Generac 120/208V, 800A RTSN800G3 User manual

Type
User manual

The Generac 120/208V, 800A RTSN800G3 automatic transfer switch is designed to seamlessly transition your critical electrical loads from utility power to generator power during outages. With its impressive 800 amp rating, it can handle the power needs of large homes or small businesses. Installation is simplified with clear instructions and diagrams provided in the owner's manual, ensuring a safe and proper setup. Once installed, the transfer switch will automatically monitor your utility power and switch to generator power within seconds of an outage.

The Generac 120/208V, 800A RTSN800G3 automatic transfer switch is designed to seamlessly transition your critical electrical loads from utility power to generator power during outages. With its impressive 800 amp rating, it can handle the power needs of large homes or small businesses. Installation is simplified with clear instructions and diagrams provided in the owner's manual, ensuring a safe and proper setup. Once installed, the transfer switch will automatically monitor your utility power and switch to generator power within seconds of an outage.

Owner's Manual
600 and 800 Amp RTS Automatic Transfer Switch
The manufacturer cannot anticipate every possible circumstance
that might involve a hazard. The warnings in this manual, and on
tags and decals affixed to the unit are, therefore, not all-inclusive. If
using a procedure, work method or operating technique the manu-
facturer does not specifically recommend, ensure that it is safe for
others. Also make sure the procedure, work method or operating
technique chosen does not render the transfer switch unsafe.
Throughout this publication, and on tags and decals affixed to the
generator, DANGER, WARNING, CAUTION and NOTE blocks are
used to alert personnel to special instructions about a particular
operation that may be hazardous if performed incorrectly or care-
lessly. Observe them carefully. Their definitions are as follows:
After this heading, read instructions that, if not
strictly complied with, will result in serious
personal injury, including death.
After this heading, read instructions that, if not
strictly complied with, could result in serious
personal injury, including death.
After this heading, read instructions that, if not
strictly complied with, might result in minor or
moderate injury.
NOTE:
After this heading, read instructions that, if not strictly complied
with, may result in damage to equipment and/or property.
These safety warnings cannot eliminate the hazards that they
indicate. Common sense and strict compliance with the special
instructions while performing the service are essential to prevent-
ing accidents.
Four commonly used safety symbols accompany the DANGER,
WARNING and CAUTION blocks. The type of information each
indicates follows:
This symbol points out important safety
information that, if not followed, could
endanger personal safety and/or property.

This symbol points out potential explosion
hazard.

This symbol points out potential fire hazard.
This symbol points out potential electrical
shock hazard.
GENERAL HAZARDS
Any AC generator that is used for backup power if a NORMAL
(UTILITY) power source failure occurs, must be isolated from
the NORMAL (UTILITY) power source by means of an approved
transfer switch. Failure to properly isolate the NORMAL and
STANDBY power sources from each other may result in injury
or death to electric utility workers, due to backfeed of electrical
energy.
Improper or unauthorized installation, operation, service or
repair of the equipment is extremely dangerous and may result
in death, serious personal injury, or damage to equipment and/
or personal property.
Extremely high and dangerous power voltages are present inside
an installed transfer switch. Any contact with high voltage ter-
minals, contacts or wires will result in extremely hazardous,
and possibly LETHAL, electric shock. DO NOT WORK ON THE
TRANSFER SWITCH UNTIL ALL POWER VOLTAGE SUPPLIES
TO THE SWITCH HAVE BEEN POSITIVELY TURNED OFF.
Competent, qualified personnel should install, operate and ser-
vice this equipment. Adhere strictly to local, state and national
electrical and building codes. When using this equipment,
comply with regulations the National Electrical Code (NEC),
CSA Standard; C22.1 Canadian Electric Code and Occupational
Safety and Health Administration (OSHA) have established.
Never handle any kind of electrical device while stand-
ing in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
Remove all jewelry (such as rings, watches, bracelets, etc.)
before working on this equipment.
SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install,
operate or service this equipment. Also read the instructions and information on tags, decals, and
labels that may be affixed to the transfer switch. Replace any decal or label that is no longer legible.
DANGER! Connection of a generator to an electrical system normally supplied by an electric util-
ity shall be by means of suitable transfer equipment so as to isolate the electric system from utility
distribution system when the generator is operating (Article 701 Legally Required Standby Systems
or Article 702 Optional Standby Systems, as applicable). Failure to isolate electric system by these
means may result in damage to generator and may result in injury or death to utility workers due to
backfeed of electrical energy.
Safety Rules
1
If work must be done on this equipment while standing on metal
or concrete, place insulative mats over a dry wood platform.
Work on this equipment only while standing on such insulative
mats.
• Never work on this equipment while physically or mentally
fatigued.
Keep the transfer switch enclosure door closed and bolted at all
times. Only qualified personnel should be permitted access to
the switch interior.
In case of an accident caused by electric shock, immediately
shut down the source of electrical power. If this is not possible,
attempt to free the victim from the live conductor but AVOID
DIRECT CONTACT WITH THE VICTIM. Use a nonconducting
implement, such as a dry rope or board, to free the victim from
the live conductor. If the victim is unconscious, apply first aid
and get immediate medical help.
When an automatic transfer switch is installed for a standby
generator set, the generator engine may crank and start at
any time without warning. To avoid possible injury that might
be caused by such sudden start-ups, the system’s automatic
start circuit must be disabled before working on or around the
generator or transfer switch. Then place a “DO NOT OPERATE”
tag on the transfer switch and on the generator. Remove the
Negative (Neg) or (–) battery cable.
Safety Rules .................................................Inside Front Cover
General Information ................................................................. 2
1.1 Introduction ................................................................................ 2
1.2 Equipment Description ................................................................ 2
1.3 Transfer Switch Data Label.......................................................... 2
1.4 Transfer Switch Enclosure ...........................................................2
1.5 Safe Use Of Transfer Switch........................................................ 2
Installation ............................................................................... 3
2.1 Introduction to Installation ...........................................................3
2.2 Unpacking .................................................................................. 3
2.3 Mounting .................................................................................... 3
2.4 Connecting Power Source and Load Lines .................................. 3
2.4.1 3-Pole Mechanism ............................................................ 3
2.5 Connecting Control Wires ........................................................... 4
2.6 Auxiliary Contacts ....................................................................... 4
2.7 Optional Accessories .................................................................. 4
Operation ................................................................................. 4
3.1 Functional Tests & Adjustments .................................................. 4
3.2 Manual Operation ........................................................................ 5
3.2.1 Trip to Neutral Position ...................................................... 5
3.2.2 Close to Emergency Source Side ...................................... 6
3.2.3 Close to Normal Source Side ............................................ 6
3.3 Voltage Checks ........................................................................... 6
3.3.1 Utility Voltage Checks ....................................................... 6
3.3.2 Generator Voltage Checks ................................................. 7
3.4 Generator Tests Under Load ........................................................ 8
Interconnection Diagram ......................................................... 9
Installation Diagram .............................................................. 10
Notes ..................................................................................... 12
For authorized service,
reference the dealer locator
number found inside the
generator owner’s manual.
Table of Contents
2
1.1 INTRODUCTION
This manual has been prepared especially for the purpose of famil-
iarizing personnel with the design, application, installation, opera-
tion and servicing of the applicable equipment. Read the manual
carefully and comply with all instructions. This will help to prevent
accidents or damage to equipment that might otherwise be caused
by carelessness, incorrect application, or improper procedures.
Every effort has been expended to make sure that the contents
of this manual are both accurate and current. The manufacturer,
however, reserves the right to change, alter or otherwise improve
the product at any time without prior notice.
1.2 EQUIPMENT DESCRIPTION
The automatic transfer switch is used for transferring critical
electrical loads from a UTILITY (NORMAL) power source to an
EMERGENCY (GNERATOR) power source.
The transfer switch prevents electrical feedback between the
UTILITY and EMERGENCY sources. For that reason, electrical
codes require a transfer switch in all standby electric system
installations.
When the transfer switch is connected to the engine generator
control panel, the control panel constantly monitors the UTILITY
voltage and controls the operation of the transfer switch.
Should the UTILITY voltage drop below a preset value, and remain
at this low voltage for a preset amount of time, the generator
cranks and starts. After the generator starts, the transfer switch
transfers the load circuits to the generator, the generator then sup-
plies the loads. When UTILITY returns above a preset level the load
is transferred back to the UTILITY and the generator shuts down.
This manual is for RTS models:
RTSN600A3 600A - 120/240V, 1-phase
RTSN600G3 600A - 120/208V, 3-phase
RTSN600J3 600A - 120/240V, 3-phase
RTSN600K3 600A - 277/480V, 3-phase
RTSN800A3 800A - 120/240V, 1-phase
RTSN800G3 800A - 120/208V, 3-phase
RTSN800J3 800A - 120/240V, 3-phase
RTSN800K3 800A - 277/480V, 3-phase
RTSN600A3S 600A-120/240V 1-PHASE
RTSN600G3S 600A-120/208V 3-PHASE
RTSN600J3S 600A-120/240V 3-PHASE
RTSN600K3S 600A-277/480V 3-PHASE
RTSN600A3S 800A-120/240V 1-PHASE
RTSN600G3S 800A-120/208V 3-PHASE
RTSN600J3S 800A-120/240V 3-PHASE
RTSN600K3S 800A-277/480V 3-PHASE
1.3 TRANSFER SWITCH DATA
LABEL
A DATA LABEL is permanently affixed to the transfer switch enclo-
sure. Use this transfer switch only with the specific limits shown
on the DATA LABEL and on other decals and labels that may be
affixed to the switch. This will prevent damage to equipment and
property.
When requesting information or ordering parts for this equipment,
make sure to include all information from the DATA LABEL.
Record the Model and Serial numbers in the space provided below
for future reference.
MODEL #
SERIAL #
1.4 TRANSFER SWITCH
ENCLOSURE
The standard switch enclosure is a National Electrical Manufacturer’s
Association (NEMA) and UL 3R type. UL and NEMA 3R type enclo-
sures primarily provide a degree of protection against falling rain
and sleet; undamaged by the formation of ice on the enclosure.
1.5 SAFE USE OF TRANSFER
SWITCH
Before installing, operating or servicing this equipment, read the
SAFETY RULES (inside front cover) carefully. Comply strictly with
all SAFETY RULES to prevent accidents and/or damage to the
equipment. The manufacturer recommends a copy of the SAFETY
RULES are made and posted near the transfer switch. Also, be
sure to read all instructions and information found on tags, labels
and decals affixed to the equipment.
Two publications that outline the safe use of transfer switches are
the following:
NFPA 70; National Electrical Code
• UL 1008, STANDARD FOR SAFETY-AUTOMATIC TRANSFER
SWITCHES
NOTE:
It is essential to use the latest version of any standard to ensure
correct and current information.
General Information
3
2.1 INTRODUCTION TO
INSTALLATION
This equipment has been wired and tested at the factory. Installing
the switch includes the following procedures:
Mounting the enclosure.
• Connecting utility and generator power source leads.
Connecting the load leads.
Connecting any auxiliary contact (if needed)
Installing/connecting any options and accessories.
• Testing functions.
2.2 UNPACKING
Carefully unpack the transfer switch. Inspect closely for any dam-
age that might have occurred during shipment. The purchaser must
file with the carrier any claims for loss or damage incurred while in
transit.
Check that all packing material is completely removed from the
switch prior to installation.
2.3 MOUNTING
Mounting dimensions for the transfer switch enclosure are in this
manual. See the “Mounting Dimensions” drawing.
Handle transfer switches carefully when
installing. Do not drop the switch. Protect
the switch against impact at all times, and
against construction grit and metal chips.
Never install a transfer switch that has been
damaged.
Install the transfer switch as close as possible to the electrical
loads that are to be connected to it. The switch enclosure is suit-
able for wall or floor mounting. For wall mounting, remove the
floor stands to gain access to the mounting points on the bottom
of the enclosure. Mount the switch vertically to a rigid supporting
structure. For floor mounting, place switch enclosure on a hard,
level surface. Secure enclosure to the floor. To prevent switch
distortion, level all mounting points. If necessary, use washers
behind mounting holes to level the unit.
2.4 CONNECTING POWER SOURCE
AND LOAD LINES

Make sure to turn OFF both the UTILITY
(Normal) and EMERGENCY (Standby genera-
tor) power supplies before trying to connect
power source and load lines to the transfer
switch. Supply voltages are extremely high
and dangerous. Contact with such high volt-
age power supply lines causes extremely
hazardous, possibly lethal, electrical shock.
Wiring diagrams and electrical schematics are provided in this
manual. Power source and load connections are made at the
transfer mechanism, inside the switch enclosure.
2.4.1 3-POLE MECHANISM
These switches (Figure 2.1) are used with a three phase system,
when the three phase NEUTRAL line is to be connected to a
NEUTRAL lug and is not to be switched.
Figure 2.1 — Typical 3-Pole Transfer Mechanism
(800 Amp Shown)
Solderless, screw-type terminal lugs are standard.
The conductor size range is as follows:
Switch Rating Wire Range
600A 2 x 1/0-500 MCM per pole
800A 4 x 4/0-500 MCM per pole
Conductor sizes must be adequate to handle the maximum cur-
rent to which they will be subjected; based on the 75°C column of
tables, charts, etc. used to size conductors. The installation must
comply fully with all applicable codes, standards and regulations.
Before connecting wiring cables to terminals, remove any surface
oxides from the cable ends with a wire brush. All power cables
should enter the switch next to transfer mechanism terminals.
If ALUMINUM conductors are used, apply corrosion inhibitor to
conductors. Tighten terminal lugs to the torque values as noted on
the decal located on the inside of the door. After tightening terminal
lugs, carefully wipe away any excess corrosion inhibitor.
All power cables should enter the switch next to the transfer
mechanism terminals.
Use a torque wrench to tighten the conduc-
tors, being sure not to overtighten, or dam-
age to the switch base could occur. If under-
tightened, a loose connection would result,
causing excess heat which could damage
the switch base.
Installation
4
Proper conductor tightening torque values are on the decal inside
the enclosure door.
Connect power source load conductors to clearly marked transfer
mechanism terminal lugs as follows
1. Connect UTILITY (NORMAL) power source cables to switch
terminals N1, N2, (N3).
2. Connect EMERGENCY (STANDBY) source power cables to
transfer switch terminals E1, E2, (E3).
3. Connect customer LOAD leads to switch terminals T1, T2,
(T3).
4. Connect neutral conductors of UTILITY, EMERGENCY and
customer LOAD to the neutral block.
Conductors must be properly supported, of approved insulative
qualities, protected by approved conduit, and of the correct wire
gauge size in accordance with applicable codes.
Be sure to maintain proper electrical clearance between live metal
parts and grounded metal. Allow at least 1/2 inch through air or
1" over surface.
2.5 CONNECTING CONTROL
WIRES
Control system interconnections consist of UTILITY 1 and 2, and
leads 23 and 194. Control system interconnection leads must
be run in a conduit that is separate from the AC power lead.
Recommended wire gauge sizes for this wiring depends on the
length of the wire, as recommended below:
MAXIMUM WIRE LENGTH RECOMMENDED WIRE SIZE
1-115 ft (1-35m) No. 18 AWG.
116-185 ft (36-56m) No. 16 AWG.
186-295 ft (57-89m) No. 14 AWG.
296-460 ft (90-140m) No. 12 AWG.
2.6 AUXILIARY CONTACTS
If desired, there are Auxiliary Contacts on the transfer switch to
operate customer accessories, remote advisory lights, or remote
annunciator devices. A suitable power source must be connected
to the COMMON (C) terminal. See Figure 2.2.
Contact operation is shown in the following chart:
Switch Position
Utility Standby
Common to Normally Open Open Closed
Common to Normally Closed Closed Open
NOTE:
Auxiliary Contacts are rated 10 amps at 125 or 250 volts AC.
DO NOT EXCEED THE RATED VOLTAGE AND CURRENT OF THE
CONTACTS.
Figure 2.2 – Auxiliary Contacts
Side views shown in Utility position
2.7 OPTIONAL ACCESSORIES
Note any optional accessories that may be installed on the trans-
fer switch or are to be installed in the standby electric system in
conjunction with the switch. Complete the necessary connections
for these accessories.
3.1 FUNCTIONAL TESTS AND
ADJUSTMENTS
Following transfer switch installation and inter-
connection, inspect the entire installation care-
fully. A competent, qualified electrician should
inspect it. The installation should comply strictly
with all applicable codes, standards, and regula-
tions. When absolutely certain the installation is
proper and correct, complete a functional test of
the system.
Perform functional tests in the exact order
presented in this manual, or damage to the
switch could be done.
IMPORTANT: Before proceeding with functional tests, read and
make sure you understand all instructions and information in this
section. Also read the information and instructions of labels and
decals affixed to the switch. Note any options or accessories that
might be installed and review their operation.
Operation
5
3.2 MANUAL OPERATION
Do NOT manually transfer under load.
Disconnect transfer switch from all power
sources by approved means, such as a main
circuit breaker(s).
A manual HANDLE is shipped with the transfer switch. Manual
operation must be checked BEFORE the transfer switch is oper-
ated electrically. To check manual operation, proceed as follows
(Figure 3.1):
1. Turn the generator’s AUTO-OFF-MANUAL switch to OFF.
2. Turn OFF both NORMAL and STANDBY power supplies to the
transfer switch, with whatever means provided (such as the
main line circuit breakers).
3. Note position of transfer mechanism main contacts by
observing display windows in “A” and “B” in Figure 3.1 as
follows:
Window “A” ON, Window “B” OFF - LOAD terminals (T1, T2,
T3) are connected to NORMAL terminals (N1, N2, N3).
Window “A” OFF, Window “B” ON - LOAD terminals (T1, T2,
T3) are connected to STANDBY terminals (E1, E2, E3).
Do not use excessive force when operating
the transfer switch manually or the manual
handle could be damaged.
3.2.1 TRIP TO NEUTRAL POSITION
Remove handle from the square lug at the upper left corner of the
switch. Insert a screwdriver into the “T” hole and push inward. The
main contact should trip to the neutral position and the word OFF
should appear in both windows “A” and “B”. See Figure 3.2.
Figure 3.2 — Trip to Neutral
Operation
Figure 3.1 — Actuating Transfer Switch
6
3.2.2 CLOSE TO EMERGENCY SOURCE SIDE
Before proceeding, verify the position of the switch by observing
window “A” and window “B”. If window “B” displays ON the ATS
is closed in the STANDBY position, with the LOAD connected to
the STANDBY source. It is not necessary to manually close in the
STANDBY position. See Figure 3.3.
If window “B” reads OFF and window “A” reads ON it will be
necessary to trip the ATS to the neutral position. See the TRIP TO
NEUTRAL section.
With handle attached to the actuating shaft. Insert screwdriver
into hole marked “S”. While pushing inward on screwdriver, move
manual handle upward as indicated by arrow in illustration until it
stops. DO NOT FORCE. Confirm main contacts close to STANDBY
source when window “B” is ON and window “A” is OFF. Remove
handle from switch.
Figure 3.3 — Closure to Emergency Source Side
CLOSURE TO EMERGENCY SOURCE SIDE
3.2.3 CLOSE TO NORMAL SOURCE SIDE
Before proceeding, verify the position of the switch by observing
window “A” and window “B”. If window “A” reads ON the ATS is
closed in the UTILITY position, with the LOAD connected to the
NORMAL source. It is not necessary to manually close in the
UTILITY position. See Figure 3.4.
If window “A” reads OFF and window “B” reads ON it will be
necessary to trip the ATS to the neutral position. See the TRIP TO
NEUTRAL section.
With handle attached to the actuating shaft. Move manual handle
upward as indicated by arrow in illustration until it stops. DO NOT
FORCE. Confirm main contacts close to UTILITY source when
window “A” is ON and window “B” is OFF. Remove handle from
switch.
Figure 3.4 — Closure to Normal Source Side
3.3 VOLTAGE CHECKS
3.3.1 UTILITY VOLTAGE CHECKS
1. Turn ON the UTILITY power supply to the transfer switch with
whatever means provided (such as the UTILITY maim line
circuit breaker).

PROCEED WITH CAUTION. THE TRANSFER
SWITCH IS NOW ELECTRICALLY HOT.
CONTACT WITH LIVE TERMINALS RESULTS
IN EXTREMELY HAZARDOUS AND POSSIBLY
FATAL ELECTRICAL SHOCK.
2. With an accurate AC voltmeter, check for correct voltage.
Single-phase utility supply:
Measure across ATS terminal lugs N1 and N2; N1 to NEUTRAL
and N2 to NEUTRAL.
Three-phase utility supply:
Measure across ATS terminal lugs N1 to N2, N2 to N3, and
N1 to N3.
Measure across ATS terminal lugs N1 to NEUTRAL, N2 to
NEUTRAL, and N3 to NEUTRAL.
Operation
7
3. Three-phase only. Locate the 3 phase power monitor relay.
Verify the following:
LED Green and ON (For an explanation of all of the LED func-
tions, see the decal on the side of the power monitor.)
The factory setting is 80% of nominal voltage (208 Vac sys-
tems = 166 Vac dropout)
4. If the LED indicator is Red or not ON, then it will be necessary
to adjust the power monitor relay setting. Rotate the adjust-
ment potentiometer in a counter-clockwise direction until the
LED turns ON. At this point the 3 phase power monitor relay
is the most sensitive to irregular power line conditions.
NOTE:
If the power monitor does not operate properly, check that all
three voltages are present, and are of the correct voltage level
and phase rotation. To change phase rotation, turn off the utility
supply, interchange 2 of the utility power phases.

FAILURE TO TURN OFF THE UTILITY SUP-
PLY BEFORE WORKING ON THE UTILITY
CONNECTIONS OF THE ATS WILL RESULT
IN EXTREMELY DANGEROUS AND POSSIBLY
FATAL ELECTRICAL SHOCK.
5. When certain that UTILITY supply voltage is correct and
compatible with transfer switch ratings, turn OFF the UTILITY
supply to the transfer switch.
3.3.2 GENERATOR VOLTAGE CHECKS
1. On the generator panel, set the AUTO/OFF/MANUAL switch to
MANUAL position. The generator should crank and start.
2. Let the generator stabilize and warm up at no-load for at least
five minutes.
3. Set the generator's main circuit breaker (CB1) to its ON or
CLOSED position.

PROCEED WITH CAUTION. GENERATOR
OUTPUT VOLTAGE IS NOW BEING
DELIVERED TO TRANSFER SWITCH
TERMINALS. CONTACT WITH LIVE
TERMINALS RESULTS IN EXTREMELY
DANGEROUS AND POSSIBLY FATAL
ELECTRICAL SHOCK.
4. With an accurate AC voltmeter and frequency meter, check the
no-load, voltage and frequency.
Single-phase generator supply:
Measure across ATS terminal lugs E1 to E2; E1 to NEUTRAL
and E2 to NEUTRAL.
a. Frequency ....................................................60-62 Hz
b. Terminals E1 to E2 .......................................240-246 VAC
c. Terminals E1 to NEUTRAL ............................120-123 VAC
d. Terminals E2 to NEUTRAL ............................120-123 VAC
Three-phase generator supply:
Measure across ATS terminal lugs E1 to E2, E2 to E3 and E1
to E3.
Measure across ATS terminal lugs E1 to NEUTRAL, E2 to
NEUTRAL and E3 to NEUTRAL.
a. Frequency ....................................................60-62 Hz
b. Terminals E1-E2, E2-E3, E1-E3 .................... 208-212VAC, 235-
245VAC or 470-
485VAC
c. Terminals E1-N, E2-N, E3-N ......................... 120-122VAC, 136-
140VAC or 272-
282VAC
It will also be necessary to verify that the phase rotation of the util-
ity matches the phase rotation of the generator. This can be done
by using a phase rotation indicator.
Failure to do so may result in damage to cer-
tain rotary equipment.
5. When certain that UTILITY supply voltage is correct and
compatible with transfer switch ratings, turn OFF the UTILITY
supply to the transfer switch.
6. Set the generator’s main circuit breaker (CB1) to its OFF or
OPEN position.
7. Set the Auto/Off/Manual switch to the OFF position to shut
down the generator.
NOTE:
Do NOT proceed until generator AC output voltage and frequen-
cy are correct and within stated limits. If the no-load voltage is
correct but no-load frequency is incorrect, the engine governed
speed probably requires adjustment. If no-load frequency is
correct but voltage is not, the voltage regulator may require
adjustment.
Operation
8
3.4 GENERATOR TESTS UNDER
LOAD
1. Set the generator's main circuit breaker to its OFF or OPEN
position.
2. Manually actuate the transfer switch main contacts to their
emergency (Standby) position. Refer to “Manual Operation”.
3. To start the generator, set the AUTO/OFF/MANUAL switch to
MANUAL. When engine starts, let it stabilize for a few min-
utes.
4. Turn the generator's main circuit breaker to the ON or CLOSED
position. The generator now powers all LOAD circuits. Check
generator operation under load as follows:
Turn ON electrical loads to the full rated wattage/amper-
age capacity of the generator. DO NOT OVERLOAD.
With maximum rated load applied, check voltage and
frequency across transfer switch terminals E1 and E2.
Voltage should be greater than 200 volts (208VAC sys-
tem) or 230 volts (240VAC system); frequency should be
greater than 59 Hz.
Let the generator run under rated load for at least 30 min-
utes. With unit running, listen for unusual noises, vibra-
tion, overheating, etc., that might indicate a problem.
5. When checkout under load is complete, set main circuit
breaker of the generator to the OFF or OPEN position.
6. Let the generator run at no-load for several
minutes. Then, shut down by setting the AUTO/OFF/MANUAL
switch to its OFF position.
7. Move the transfer switch's main contacts back to the
UTILITY position. For example, load connected to utility power
supply. Refer to “Manual Operation”. Handle and operating
lever of transfer switch should be in down position.
8. Turn on the utility power supply to transfer switch, using
whatever means provided (such as a utility main line circuit
breaker). The utility power source now powers the loads.
9. Set the generator's AUTO/OFF/MANUAL switch to its AUTO
position. The system is now set for fully automatic opera-
tion.
Operation
9
QT SERIES ENGINE GENERATOR
CONNECTION PANEL
LIQUID COOLED INSTALLATION
RTS TRANSFER SWITCH
UTILITY SUPPLY FROM
SERVICE DISCONNECT
CUSTOMER LOAD
(DISTRIBUTION PANEL)
800A-3 PHASE SHOWN
3 PHASE
SINGLE PHASE
NOTE:
N3, E3 AND T3 WIRES ARE ONLY
USED ON 3 PHASE SYSTEMS.
NEUTRAL BLOCK
GROUND
194
23
N1
N2
E1 E2
NOTE:
MATCH WIRE
TERMINAL NUMBERS
NUMBERS TO
ON
N1
N2
T1/LINE
NEU
178
183
23
194
N1 N2 (N3)
NEUTRAL
GROUND
BLOCK
(T3)T1 T2
(E3)E1 E2
(E3)
CUSTOMER
CONTROL
WIRING SUPPORT
194
23
N1
N2
67210X
063925-T
063925-T
063925-T
063925-T063925-T
063925-T063925-T
063925-T 063925-T
E1 E2
NOTE: INSTALLATION TO BE DONE BY A
LICENSED ELECTRICIAN AND MUST
MEET ALL NATIONAL, STATE AND
LOCAL ELECTRICAL CODES.
0D2907-T
M4X10STUD-T
0D2907-T
M4X10STUD-T
0D2907-T
M4X10STUD-T
0D2907-T
M4X10STUD-T
M8X35 PEM STUD
0F7808-T
M8X35 PEM STUD
0F7808-T
M8X35 PEM STUD
0F7808-T
M8X35 PEM STUD
0F7808-T
WS16-0F
0D2905-S
M5X12STUD
0D2905-S
M5X12STUD
0D2905-S
M5X12STUD
0H3797B-S
0F7807B-S
10-32X5/16
0H3797A-F
0F7807B-S
10-32X5/16
0D2908-S
M4X15STUD
0D2907-S
M4X10STUD
0F7806-T
M4 WHIZ
0F7806-T
M4 WHIZ
0F7806-T
M4 WHIZ
050299E-S
M6X20
0C8112A-S
3/8X16
0F7807C-S
0F7807B-S
10-32X5/16
0H3797A-F
0F7807B-S
10-32X5/16
0H3797B-S
3/8-16 LH
64101-S
3/8X16
0F7807C-S
050299E-S
0H3797B-S
0H3797A-F
0D2908-S
M4X15STUD
0H3797A-F
0F7807B-S
10-32X5/16
0F7807B-S
10-32X5/16
10-32X5/16
0F7807B-S
10-32X5/16
0F7807B-S
0A9457X
050299E-S050299E-S 050299E-S
050299E-S050299E-S050299E-S
050299E-S050299E-S 050299E-S
050299E-S050299E-S050299E-S
0D2905-S
M5X12STUD
0D2905-S
M5X12STUD
0D2905-S
M5X12STUD
0D2905-S
M5X12STUD
0D2905-S
M5X12STUD
0D2908-S
M4X15STUD
0D2907-S
M4X10STUD
0D2907-S
M4X10STUD
0D2907-S
M4X10STUD
0F7808-S
M8X35 PEM STUD
0F7808-S
M8X35 PEM STUD
0F7808-S
M8X35 PEM STUD
0H3797A-SH
0H3797A-SH
0H3797A-SH
3/8 x 2
49572-S
3/8 x 2
49572-S
H4
X4
240V
H1
480V
X1
480/240V 200VA
64126-T
SNC P17001
48850-T
NOTE WIRE ORIENTATION
P/N 0C2262
WARNING
CUSTOMER CONNECTIONS
N2
N1
WIRE
(240 VAC)
(240 VAC)
WIRE
194
23
(12 VDC)
WIRE
(12 VDC)
WIRE
H4
X4
240V
H1
480V
X1
480/240V 200VA
64126-T
SNC P17001
8127
35
4
6
LEFT INSIDE VIEW
FRONT VIEW
A7822-T
600MCM
0D6584-T
A7822-T
600MCM
A7822-T
600MCM
0D6584-S
1/4 STL
22097-S
1/4-20 x 3/4
22287-S
600MCM
A7822-S
M6
049811
BT2
BT2
TRANSFER SWITCH
RATED CURRENT
XXXXXX
72112
RATED VOLTAGE
600 VAC CSA
480 VAC UL
800 AMP
TRIP
SELECT
MANUAL OPERATION
THE "SELECT" WITH A SCREWDRIVER.
IN THE DIRECTION WHILE PUSHING
DO NOT OPERATE WHILE THE SWITCH IS UNDER LOAD.
OPERATE IN THE DIRECTION
SET MANUAL HANDLE ON "M" AND OPERATE
PUSH THE "TRIP" WITH A SCREWDRIVER.
SET MANUAL HANDLE ON "M" AND
ST
M
CLOSE STANDBY
CLOSE UTILITY
TRIP OPEN
A2A1 B1
A2A1 B1 AT1
AT1B2
B2
AT2 BT1
AT2 BT1
STANDBY
B
UTILITY
A
091472-17T
WIRE DUCT 1.25X1.5X17"
30A, 600V
D2806-T
30A, 600V
D2806-T
30A, 600V
D2806-T
0E5820-F
POTTER & BRUMFIELD
KUP-11A55-24
24V 50/60 Hz
1/3HP, 120VAC
10A, 240VAC
MADE IN MEXICO
Drawing No. 0J0911-C Interconnection Diagram
10
Installation Diagram Drawing No. 0J0915-A
11
Drawing No. 0J0915-A Installation Diagram
12
Notes
12
13
Notes
13
Part No. 0J0917 Revision C (08/06/13) Printed in U.S.A.
1 0J0901 1 E NCL NEMA 3R 36 X 60 X 20 RTS
2 0F6521 1 DECAL RTS T RANSFER SW NE MA 3R
3 095282 1 DECAL LI VE CIRCUIT
4 0E8594 1 DECAL E NCLOSURE NOTE NE MA 3R
5 0G1484 1 DECAL U L CTRL P ANEL ENCL
6 0J0925 1 DECAL RTS TEST SEQUE NCE 600A
0J0926 1 DECAL RTS TEST SEQUE NCE 800A
7 0536210193 1 ASS Y WIRE #0 12. 00" (GROUND WIRE)
8 072164 1 MNL HNDL 6-1600A WN (SUPP LIE D W/ S WITCH)
9 074525 1 DECAL MANUAL OPE RATION
10 072111 1 X FRS W 600A 3P WN600V
072112 1 X FRS W 800A 3P WN600V
11 080433 9 LUG SL DLS S 500- #1X13/32 AL/CU
063925 9 LUG SL DLS S 500- 4/0X17/32 AL/CU
12 074349A 2 S W CV R WN 600A 3P
074349C 2 S W CV R WN 800/1000A 3P
13 074351 2 CVR BKRT 600-1600A RH
14 074351A 2 CVR BKR T 600-1600A LH
15 063986 4 KNOB, COV ER HOLD-DOWN
16 0C8308 2 DECAL TERMINA L SHOCK HAZARD
17 064510 1 DECAL TERMINAL NOTE
18 0D8700 1 ASSY NEUTRAL BL K 600-1000A ATS
19 0A9457 1 DECAL NEUTRAL
20 0D6584 1 ASSY GRD. TERM . 600-2600A
21 067210A 1 DECAL GROUND LUG
22 0J09080ST14 1 S UB-PLATE RTS 600-800A
23 0J2328$ 1 P LATE DATA - RTS
24 * 063617 1 RELAY PNL 12VDC DP DT 10A@240VA
25 * 0D2806 RE F. FUSEBLOCK 30A 600V 2 POS W/S Q
26 073590A RE F. FUSE 5A X BUSS
27 * 048850 1 BLCK T ERM 20A 5 X 6 X 1100V
28 0C2282 1 DECAL TERMINA L STRIP
29 063306 RE F. P OWER MONITOR 3-P H 208-480V
30 * 0F6760 1 S OCKET RE LAY 8P 600V-10A
31 064126 RE F. TRANSF RM 240/ 480V-120/ 240V
32 054199 1 DECAL D ANGER HIGH VOL TAGE
33 091472 1 DUCT WI RI NG 1 X 1. 5 (33 LG)
34 091472A 1 COVER WI RE DUCT 1 IN (33LG)
35 0F6685 4 TI E-WRAP M OUNT(FIR TREE SYTLE)
36 0E4415G 1 DECAL, FUSE RAT ING 5A 600V
37 * 0J0918 1 WIRE HARNE SS RTS 1 P HASE
0J0919 1 WIRE HARNE SS RTS 3 P HASE
0J0920 1 WIRE HARNE SS RTS K V OLTAGE
100 038150 2 WASHER FLAT #8 ZINC
101 022264 2 WASHER LOCK #8-M4
102 051715 2 NUT HEX M4-0. 7 G8 YEL CHR
103 087680 1 NUT WING M 6-1.0
104 0A1661 2 RIVET POP .156 X .675 AL
105 022152 8 WASHER LOCK #10
106 024469 8 SCREW HHTT #10-32 X 3/8 CZ
107 022302 18 WASHER LOCK 7/16
108 026209 18 SCREW HHC 7/16-14 X 1-3/4 G5
109 022509 18 NUT HEX 7/16-14 STEEL
110 026902 7 SCREW HHTT #8-32 X 1/ 4 CZ
111 067989 4 NUT HEX FL WHIZ M8-1. 25
112 042911 6 SCREW HHC M10-1.5 X 30 G8.8
113 046526 6 WASHER LOCK M10
114 022195 9 WASHER LOCK 1/2
115 022196 9 NUT HEX 1/2-13 STEE L
116 023316 9 SCREW HHC 1/2-13 X 4 G5
117 0C2265 REF. SCREW PHTT M4-0.7 X 12 ZP
118 0C2695 REF. SCREW HHTT M 4-0.7 X 20 BP
119 0C2267 8 SCREW HHTT M 5-0.8 X 12 BP
120 091477 2 RIV ET WIRE DU CT MNT
* DESIGNATES ITEMS ST RUCTURED I N WI RE HARNESS
(NOT S HOWN)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30

Generac 120/208V, 800A RTSN800G3 User manual

Type
User manual

The Generac 120/208V, 800A RTSN800G3 automatic transfer switch is designed to seamlessly transition your critical electrical loads from utility power to generator power during outages. With its impressive 800 amp rating, it can handle the power needs of large homes or small businesses. Installation is simplified with clear instructions and diagrams provided in the owner's manual, ensuring a safe and proper setup. Once installed, the transfer switch will automatically monitor your utility power and switch to generator power within seconds of an outage.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI