SICK WT 9-2P/N-160/P460 Energetic Photoelectric Proximity Switch Product information

Type
Product information
WT 9-2
P/N160
P460
Energetic
Photoelectric
Proximity
Switch
Axis of the receiver optics
Axis of the sender optics
Mounting hole
Ø
3.2 mm
LED signal strength indicator
2 m connection cable or plug M 12, 4 pin
Scanning distance adjuster
Standard direction of the material to be scanned
Setting options
Connection type
Dimension illustration
1
2
3
4
12
22
40
20
3
3
1.5
1
3
2
3
18.5 10.5
11
4
5
7
Emitter LED IR
Scanning distance
adjustable
Switching frequency 500/s
2 m connection cable or plug
M 12, 4 pin
Outputs short-circuit
protected
Scanning distance
50 ... 1500 mm
Photoelectric proximity switch
5
T ECHNICAL I NFORMATION
L+
Q
Q
M
brn
wht
blu
blk
4 x 0.14 mm
2
WT 9-2P460
WT 9-2P160
WT 9-2N160
WT 9-2P160
WT 9-2N160
1
L+
Q
Q
4
2
3
M
brn
wht
blu
blk
4 pin, M 12
WT 9-2P460
6
7
4
6
Scanning distance, adjustable
1)
50 ... 1500 mm
Supply voltage V
S
2)
10 ... 30 V DC
Ripple
3)
5 V
PP
Current consumption
4)
30 mA
Light source
5)
LED, infrared
Light spot diameter 600 mm at a distance of 1500 mm
Switching outputs PNP, Q und Q
NPN, Q und Q
Signal voltage HIGH V
S
– 2.9 V
V
S
Signal voltage LOW
6)
Approx. 0 V
< 2.9 V
Output current I
A
max. 100 mA
Response time
7)
1000 µs
Switching frequency max.
8)
500/s
Connection technology Connection cable, 2 m
Plug M 12, 4 pin
VDE protection class
9)
Protection type IP 67
Protection circuits
10)
A, B, C
Ambient temperature
11)
Operation –40 ... +60 °C
Storage –40 ... +75 °C
Weight with cable 2 m Approx. 80 g
with plug Approx. 20 g
WT 9-2P160/N160/P460 Photoelectric Proximity Switch, Energetic
Technical data WT 9-2
8 009 318/19-02-01 • HJS/SM • Printed in Germany (02.01) • We reserve the right to make changes
P160 P460 N160
1)
Object with 90% reflectance
(referred to standard white DIN 5033)
2)
Limit values
3)
Must be within V
S
tolerances
4)
Without load
5)
Average service life at
room temperature 100,000 h
at T
U
= +25 °C
6)
At T
U
= +25 °C and 100 mA
output current
7)
With resistive load
8)
With light/dark ratio 1:1
9)
Withstand voltage 50 V DC
10)
A = supply connections reverse
polarity protected
B = outputs short-circuit protected
C = interference suppression
11)
Do not distort cable below 0 °C
Ordering informationScanning distance
Type
WT 9-2P160
WT 9-2P460
WT 9-2 N160
Order no.
1 019 097
1 019 098
1 019 342
(mm) 300 600
1000
10
100
1
900
1200 1500
Function reserve
Operating
distance
Limiting scanning
distance
WT 9-2 energetic
6%/90%
18%/90%
90%/90%
3
2
1
0(mm) 300 600 900 1200 1500
3
1
2
Operating distance
50 600
50 800
50 1500
Scanning range on white, 90 % reflectance
Scanning range on gray, 18 % reflectance
Scanning range on black, 6 % reflectance
1
2
3
Great Britain
Erwin Sick Ltd.
Waldkirch House
39 Hedley Road, St. Albans
Hertfordshire AL 1 5BN
+44 17 27-83 11 21
Fax +44 17 27-85 67 67
USA
SICK, Inc.
6900 West 110th Street
Bloomington, MN 55438
+1 (952) 9 41-67 80
Fax +1 (952) 9 41-92 87
WATS: 1-800-325-7425
Australia
Erwin Sick Optic-Electronic
Pty. Ltd. Head Office, P.O. Box 214
899 Heidelberg Road
Ivanhoe, Vic. 3079, Australia
+61 39 49 74 10 0
(0 08) 33 48 02 - toll free
Fax +61 39 49 71 18 7
  • Page 1 1
  • Page 2 2

SICK WT 9-2P/N-160/P460 Energetic Photoelectric Proximity Switch Product information

Type
Product information

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI