Fluke 1625-2 GEO Earth Ground Tester Kit allows you to perform earth ground loop and stakeless ground loop tests, 3 and 4-pole soil resistivity tests, and 2-pole ground resistance tests. The kit includes a tester, two H/C clamps, a sensing current clamp with an adapter cable, test leads, earth stakes, and a soft carrying case. With an IP56 rating, it can withstand dust, water, and accidental drops, making it suitable for use in harsh conditions.

Fluke 1625-2 GEO Earth Ground Tester Kit allows you to perform earth ground loop and stakeless ground loop tests, 3 and 4-pole soil resistivity tests, and 2-pole ground resistance tests. The kit includes a tester, two H/C clamps, a sensing current clamp with an adapter cable, test leads, earth stakes, and a soft carrying case. With an IP56 rating, it can withstand dust, water, and accidental drops, making it suitable for use in harsh conditions.

Manual Supplement
© 2014-2015 Fluke Corporation. All rights reserved.
Manual Title: 1625-2 Users Supplement Issue: 3
Print Date: January 2014 Issue Date: 5/15
Revision/Date: Page Count: 3
This supplement contains information necessary to ensure the accuracy of
the above manual. This manual is distributed as an electronic manual on the
following CD-ROM:
CD Title: 1623-2/1625-2
CD Rev. & Date: 1/2014
CD PN: 4325414
1625-2 Users Manual Supplement
5/15 1
Change #1, 152
On page 36, following Figure 14 add:
Stakeless Ground Loop Measurement
With this test method, two clamps are placed around the earth ground rod or the connecting cable and
each are connected to the Tester. Earth ground stakes are not used. A known voltage is induced by one
clamp, and the current is measured with the second clamp. The tester automatically determines the
ground loop resistance at this ground rod.
1. Select
. See Figure.
2. Connect current clamps.
Connect the inducing clamp to terminals H/C2 and E/C1 with the supplied safety
test leads (15 cm) as shown.
Note
Use the recommended current clamp for inducing only.
Other current clamps are not suited.
Connect the second current clamp using the adapter cable (sensing current clamp).
Clamp both current clamps around the earth electrode, which will subsequently be
measured.
Note
Minimum distance between the two current clamps is 15 cm.
3. Push "START TEST" button.
4. Read out measured value R
E.
Manual Supplement 1625-2 Users
2 5/15
edw008.eps
Stakeless Ground Loop Measurement
START
1 2
3 4
1623-2 EARTH/GROUND TESTER
1
15 cm
1625-2 Users Manual Supplement
8/14 3
Change #2
On page 44, replace the first table with:
Range Display Range Resolution Accuracy Operating Error
0.020...300 k
0.02...29.99 0.01
±(2 % rdg+2 digits) ±(5 % rdg+5 digits)
30.0...299.9 0.1
0.300 k...2.999 k 1
3.00...29.99 k 10
30.0 k...299.9 k 100
*If auxiliary earth resistance is lower than 300 ohms, the resolution of test range 0.020 to 2.999 will improve to
0.001 .
On page 45, replace the table with:
Range Display Range Resolution Accuracy Operating Error
0.020...300 k
0.02...29.99 0.01
±(7 % rdg+2 digits) ±(10% rdg + 5 digits)
30.0...299.9 0.1
0.300 k...2.999 k 1
3.00...29.99 k 10
30.0 k...299.9 k 100
*If auxiliary earth resistance is lower than 300 ohms, the resolution of test range 0.020 to 2.999 will improve to
0.001 .
On page 47, replace the table with:
Resolution Range Accuracy Operating Error
0.001 0.020 to 1.000 ±(7 % rdg + 10 digits) ±(10 % rdg + 5 digits)
0.001 to 0.1 1.001 to 199.9 ±(7 % rdg + 3 digits) ±(10 % rdg + 5 digits)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Fluke 1625-2 GEO Earth Ground Tester Kit allows you to perform earth ground loop and stakeless ground loop tests, 3 and 4-pole soil resistivity tests, and 2-pole ground resistance tests. The kit includes a tester, two H/C clamps, a sensing current clamp with an adapter cable, test leads, earth stakes, and a soft carrying case. With an IP56 rating, it can withstand dust, water, and accidental drops, making it suitable for use in harsh conditions.