Pool/Spa Underwater Lighting Application
LANDSCAPE LIGHTING APPLICATIONS
INSTALLATION
For field wiring information, please refer to the instructions attached to inside of front cover.
• Make sure that all unused taps (leads) are separately insulated.
• Use the following tables as a guide to determine the correct wire size.
• The voltage at lamp terminals after installation should be 12 ± 0.3 VAC.
• Voltages above 12.3 VAC at the light may cause the internal safety fuse of the transformer to
switch off and on. To prevent this from happening follow chart below for correct voltage and
wire gauge selection.
1. Select power source by combining Bulb wattage.
2. Determine length of cable run(s).
3. Determine wire gauge needed to deliver necessary power.
4. Connect cable to output tap of transformer given in table.
Distance* 2#6AWG 2#8AWG 2#10AWG 2#12AWG 2#14AWG
Feet
5 ft. 12 VAC 12 VAC 12 VAC 12 VAC 12 VAC
30 ft. 12 VAC 12 VAC 12 VAC 13 VAC 13 VAC
60 ft. 12 VAC 12 VAC 13 VAC 13 VAC
90 ft. 12 VAC 13 VAC 13 VAC
120 ft. 13 VAC 13 VAC
150 ft. 13 VAC 13 VAC
180 ft. 13 VAC
210 ft. 13 VAC
240 ft. 13 VAC
* Length of run to light from transformer.
Distance* 2#6AWG 2#8AWG 2#10AWG 2#12AWG
Feet
5 ft. 12 VAC 12 VAC 12 VAC 12 VAC
10 ft. 12 VAC 12 VAC 12 VAC 13 VAC
20 ft. 12 VAC 12 VAC 13 VAC 13 VAC
30 ft. 12 VAC 13 VAC 13 VAC 14 VAC
40 ft. 13 VAC 13 VAC 14 VAC
50 ft. 13 VAC 13 VAC 14 VAC
60 ft. 13 VAC 14 VAC
70 ft. 13 VAC 14 VAC
80 ft. 13 VAC 14 VAC
90 ft. 14 VAC
100 ft. 14 VAC
110 ft. 14 VAC
* Length of run to light from transformer.
120 VAC Primary Input - 100 W Output 120 VAC Primary Input - 300 W Output
LIMITED ONE-YEAR WARRANTY
If within the warranty period specified, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace it, at its sole option, free of charge.
This warranty is extended to the original household purchaser only and is not transferable. This warranty does not apply to: (a) damage to units caused by accident, dropping or abuse
in handling, acts of God or any negligent use; (b) units which have been subject to unauthorized repair, opened, taken apart or otherwise modified; (c) units not used in accordance
with instructions; (d) damages exceeding the cost of the product; (e) sealed lamps and/or lamp bulbs, LED’s and batteries; (f) the finish on any portion of the product, such as surface
and/or weathering, as this is considered normal wear and tear; (g) transit damage, initial installation costs, removal costs, or reinstallation costs.
INTERMATIC INCORPORATED WILL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF
INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU. THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS OR
IMPLIED WARRANTIES. ALL IMPLIED WARRANTIES, INCLUDING THE WARRANTY OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE,
ARE HEREBY MODIFIED TO EXIST ONLY AS CONTAINED IN THIS LIMITED WARRANTY, AND SHALL BE OF THE SAME DURATION AS THE WARRANTY PERIOD STATED ABOVE.
SOME STATES DO NOT ALLOW LIMITATIONS ON THE DURATION OF AN IMPLIED WARRANTY, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a warranty claim online at www.
intermatic.com. This warranty is made by: Intermatic Incorporated, Customer Service 7777 Winn Rd., Spring Grove, Illinois 60081-9698. For warranty service go to: http://www.
Intermatic.com or call 815-675-7000.
2
• Use only CSA or UL certified low-voltage cable.
• Low voltage cable shall be buried a maximum 6
inches (15.2 cm) in order to connect to the main low
voltage cable.
Transformer Wattage (W) Minimum Gauge AWG
300 12
100 16-14-12