Dwyer Series 160F User manual

Type
User manual
S
eries 160F Pitot Tubes are designed to meet the need of the environmental
t
esting field for an inexpensive, yet accurate and reliable way to measure the flow
of air or gas streams.
For maximum accuracy of ±2%, as in laboratory applications, care is required and
the following recommendations should be followed.
1. Duct diameter should be 4˝ or larger.
2. Point total pressure opening upstream facing flow, and static
pressure opening downstream pointing in the direction of the flow.
The faces of both openings must be perpendicular to the airflow.
3. Make an accurate traverse per drawings; calculate the velocities at
each point and average them.
4. Take readings in a smooth, straight duct section a minimum of 10-15
duct diameters in length upstream and 5 diameters downstream
from the pitot tube.
5. Provide an egg-crate type straightener upstream from the pitot tube
for best performance.
TAKING AIR VELOCITY READINGS
To measure air velocity with a Series 160F Pitot Tube, make a 0.35˝ opening in
duct. Connect tubing from total pressure port or port facing flow to high pressure
side of manometer, and from static pressure port or port facing perpendicular to
flow to the low pressure side. If reading is negative, reverse connections.
Make a series of readings traversing the duct in horizontal and vertical planes.
Using velocity pressures recorded at each location, calculate velocities and
average them for final velocity value. See Figure 1 for more detail.
Series 160F Straight Pitot Tubes
Installation and Operating Instructions
Bulletin AQ-160F
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: [email protected]
CALCULATING VELOCITY
Air Velocity = 1096.2 (C
p
) P
v
D
where:
P
v
= Sensed pressure difference (velocity pressure) in inches of
water column
D = Air density in lbs./ft.
3
(dry air = .075)
C
p
= Pitot tube coefficient: 0.81
Air Density = 1.325 X P
B
T
P
B
= Barometric pressure in inches of mercury
T = Absolute Temperature (Indicated Temperature in °F plus 460)
Flow in cubic feet per minute equals duct cross sectional area in square feet x air
velocity in feet per minute.
With dry air at 29.9 inches of mercury, air velocity can be read directly from
temperature correction charts on reverse.
SPECIFICATIONS
Wetted Material: 304 SS.
Accuracy: ±2% FS, 0 to 9000 FPM (45 M/s).
K-Factor: 0.81.
T
emperature Limit: 1500°F (815°C).
Process Connections: 1/4˝ OD.
Weight: 4.3 oz (122 g).
A
5/8
[16.00]
2
-35/64
[
64.54]
1/4
[6.30]
5/16
[7.92]
Ø
1/8
[Ø3.05]
1/4
[6.35]
[4] Ø 3/64 [Ø1.09] PRESSURE HOLES
[2 ON EACH SIDE]
M
odel
1
60F
1
60F-24
160F-36
160F-48
160F-60
D
imension “A” in (mm)
1
9-9/32 (489.56)
2
5-9/32 (642.14)
37-9/32 (946.94)
49-9/32 (1251.74)
61-9/32 (1556.54)
Figure 1
Traverse on Round and Square Duct Areas
©Copyright 2015 Dwyer Instruments, Inc. Printed in U.S.A. 3/15 FR# 443939-00 Rev. 2
GAGE READING WITH 160F PITOT TUBE (VELOCITY PRESSURE) IN INCHES OF WATER
GAGE READING WITH 160F PITOT TUBE (VELOCITY PRESSURE) IN INCHES OF WATER
AIR VELOCITY IN FEET PER MINUTE
AIR VELOCITY IN FEET PER MINUTE
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: [email protected]
  • Page 1 1
  • Page 2 2

Dwyer Series 160F User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI