Eaton Series NRX Installation Instructions Manual

Type
Installation Instructions Manual

Eaton Series NRX circuit breakers offer reliable protection for your electrical systems. With a range of configurations, including rear connect, front connect, and hybrid options, these breakers can be tailored to your specific needs. The universal bus adapters and copper adapter extensions provide flexibility for various connection options. The arc hood and shroud enhance safety by directing arc gas discharge and insulating the bus adapters. These breakers are suitable for both surface and fixed mounting, making them a versatile choice for your electrical installations.

Eaton Series NRX circuit breakers offer reliable protection for your electrical systems. With a range of configurations, including rear connect, front connect, and hybrid options, these breakers can be tailored to your specific needs. The universal bus adapters and copper adapter extensions provide flexibility for various connection options. The arc hood and shroud enhance safety by directing arc gas discharge and insulating the bus adapters. These breakers are suitable for both surface and fixed mounting, making them a versatile choice for your electrical installations.

Instruction Leaet IL01301015E
Effective November 2016
Supersedes July 2015
Contents
Description Page
General information ........................2
Rear connected configurations ...............3
Front connected configurations ...............5
Hybrid connected configurations .............10
Installation instructions for Series NRX
Type NF frame fixed breaker rear connect,
front connect, and hybrid configurations
Instructions apply to:
Series NRXT, Type NF frame (rear connect),
ULT 489, UL 1066, IEC
Series NRX, Type NF frame (front connect)
UL 489, IEC
Series NRX, Type NF frame (hybrid),
UL 489, IEC
2
Instruction Leaet IL01301015E
Effective November 2016
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
EATON www.eaton.com
m WARNING
(1) ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE PERMITTED TO
WORK ON THE EQUIPMENT.
(2) ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF A
CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK LOCATION.
(3) DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) OUT TO
THE DISCONNECT POSITION.
(4) ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF POSITION
AND MECHANISM SPRINGS DISCHARGED.
FAILURE TO FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN
THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH, BODILY INJURY, OR
PROPERTY DAMAGE.
m WARNING
THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS
HAVE TO BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES:
– DISCONNECTING
ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED
VERIFY ISOLATION FROM THE SUPPLY
EARTHING AND SHORT-CIRCUITING
COVERING OR PROVIDING BARRIERS TO ADJACENT LIVE PARTS
DISCONNECT THE EQUIPMENT FROM THE SUPPLY. USE ONLY AUTHORIZED
SPARE PARTS IN THE REPAIR OF THE EQUIPMENT. THE SPECIFIED
MAINTENANCE INTERVALS AS WELL AS THE INSTRUCTIONS FOR REPAIR
AND EXCHANGE MUST BE STRICTLY ADHERED TO PREVENT INJURY TO
PERSONNEL AND DAMAGE TO THE EQUIPMENT.
General information
Series NRX fixed circuit breakers are available in rear connect
(Figure 1) and front connect configurations (Figure 2). The arc hood
on a Series NRX fixed circuit breaker is positioned over the breakers
arc chambers to primarily direct arc gas discharge (Figure 1 and
Figure 2). An arc hood is used on all fixed circuit breakers whether
they are configured for rear or front connection. The front connect
configuration also contains a shroud mounted on the load side of the
breaker (Figure 2).
Both breaker configurations can be surface mounted (Figure 1) or
fixed mounted (Figure 2). Mounting feet can be used to fix mount
breakers to a vertical surface (Figure 2). Refer to IL01301020E for
mounting instructions.
Arc hood
Figure 1. Rear connect breaker
Arc hood
Holes for
surface
mounting
Mounting
feet for fixed
mounting
Shroud
Figure 2. Front connect breaker
3
Instruction Leaet IL01301015E
Effective November 2016
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
EATON www.eaton.com
Rear connected congurations
m CAUTION
DO NOT EXCEED THE RECOMMENDED TORQUE VALUES WHEN MAKING
BOLTED CONNECTIONS TO THE EQUIPMENT OR TO THE ADAPTERS
THEMSELVES, ALL WHICH HAVE PRE-TAPPED HOLES. IN ADDITION,
ANY CONNECTION HARDWARE USED SHOULD BE THE EXACT LENGTH
REQUIRED AND SHOULD NOT EXTEND OUT PAST THE MOUNTING
HOLE. FAILURE TO FOLLOW THESE REQUIREMENTS COULD RESULT IN
EQUIPMENT DAMAGE AND/OR FAILURE.
m IMPORTANT
IT IS RECOMMENDED THAT APPROPRIATE INTERPHASE BARRIERS BE
INSTALLED BETWEEN INSIDE AND OUTSIDE PRIMARY TERMINALS WITH
ALL REAR CONNECTED CONFIGURATIONS TO ENSURE INSULATION
INTEGRITY. IF INTERPHASE BARRIERS ARE ORDERED FROM EATON,
INSTALLATION INSTRUCTIONS ARE PROVIDED WITH THE BARRIERS.
Rear connect kit installation
This breaker configuration uses universal bus adapters that bolt to
the rear primary terminal pads (Figure 3). This type of adapter only
supports bus connections.
ØD
L
W
Dimensions in inches (mm)
L = 2.36 (59.9)
W = 1.96 (49.8)
D = 0.53 (13.5)
Figure 3. Universal bus adapter
For a horizontal bus connection, bolt a universal bus adapter
to the vertically positioned mounting holes of a rear primary
terminal pad using the hardware provided (Figure 4). For a vertical
bus connection, bolt a universal bus adapter to the horizontally
positioned mounting holes using the hardware provided.
Complete the other adapter connections in a similar fashion. The line
and load adapters can be mounted in opposite orientations at the
line and load sides (Figure 5). Torque the bolted connections to
10 ft-lb (13.6 N∙m).
To remove the adapters, reverse the procedure described above.
Figure 4. Horizontal universal bus connection
Horizontal
orientation
Vertical
orientation
Figure 5. Universal bus adapters in opposite orientations
4
Instruction Leaet IL01301015E
Effective November 2016
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
EATON www.eaton.com
Table 1. List of rear adapters
List
number Connector
Catalog
number
UL 489 UL 1066 IEC
42/50 kA 65 kA 42/50 kA 65 kA 42/50 kA 65 kA
1 Universal bus adapter—short SADP316
SADP416
n n n n n n
2 Universal bus adapter—long LADP316
LADP416
n n n n n n
3 Universal bus adapter—three hole, thick TADP316
TADP416
n n
Future Future
n n
4 Rear connect adapter extensions—short
(horizontal holes)
SBADPI316
SBADPI416
Future Future Future Future
n n
5 Rear connect adapter extensions—long
(vertical holes)
LBADPU316
LBADPU416
Future Future Future Future
n n
Rear connect long adapter extension kit installation
This breaker configuration uses long copper adapter extensions that
bolt to the rear primary terminal pads. The long adapter extension
comes with vertical holes for making the required connections
(Figure 6).
Use the hardware provided in the kits and torque bolted connections
to 10 ft-lb (13.6 N∙m).
Figure 6. Rear connect long adapter extension kit
Rear connect short adapter extension kit installation
This breaker configuration uses short copper adapter extensions that
bolt to the rear primary terminal pads. The short adapter extension
comes with horizontal holes for making the required connections
(Figure 7).
Use hardware provided in the kits and torque bolted connections
to 10 ft-lb (13.6 N∙m)
Figure 7. Rear connect short adapter extension kit
5
Instruction Leaet IL01301015E
Effective November 2016
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
EATON www.eaton.com
Front connected congurations
m CAUTION
IT IS IMPORTANT NOT TO EXCEED THE RECOMMENDED TORQUE VALUES
WHEN MAKING BOLTED CONNECTIONS TO THE EQUIPMENT OR TO THE
ADAPTERS THEMSELVES, ALL WHICH HAVE PRE-TAPPED HOLES. FAILURE
TO FOLLOW THESE REQUIREMENTS COULD RESULT IN EQUIPMENT
DAMAGE AND/OR FAILURE.
This breaker configuration has bus adapters that are internal to the
breaker and are intended to accommodate cable terminals and other
external bus connections. These cannot be replaced in the field.
The arc hood on the line side and the shroud on the load side serve
to insulate the bus adapters from their surroundings (Figure 8).
Refer to Table 2 for a list of available front connectors.
Arc hood
Shroud
Bus
adapters
Figure 8. Bus adapters at the line and load sides—back cover
not shown to highlight the bus adapters
Table 2. List of front connectors
List
number Connector
Catalog
number
UL 489 UL 1066 IEC
42/50 kA 65 kA 42/50 kA 65 kA 42/50 kA 65 kA
1 Bus conductor extension NRXBUSEXT
n
Future None None Future Future
2 Cable terminal (2 holes)
with control wire provision
TA700NB1M
TA700NB1MCWT
n n
None None
n n
3 Cable terminal (3 holes)
with control wire provision
TA1000NB1M
TA1000NB1MCWT
n n
None None
n n
4 Cable terminal (4 holes)
with control wire provision
TA1200NB1M
TA1200NB1MCWT
Future Future None None Future Future
Table 3. Cable terminal specifications
Maximum
breaker amperes
Terminal
body material Wire type
AWG wire range /
number of conductors
Metric wire
range mm
2
Catalog
number
Standard Cu/Al pressure terminals
700 Aluminum Cu/Al 1–500 kcmil (2) 50–240 TA700NB1M
TA700NB1MCWT
1000 Aluminum Cu/Al 3/0–400 kcmil (3) 95–185 TA1000NB1M
TA1000NB1MCWT
1200 Aluminum Cu/Al 4/0–500 kcmil (4) 120–240 TA1200NB1M
TA1200NB1MCWT
6
Instruction Leaet IL01301015E
Effective November 2016
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
EATON www.eaton.com
There are several connection configurations that can be used on the
Series NRX front connect. The list of available connections is shown
in Figure 9. These connectors can be used in any combination at
both the line and the load side as needed for the application.
Bus conductor extension
Cable terminal
Bus conductor extension
with cable terminal
Figure 9. Fixed front connect connection options
Front connect kit installation
In order to attach cable terminals or bus conductor extensions to the
line and load bus adapters, proceed with the following steps.
Step 1
Remove the four screws (or five screws for a four-pole breaker)
while holding the front of the arc hood. Also remove the four screws
(or five screws for a four-pole breaker) to remove the front of the
shroud that is mounted on the load side (Figure 10).
Remove screws
Remove screws
Figure 10. Step 1
Step 2
With the screws removed, pull out the front of the arc hood and set
it aside (Figure 11). Follow the same procedure to remove the front
shroud at the load side.
Figure 11. Step 2
Step 3
Slide each of the baffles forward and out to provide proper access to
the bus adapters (Figure 12).
Baffle
notches
Figure 12. Step 3
7
Instruction Leaet IL01301015E
Effective November 2016
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
EATON www.eaton.com
Step 4
Remove four screws and lift up front cover. On the line side, remove
the three screws on the secondary contact block assembly. Slide out
secondary contact block shield. With the screws removed, pull out
the secondary contact block assembly. On the load side, pull off the
front terminal load shield (Figure 13).
Terminal
shield
Front
terminal
load shield
Secondary
contact block
assembly
Figure 13. Step 4
Step 5
Access is now available to make the required bus conductor
extension or cable terminal connections. Access to the bottom
adapters is also now available for bus or cable terminal connections
(Figure 14).
If using bus conductor extensions, start at Step 6.
If using cable terminal connection, move to Step 7.
Figure 14. Step 5
Step 6
Bus conductor extension kit installation—catalog number NRXBUSEXT.
(E)
M12 lock
washer
12x
(D)
M12 flat
washer
12x
(H)
M8 flat
washer
6x
(G)
M8 belleville
washer
6x
(F)
M8 x 16 mm
flathead screw
6x
(C)
M12 x 30 mm
socket cap screw
12x
(B)
Bus conductor
extension
6x
(A)
Phase
barrier
2x
Figure 15. Bus conductor extension kit—
catalog number NRXBUSEXT
1. Bolt the bus conductor extensions to the breaker bus adapters
using the provided hardware. Torque the bolted connections to
30 ft-lb (40.7 N∙m).
Make sure that the hardware used to make the connections
does not extend out past the adapter surface. Check that the
bolt goes all the way through the bus adapters.
2. Once the bolted connections are made, replace the baffles
removed in Step 3 by sliding them back into position, making sure
that the baffle notches are oriented toward the breaker. The bus
extensions will fit through the space available between the baffles
and the arc hood. Replace secondary block assembly shield.
3. Replace the secondary contact block assembly previously
removed in Step 4.
4. Replace front of the arc hood and the front of the shroud
previously removed in Step 1 and Step 2. Replace front cover.
5. Phase barriers made from flexible rubber material are supplied
with the bus extension kit, along with the cable terminals. The
phase barriers should be installed to the right and left of the
center bus connector extension on both the line and the load
sides. These phase barriers provide proper insulation integrity
(Figure 16).
m CAUTION
MAKE SURE THE PHASE BARRIERS FROM STEP 6.5 ARE PROPERLY
INSTALLED BEFORE PLACING THE CIRCUIT BREAKER INTO SERVICE.
FAILURE TO FOLLOW THESE REQUIREMENTS COULD RESULT IN
EQUIPMENT DAMAGE AND/OR FAILURE.
8
Instruction Leaet IL01301015E
Effective November 2016
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
EATON www.eaton.com
Phase barriers
Tapped holes
Bus conductor
extensions
Figure 16. Step 6.5
If only using bus conductor extension kit, skip Step 7.
Cable terminal kit installation
ote:N Step 1 through Step 4 need to be completed before proceeding
with Step 7.
(I)
Cable terminal
TA700NB1M (CWT)
(J)
Cable terminal
TA1000NB1M (CWT)
(K)
Cable terminal
TA1200NB1M (CWT)
(L)
M12
hex bolt
(M)
M12 lock
washer
Figure 17. Cable terminal kit (CWT—control wire provision)
66B2638H01
NOTICE
Figure 18. Cable terminals torque requirements
Step 7
Cable terminal connections can be made directly to the bus adapters
inside the breaker or to the bus conductor extensions that extend
out of the line and load sides of the breaker (refer to Step 5). Cable
terminals are shown in Figure 19 and described in Table 3.
To complete the connections, proceed with the following steps.
1. Bolt the cable terminals directly to the bus adapters using the
hardware provided (Figure 19). Cable terminals can also be
bolted to the bus connector extensions (Figure 20). Torque the
bolted connections to 30 ft-lb (27 N∙m).
ote:N Bus conductor extensions with cable terminals only available for
42/50 kA interruption ratings.
Figure 19. Step 7.1—Connecting cable terminals directly
to bus adapters
Figure 20. Bus conductor extension with cable terminal
(available for 42/50 kA interruption ratings)
9
Instruction Leaet IL01301015E
Effective November 2016
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
EATON www.eaton.com
2. Install additional cable terminal connections as required
(Figure 21). Complete cable installation before proceeding
with next step.
Figure 21. Step 7.2—Cable terminals connected directly
to bus adapters
3. Replace the front of the arc hood and the shroud as previously
removed in Step 1 and Step 2. The baffles removed in Step 1 are
no longer required in the arc hood if connecting cable terminals
directly to the bus adapter. The newly mounted cable terminals
will now perform the baffles’ function. However, if connecting the
cable terminals to a bus conductor extension, re-install baffles
before replacing the arc hood and shroud.
4. Phase barriers made from a flexible rubber material are supplied
with the cable terminals. If using cable terminals connected to
bus connecter extensions, phase barriers must be installed to
the right and left of the center cable terminal on both the line
and the load sides (to the right and left of the two center cable
terminals for four-pole) (Figure 22). These phase barriers provide
proper insulation integrity.
Figure 22. Step 7.4—Cable terminals connected onto bus
extensions on both line and load side
10
Instruction Leaet IL01301015E
Effective November 2016
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
EATON www.eaton.com
As an option, customers can order a terminal shield to install at the
line side of the front connect breaker (Figure 23).
Figure 23. Terminal shield installed on a front connect breaker
5. When making the cable terminal connections, properly torque
the cable retaining screws and periodically check all mounting
hardware for proper torque loading. Refer to Figure 24 for rope
lacing support instructions.
To remove the cable terminals, reverse the procedure
described above.
NYLON
6 INCHES
(152 mm.)
ROPE
EXCEPTION: Not required
when installed in Panelboards
or Switchboards using
busbar connections.
Unsupported cables can cause
minor personal injury or
equipment damage under short
circuit conditions.
Wrap breaker cables with 3/8 inch
nylon or equivalent rope as shown
in Figure having a minimum
tensile strength of 2000 pounds at
6 inches from terminals and every
additional 6 inches with five wraps
or every additional 1 inch with
one wrap.
CAUTION
66B2609H01
Figure 24. Rope lacing instructions
Hybrid connected congurations
The hybrid breaker configuration family of rear-fixed adapters
(Table 1) and front-fixed connectors (Table 2) may be used
interchangeably on the line side or load side of the breaker.
Figure 25 and Figure 26 show two of the most common
configurations. For proper installation procedures, please refer
to pages 3–9 of this manual or contact the Eaton production
facility for further information.
Figure 25. Typical hybrid configuration 1 using connectors
on the line side and adapters on the load side
Figure 26. Typical hybrid configuration 2 using adapters on the
line side and connectors on the load side
11
Instruction Leaet IL01301015E
Effective November 2016
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
EATON www.eaton.com
Disclaimer of warranties and limitation
of liability
The information, recommendations, descriptions, and safety
notations in this document are based on Eatons experience and
judgment, and may not cover all contingencies. If further information
is required, an Eaton sales office should be consulted.
Sale of the product shown in this literature is subject to the terms
and conditions outlined in appropriate Eaton selling policies or other
contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES,
EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF
FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY,
OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING
CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT
STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF
THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY
ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in
contract, in tort (including negligence), strict liability or otherwise
for any special, indirect, incidental or consequential damage or loss
whatsoever, including but not limited to damage or loss of use of
equipment, plant or power system, cost of capital, loss of power,
additional expenses in the use of existing power facilities, or claims
against the purchaser or user by its customers resulting from
the use of the information, recommendations and description
contained herein.
The information contained in this manual is subject to change
without notice.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2016 Eaton
All Rights Reserved
Printed in USA
Publication No. IL01301015E / Z18850
Part Number: IL01301015EH08
November 2016
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Installation instructions for Series NRX
Type NF frame xed breaker rear connect,
front connect, and hybrid congurations
Instruction Leaet IL01301015E
Effective November 2016
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Eaton Series NRX Installation Instructions Manual

Type
Installation Instructions Manual

Eaton Series NRX circuit breakers offer reliable protection for your electrical systems. With a range of configurations, including rear connect, front connect, and hybrid options, these breakers can be tailored to your specific needs. The universal bus adapters and copper adapter extensions provide flexibility for various connection options. The arc hood and shroud enhance safety by directing arc gas discharge and insulating the bus adapters. These breakers are suitable for both surface and fixed mounting, making them a versatile choice for your electrical installations.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI