure (psig)
250
275
300
325
350
375
400
425
450
475
500
70 75 80 85 90 95 100 105 110 115 120 12
5
Remove refrigerant when above curve
Add refrigerant when below curve
Figure 7. Charging Chart for 5 Ton Units
Liquid Temperature (° F)
Liquid Pressure (psig)
250
275
300
325
350
375
400
425
450
475
500
70 75 80 85 90 95 100 105 110 115 120 125
Remove refrigerant when above curve
Add refrigerant when below curve
16
Heating Charging Chart
Figure 8. Heating Charging Chart
Liquid Temperature (° F)
Liquid Pressure (psig)
200
225
250
275
300
325
350
375
400
50 55 60 65 70 75 80 85 90
Remove refrigerant when above curve
Add refrigerant when below curve
17
Status
LED
Status LED
Description
Status LED Troubleshooting Information
Green
“POWER”
Module has
power
Supply voltage is present at module terminals
Red “TRIP”
Thermostat
demand signal
Y is present, but
compressor is not
running
Compressor protector is open
Check for high head pressure
Check compressor supply voltage
Outdoor unit power disconnect is open
Compressor circuit breaker or fuse(s) is open
Broken wire or connector is not making contact
Low pressure switch open if present in system
Compressor contactor has failed open
Yellow “ALERT”
Flash Code 1
Long Run Time
Compressor is
running extremely
long run cycles
Low refrigerant charge
Evaporator blower is not running
Check blower relay coil and contacts
Check blower motor capacitor
Check blower motor for failure or blockage
Check evaporator blower wiring and connectors
Check indoor blower control board
Check thermostat wiring for open circuit
Evaporator coil is frozen
Check for low suction pressure
Check for excessively low thermostat setting
Check evaporator airfl ow (coil blockages or return airfi lter)
Check ductwork or registers for blockage
Faulty metering device
Check TXV bulb installation (size, location and contact)
Check if TXV/fi xed orifi ce is stuck closed or defective
Condenser coil is dirty
Liquid line restriction (fi lter drier blocked if present in system)
Thermostat is malfunctioning
Solenoid plug not connected
Y2 not wired at Comfort Alert
Check thermostat sub-base or wiring for short circuit
Check thermostat installation (location, level)
Comfort Alert failure
Yellow “ALERT”
Flash Code 2
System Pressure
Tr ip
High head pressure
Check high pressure switch if present in system
Check if system is overcharged with refrigerant
Check for non-condensable in system
Discharge or
suction
Condenser coil poor air circulation (dirty, blocked, damaged)
pressure out of
limits
Condenser fan is not running
Check fan capacitor
Check fan wiring and connectors
Check fan motor for failure or blockage
compressor
overloaded
Return air duct has substantial leakage
If low pressure switch present in system, check Flash Code
1 information
TROUBLESHOOTING
Table 4. LED Diagnostics
18
Status LED
Status LED
Description
Status LED Troubleshooting Information
Yellow “ALERT”
Flash Code 3
Short Cycling
/ Compressor
is running only
briefl y
Thermostat demand signal is intermittent
Low line voltage (contact utility if voltage at disconnect is low)
Excessive liquid refrigerant in compressor
Compressor bearings are seized
Yellow “ALERT”
Flash Code 4
Locked Rotor
Run capacitor has failed
Low line voltage (contact utitlity if voltage at disconnect is
low)
Check wiring connections
Excessive liquid refrigerant in compressor
Compressor bearings are seized
Measure compressor oil level
Yellow “ALERT”
Flash Code 5
Open Circuit
Outdoor unit power disconnect is open
Compressor circuit breaker or fuse(s) is open
Compressor contactor has failed open
Check compressor contactor wiring and connectors
Check for compressor contactor failure (burned, pitted
or open)
Check wiring and connectors between supply and
compressor
Check for low pilot voltage at compressor contactor coil
High pressure switch is open and requires manual reset
Open circuit in compressor supply wiring or connections
Unusually long compressor protector reset time due to extreme
ambient temperature
Compressor windings are damaged
Check compressor motor winding resistance
Yellow “ALERT”
Flash Code 6
Open Start Circuit
Current only in
run circuit
Run capacitor has failed
Open circuit in compressor start wiring or connections
Check wiring and connectors between supply and the
compressor S terminal
Compressor start winding is damaged
Check compressor motor winding resistance
Yellow “ALERT”
Flash Code 7
Open run circuit
Current only in
start circuit
Open circuit in compressor run wiring or connections
Check wiring and connectors between supply and the
compressor R terminal
Compressor run winding is damaged
Check compressor motor winding resistance
Yellow “ALERT”
Flash Code 8
Welded Contactor
Compressor
always runs
Compressor contactor has failed closed
Thermostat demand signal not connected to module
Yellow “ALERT”
Flash Code 9
Low Voltage
Control circuit
< 17VAC
Control circuit transformer is overloaded
Low line voltage (contact utility if voltage at disconnect is low)
Check wiring connections
* Flash code number corresponds to a number of LED fl ashes, followed by a pause and then
repeated. Trip and alert LED’s fl ashing at same time means control circuit voltage is too low for
operation.
Table 4. LED Diagnostics - Continued
TROUBLESHOOTING - CONTINUED
19
Table 5. Module Wiring Troubleshooting
Miswired Module Indication Recommended Troubleshooting Action
Green LED is not on, module
does not power up
• Determine if both R & C module terminals are connected.
Verify voltage is present at module’s R & C terminals.
Green LED intermittent,
module powers up only when
compressor runs
• Determine if R & Y terminals are wired in reverse.
Verify modules R and C terminals have a constant source.
Trip LED is on, but system and
compressor check OK
• Verify Y terminal is connected to 24VAC at contactor coil.
Verify voltage at contactor coil falls below 0.5VAC when
off.
Verify 24VAC is present across Y & C when thermostat
demand signal is present. If not, R & C are reversed wired.
TRIP LED and ALERT LED
ashing together
• Verify R and C terminals are supplied with 19 - 28VAC.
ALERT Flash CODE 3 displayed
incorrectly (Compressor short
cycling)
• Verify Y terminal is connected to 24VAC at contactor coil.
Verify voltage at contactor coil falls below 0.5VAC when
off.
ALERT Flash Code 5, 6, or 7
displayed incorrectly (Open
Circuit, Open Start Circuit or
Open Run Circuit)
Verify the compressor run and start wires are routed
through the module’s current sensing holes.
• Verify the Y terminal is connected to 24VAC at contactor
coil.
Verify voltage at contactor coil falls below 0.5VAC when
off.
ALERT Flash Code 6 (Open
Start Circuit) displayed for
Code 7 (Open Run Circuit) or
vice-versa
Verify the compressor run and start wires are routed
through the correct module sensing holes.
ALERT Flash Code 8 displayed
incorrectly (Welded Contactor)
Determine if module’s Y terminal is connected.
• Verify Y terminal is connected to 24VAC at contactor coil.
Verify 24VAC is present across Y & C when thermostat
demand signal is present. If not, R and C are reversed
wired.
Verify voltage at contactor coil falls below 0.5VAC when
off.
Review Thermostat Demand Wiring (page 10) for Y & C
wiring.
TROUBLESHOOTING - CONTINUED
INSTALLER: PLEASE LEAVE THESE
INSTALLATION INSTRUCTIONS WITH
THE HOMEOWNER.
708868A(Replaces 7088680)
Specifi cations and illustrations subject to change
without notice t incurring obligations.
Printed in U.S.A. (10/09)
¢708868b¤
708868AO’Fallon, MO
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

GrandAire JT4BF User manual

Category
Heat pumps
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI