EXHAUST HOSE REEL
8
Foreword
To guarantee a correct function and a minimal
service, iot is important to read and understand the
information in this instruction manual.
The product is designed to meet the requirements
of the relevant EC directives. To maintain this status
all installation, repair and maintenance work must be
carried out by qualied personnel using only original
spare parts. Contact your nearest authorised dealer
or AB Ph. Nederman & Co. for advice on technical
service or if you require spare parts.
Connection duct
See picture page 3. The connection hose supplied with
the reel, should be used for connecting the reel
to duct systems and a central fan. NB! The duct
must be tted with hose clips. Do not drill or t with
screws.
Fan positioning
A suitable fan can be selected from the Nederman
fan range. To avoide leakage in the ducting system
the fan should be positioned outdoors or as near the
duct outlet in the room as possible.
GB
Technical data
Weights
Without hose: 32 kg (70.5 lbs)
With hose and nozzle: 40 – 55 kg (82 – 121 lbs)
Duct connection Ø 200 mm (8 in)
Recommended airows
For trucks: 800 – 2500 m
3
/h (470 – 1460 cfm)
Ambient temperature
-10 °C to +50 °C (15 °F to 120 °F)
Exhaust temperature Maximum 300 °C
Hose temperature resistance
Hose NR-CP: 150 °C (300 °F) continuously
Hose NFC-3: 300 °C (570 °F) continuously
Power supply
100 V, 115 V, 200 V, 230-240 V AC
1-phase, 50/60 Hz
Power consumption Maximum 325 VA
Protection class IP 44
Noise level
Measured according to ISO 11201. < 70 dB(A).
Material recycling
Reels without hose: 100 weight-%
Mounting instruction
See pictures page 2. The maximum mounting height
is depending of the hose length and weight. NB! The
maximum allowed uncoiled free hanging hose weight
including nozzle is 27,5 kg. Choose such mounting
height so that the hose in uncoiled position can be
connected to the vehicle’s exhaust pipe without being
stretched.
1. Make sure that the surface, on which to mount the
reel, is level. Drill 4 holes, using the hole template
which comes in the package.
2. Fit the mounting brackets in such a way that will
make the reel hanging horizontally. Ensure that suitable
xing bolts are used considering the ceiling
or wall construction material. The bolts must each
stand a tractive force of minimum 6500 N.
3. Use approved lifting equipment to lift the reel. Fasten
the reel in the brackets.
Mounting the hose
See pictures page 3. When the reel has been mounted
and connected to the power suppy, the hose should be
tted (concer-ning reels delivered without hose only).
It should be noted that the reel can not be rotated by
hand.
1. Fasten the hose with a hose clip on the connecting
piece inside the drum.
2. Aim the hand control towards the indicator (remote
controled reel only). Press the UP-button on the hand
control. The indicator shows xed red light. Release the
button at required hose position.
3. Fit the nozzle.
4. When needed adjust the limit positions for coiled and
uncoiled hose (see page 9).
Electrical installation
See wiring diagram page 4.
All electrical work must be done by a qualied electri-
cian according to local regulations.
Connect the reel to the power supply by joining the
incoming cable to the connection block in the reel’s
receiver.
After installation check that the functions for
uncoiling and coiling the hose correspond to
the press button arrows on the hand control.
If not, reconnect the cable from the hand control cor-
rectly on the connection block.
Cable recommendation for the hand control:
3 x 0,75 mm
2
, to be connected according to the
wiring diagram.
The reel is factory set for a voltage supply
of 230/240 V AC