Potter NGP-1000D-M3 Nitrogen Generator Owner's manual

Category
Fire protection
Type
Owner's manual
NGP-1000D-M3
Nitrogen Generator
8820026 - REV A 7/15 PAGE 1 OF 2
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
Description
The Potter Nitrogen Generator, NGP-1000D-M3, is specically
designed to provide on-site, high purity nitrogen for use in re
protection sprinkler systems. When used as a supervisory gas in re
sprinkler systems, nitrogen slows corrosion, improves the life of your
system, and lowers maintenance costs. Potter Nitrogen Generators are
fully assembled packages ready to be connected to a new or existing
re sprinkler system. These turn-key systems include all air ltration
equipment, an air compressor, nitrogen membrane, as well as tanks
required to keep the generator operating at peak efciency. Potter
Nitrogen Generator Systems provide a low cost, reliable, and efcient
method of producing a minimum of 98% nitrogen at the point of usage.
The NGP-1000D-M3 utilizes nitrogen membrane technology for
gas separation. Nitrogen membranes are highly effective and a cost
conscious way of producing on-site nitrogen. Acting as a lter, the
smaller oxygen and water vapor molecules can pass through the
membrane quickly. The larger nitrogen molecules are less likely
to diffuse through the separator tubes; therefore, they continue
downstream to the separator outlet, through the air maintenance device
and into the re protection system. As the system lls with nitrogen,
the remaining oxygen molecules in the re protection system are
exhausted by using the Potter IntelliPurge® Nitrogen Purge Valve. The
Potter IntelliPurge® Nitrogen Purge Valve will periodically monitor
the re protection system to ensure high purity nitrogen is consistent
throughout the sprinkler system.
Installation
The Potter NGP-1000D-M3 should be installed in a dry, clean, and
well-ventilated room with ambient temperatures above 50°F at all times.
Allow access to the front for service and place the unit in a location
that is conveniently located near re sprinkler system connections and
a drain.
The Potter Nitrogen Generator should always be installed in an
adequately ventilated room. Nitrogen is nontoxic and largely inert.
Rapid release of nitrogen gas into an enclosed space displaces the
oxygen and can cause an asphyxiation hazard. Inhalation of nitrogen
in excessive concentrations can result in unconsciousness without any
warning symptoms.
For detailed installation and operation instructions please refer to the
Potter Nitrogen Generator Manual #5401548.
Technical Specications
Size (HxWxD) 62” x 44” x 33”
Weight 550 lbs
Power Supply
Available in 208V (11.6A), 230V (11A),
single phase and 208V (9.2A), 230V (9.2A),
460V (4.6A) three phase
Fire Sprinkler System
Connection ½” Female NPT
Mounting Holes (4) ½” Ø
Max operating Pressure 100 PSI
Temperature Range 50°F (10°C) to 110°F (43°C)
Air Purity
ISO Class 1.4.1 or better: Free of water 38°F
(3°C) Dew Point, compressor oil (0.008 PPM
or .01 mg/m3), hydrocarbons, and particles
(<0.01 μm microns)
Features
Complete skid mounted unit – easy plug and play installation
Integrated 2 HP oil-less air compressor needed for NFPA 13 required
30 minutes ll for 1000 gallon system at 40 PSI
Handles up to 5000 gallons of total sprinkler system capacity (based
on NFPA 13 allowable leak rates for a new sprinkler system)
Premium nitrogen membrane
UL 508A listed industrial control panel
Requires only one power connection
Built-in Programmable Logic Controller for leak detection and air
bypass alarm systems
Form C dry contacts for Building Management System (BMS)
notication
30 gallon air tank and 30 gallon nitrogen tank
Includes all lters, relief valves, automatic drains and gauges
firealarmresources.com
8820026 - REV A 7/15 PAGE 2 OF 2
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
NGP-1000D-M3
Nitrogen Generator
Fig 1
Dimensions
Model Description Stock No.
NGP-1000D-M3-2A SINGLE PHASE 208V 1119524
NGP-1000D-M3-3A SINGLE PHASE 230V 1119526
NGP 1000D-M3-2B THREE PHASE 208V 1119527
NGP 1000D-M3-3B THREE PHASE 230V 1119528
NGP 1000D-M3-4B THREE PHASE 460V 1119529
Ordering Information
Model Description Stock No.
NGP-MK Maintenance Kit M2-M5 1119785
INS-PV Potter IntelliPurge® Nitrogen Purge
Valve 1119478
NGP-SPV Potter Purge Valve 1119784
NGP-AMD-1 Potter Air Maintenance Device 1119787
61 5/8"
13 5/8"
11 5/8"
18"
4"
2 PLCS
DRAIN
CONNECTION
1/4" OD TUBING,
PUSH TO CONNECT
32 3/8"
12 7/8"
30"
28"
16"
16"
9 1/8"
48"
AFTERCOOLER
30 GALLON
AIR TANK
30 GALLON
NITROGEN TANK
1/2" CONDUIT
CONNECTION
2 PLCS
DRAIN
CONNECTION
1/4" OD TUBING,
PUSH TO CONNECT
SEPARATOR
43 3/4"
30"
PS-1 PRESSURE SWITCH
WITH UNLOADER
1/2" MOUNTING HOLES
4 PLCS
OIL LESS AIR
COMPRESSOR
AIR TANK
PRESSURE
GAUGE
CHECK VALVE
POWER ON LIGHT
NITROGEN SOLENOID
LIGHT
ALARM LIGHT
ALARM HORN
MEMBRANE PRESSURE
GAUGE
NITROGEN TANK
PRESSURE GAUGE
1/2" FNPT NITROGEN
OUTLET CONNECTION
2 PLCS
REVISIONS
REV.
ENG. CHG. NO.
DESCRIPTION DATE
BY
CHK.
A
--
RELEASED
7-15
NWD
MJA
D
C
B
A
A
B
C
D
CAD GENERATED DRAWING,
DO NOT MANUALLY UPDATE
SCALE
SIZE
DWG. NO.
D
SHEET
1 OF 1
DATE
APPROVALS
DRAWN
CHECKED
DO NOT SCALE DRAWING
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
E
F
E
F
POTTER ELECTRIC SIGNAL CO.
--
NWD
MJA
7-22-2015
7-22-2015
1:6
DATA CONTAINED HEREIN SHALL NOT BE USED, DUPLICATED OR DISCLOSED IN WHOLE
OR PART OUTSIDE POTTER ELECTRIC, INC. WITHOUT WRITTEN PERMISSION OF SAME.
PROPRIETARY DATA
OUTLINE
NGP-1000D-M2
VENDOR CERTIFIES ALL PARTS SUPPLIED FROM THIS DRAWING HAVE BEEN PRODUCED
TO ITS SPECIFICATIONS AND VENDOR WILL BE RESPONSIBLE FOR ANY REWORK COST
WHERE SPECIFICATIONS HAVE NOT BEEN MET.
VENDOR CERTIFICATION
TITLE
61 5/8"
13 5/8"
11 5/8"
18"
4"
2 PLCS
DRAIN
CONNECTION
1/4" OD TUBING,
PUSH TO CONNECT
32 3/8"
12 7/8"
30"
28"
16"
16"
9 1/8"
48"
AFTERCOOLER
30 GALLON
AIR TANK
30 GALLON
NITROGEN TANK
1/2" CONDUIT
CONNECTION
2 PLCS
DRAIN
CONNECTION
1/4" OD TUBING,
PUSH TO CONNECT
SEPARATOR
43 3/4"
30"
PS-1 PRESSURE SWITCH
WITH UNLOADER
1/2" MOUNTING HOLES
4 PLCS
OIL LESS AIR
COMPRESSOR
AIR TANK
PRESSURE
GAUGE
CHECK VALVE
POWER ON LIGHT
NITROGEN SOLENOID
LIGHT
ALARM LIGHT
ALARM HORN
MEMBRANE PRESSURE
GAUGE
NITROGEN TANK
PRESSURE GAUGE
1/2" FNPT NITROGEN
OUTLET CONNECTION
2 PLCS
REVISIONS
REV.
ENG. CHG. NO.
DESCRIPTION DATE
BY
CHK.
A
--
RELEASED
7-15
NWD
MJA
D
C
B
A
A
B
C
D
CAD GENERATED DRAWING,
DO NOT MANUALLY UPDATE
SCALE
SIZE
DWG. NO.
D
SHEET
1 OF 1
DATE
APPROVALS
DRAWN
CHECKED
DO NOT SCALE DRAWING
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
E
F
E
F
POTTER ELECTRIC SIGNAL CO.
--
NWD
MJA
7-22-2015
7-22-2015
1:6
DATA CONTAINED HEREIN SHALL NOT BE USED, DUPLICATED OR DISCLOSED IN WHOLE
OR PART OUTSIDE POTTER ELECTRIC, INC. WITHOUT WRITTEN PERMISSION OF SAME.
PROPRIETARY DATA
OUTLINE
NGP-1000D-M2
VENDOR CERTIFIES ALL PARTS SUPPLIED FROM THIS DRAWING HAVE BEEN PRODUCED
TO ITS SPECIFICATIONS AND VENDOR WILL BE RESPONSIBLE FOR ANY REWORK COST
WHERE SPECIFICATIONS HAVE NOT BEEN MET.
VENDOR CERTIFICATION
TITLE
61 5/8"
13 5/8"
11 5/8"
18"
4"
2 PLCS
DRAIN
CONNECTION
1/4" OD TUBING,
PUSH TO CONNECT
32 3/8"
12 7/8"
30"
28"
16"
16"
9 1/8"
48"
AFTERCOOLER
30 GALLON
AIR TANK
30 GALLON
NITROGEN TANK
1/2" CONDUIT
CONNECTION
2 PLCS
DRAIN
CONNECTION
1/4" OD TUBING,
PUSH TO CONNECT
SEPARATOR
43 3/4"
30"
PS-1 PRESSURE SWITCH
WITH UNLOADER
1/2" MOUNTING HOLES
4 PLCS
OIL LESS AIR
COMPRESSOR
AIR TANK
PRESSURE
GAUGE
CHECK VALVE
POWER ON LIGHT
NITROGEN SOLENOID
LIGHT
ALARM LIGHT
ALARM HORN
MEMBRANE PRESSURE
GAUGE
NITROGEN TANK
PRESSURE GAUGE
1/2" FNPT NITROGEN
OUTLET CONNECTION
2 PLCS
REVISIONS
REV.
ENG. CHG. NO.
DESCRIPTION DATE
BY
CHK.
A
--
RELEASED
7-15
NWD
MJA
D
C
B
A
A
B
C
D
CAD GENERATED DRAWING,
DO NOT MANUALLY UPDATE
SCALE
SIZE
DWG. NO.
D
SHEET
1 OF 1
DATE
APPROVALS
DRAWN
CHECKED
DO NOT SCALE DRAWING
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
E
F
E
F
POTTER ELECTRIC SIGNAL CO.
--
NWD
MJA
7-22-2015
7-22-2015
1:6
DATA CONTAINED HEREIN SHALL NOT BE USED, DUPLICATED OR DISCLOSED IN WHOLE
OR PART OUTSIDE POTTER ELECTRIC, INC. WITHOUT WRITTEN PERMISSION OF SAME.
PROPRIETARY DATA
OUTLINE
NGP-1000D-M2
VENDOR CERTIFIES ALL PARTS SUPPLIED FROM THIS DRAWING HAVE BEEN PRODUCED
TO ITS SPECIFICATIONS AND VENDOR WILL BE RESPONSIBLE FOR ANY REWORK COST
WHERE SPECIFICATIONS HAVE NOT BEEN MET.
VENDOR CERTIFICATION
TITLE
61 5/8"
13 5/8"
11 5/8"
18"
4"
2 PLCS
DRAIN
CONNECTION
1/4" OD TUBING,
PUSH TO CONNECT
32 3/8"
12 7/8"
30"
28"
16"
16"
9 1/8"
48"
AFTERCOOLER
30 GALLON
AIR TANK
30 GALLON
NITROGEN TANK
1/2" CONDUIT
CONNECTION
2 PLCS
DRAIN
CONNECTION
1/4" OD TUBING,
PUSH TO CONNECT
SEPARATOR
43 3/4"
30"
PS-1 PRESSURE SWITCH
WITH UNLOADER
1/2" MOUNTING HOLES
4 PLCS
OIL LESS AIR
COMPRESSOR
AIR TANK
PRESSURE
GAUGE
CHECK VALVE
POWER ON LIGHT
NITROGEN SOLENOID
LIGHT
ALARM LIGHT
ALARM HORN
MEMBRANE PRESSURE
GAUGE
NITROGEN TANK
PRESSURE GAUGE
1/2" FNPT NITROGEN
OUTLET CONNECTION
2 PLCS
REVISIONS
REV.
ENG. CHG. NO.
DESCRIPTION
DATE
BY
CHK.
A
--
RELEASED
7-15
NWD
MJA
D
C
B
A
A
B
C
D
CAD GENERATED DRAWING,
DO NOT MANUALLY UPDATE
SCALE
SIZE
DWG. NO.
D
SHEET
1 OF 1
DATE
APPROVALS
DRAWN
CHECKED
DO NOT SCALE DRAWING
1
2
3
4
5
6
7
8
8
7
6
5
4
3
2
1
E
F
E
F
POTTER ELECTRIC SIGNAL CO.
--
NWD
MJA
7-22-2015
7-22-2015
1:6
DATA CONTAINED HEREIN SHALL NOT BE USED, DUPLICATED OR DISCLOSED IN WHOLE
OR PART OUTSIDE POTTER ELECTRIC, INC. WITHOUT WRITTEN PERMISSION OF SAME.
PROPRIETARY DATA
OUTLINE
NGP-1000D-M2
VENDOR CERTIFIES ALL PARTS SUPPLIED FROM THIS DRAWING HAVE BEEN PRODUCED
TO ITS SPECIFICATIONS AND VENDOR WILL BE RESPONSIBLE FOR ANY REWORK COST
WHERE SPECIFICATIONS HAVE NOT BEEN MET.
VENDOR CERTIFICATION
TITLE
firealarmresources.com
  • Page 1 1
  • Page 2 2

Potter NGP-1000D-M3 Nitrogen Generator Owner's manual

Category
Fire protection
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI