4. COOLING CAPACITY
115V
RS1211 / C1211 and CL1211
5
WM– 700703
TC: Total Cooling Capacity (BTU/H)
SHC: Sensible Heat Capacity (BTU/H)
kW: Compressor Input (kW)
Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB
Indoor unit entering air temperature 80°F DB/67°F WB
Rating Capacity: 11,500 BTU/H Air Flow Rate: 280 CFM
Evaporator Condenser
Ent. Temp. °F/(°C) Ambient Temp. °F/(°C)
WB DB
75 85 95 105 115
(23.9) (29.4) (35.0) (40.6) (46.1)
TC 11,390 10,870 10,350 9,760 8,970
kW 0.85 0.93 1.01 1.10 1.21
59 72 (22.2) SHC 8,140 7,870 7,600 7,310 6,920
(15.0) 76 (24.4) SHC 9,150 8,880 8,610 8,320 7,930
80 (26.7) SHC 10,210 9,940 9,670 9,380 8,970
84 (28.9) SHC 11,220 10,870 10,350 9,760 8,970
88 (31.1) SHC 11,390 10,870 10,350 9,760 8,970
TC 11,780 11,410 10,960 10,360 9,550
kW 0.86 0.94 1.03 1.12 1.23
63 72 (22.2) SHC 6,860 6,680 6,470 6,190 5,820
(17.2) 76 (24.4) SHC 7,870 7,690 7,480 7,200 6,830
80 (26.7) SHC 8,930 8,750 8,540 8,260 7,890
84 (28.9) SHC 9,940 9,760 9,550 9,270 8,900
88 (31.1) SHC 10,950 10,770 10,560 10,280 9,550
TC 12,100 11,900 *11,500 10,870 10,120
kW 0.87 0.95 1.04 1.13 1.26
67 72 (22.2) SHC 5,530 5,450 5,270 5,000 4,690
(19.4) 76 (24.4) SHC 6,550 6,460 6,290 6,020 5,700
80 (26.7) SHC 7,600 7,520 7,340 7,070 6,760
84 (28.9) SHC 8,620 8,530 8,360 8,090 7,770
88 (31.1) SHC 9,630 9,540 9,370 9,100 8,790
TC 12,480 12,270 11,960 11,420 10,750
kW 0.88 0.96 1.06 1.16 1.28
71 72 (22.2) SHC 4,170 4,090 3,970 3,760 3,510
(21.7) 76 (24.4) SHC 5,190 5,110 4,980 4,770 4,520
80 (26.7) SHC 6,240 6,160 6,040 5,830 5,580
84 (28.9) SHC 7,260 7,180 7,050 6,840 6,590
88 (31.1) SHC 8,270 8,190 8,070 7,860 7,600
TC 12,720 12,580 12,310 11,870 11,390
kW 0.89 0.98 1.07 1.19 1.32
75 76 (24.4) SHC 3,830 3,780 3,690 3,530 3,370
(23.9) 80 (26.7) SHC 4,890 4,840 4,740 4,590 4,420
84 (28.9) SHC 5,900 5,850 5,760 5,600 5,440
88 (31.1) SHC 6,910 6,870 6,770 6,620 6,450