MQ Multiquip GA4.5R User manual

Category
Power generators
Type
User manual

This manual is also suitable for

OPERATION AND PARTS MANUAL
MODEL GA4.5R/GA4.5RA
PORTABLE AC GENERATOR
(ROBIN GASOLINE ENGINE)
Revision #1 (11/27/06)
THIS MANUAL MUST ACCOMPANY
THE EQUIPMENT AT ALL TIMES.
PAGE 2 — GA-4.5R/GA-4.5RA A.C. GENERATOR— OPERATION & PARTS MANUAL — REV. #1 (11/27/06)
GA-4.5R/GA-4.5RA A.C. GENERATOR — OPERATION & PARTS MANUAL — REV. #1 (11/27/06) — PAGE 3
NOTE PAGE
PAGE 4 — GA-4.5R/GA-4.5RA A.C. GENERATOR— OPERATION & PARTS MANUAL — REV. #1 (11/27/06)
TABLE OF CONTENTS
Specification and part
number are subject to change
without notice.
ROBIN
EX270D
Engine
(EPA)
Crankcase Assembly .........................................48-49
Crankshaft and Piston Assembly .......................50-51
Governor Assembly ........................................... 52-53
Intake and Exhaust Assembly ............................ 54-55
Muffler Assembly ...............................................56-57
Air Cleaner Assembly.........................................58-59
Recoil Starter Assembly.....................................60-61
Carburetor Assembly .........................................62-63
Flywheel Assembly ............................................64-65
Terms and Conditions Of Sale — Parts .................. 66
NOTE
NOTE
As a continuing effort to
update our parts book, contact
the MQ literature department
for the latest revision of your
"Operation and Parts Manual"
Generator Component
Drawings
Nameplate and Decals....................................... 38-39
Generator Assembly .......................................... 40-41
Control Box Assembly (GA-4.5R) ...................... 42-43
Control Box Assembly (GA-4.5RA) .................... 44-45
Pipe Frame Assembly ........................................ 46-47
GA-4.5R/GA-4.5RA — AC
Portable Generators
California Proposition 65 Warning ............................. 3
Table Of Contents ..................................................... 4
Parts Ordering Procedures ....................................... 5
Safety Alert Message Symbols .............................. 6-7
Rules for Safe Operation ..................................... 8-10
Specifications .......................................................... 11
Dimensions ............................................................. 12
General Information ................................................ 13
Load Application ..................................................... 14
Controls and Indicators ...................................... 15-17
Generator Refueling ............................................... 18
Installation .......................................................... 19-20
Pre-Inspection ......................................................... 21
Pre-Inspection (Engine) .......................................... 22
Initial Start-up (Engine) ........................................... 23
Initial Start-up (Engine/Operation) ..................... 24-25
Preparation For Long Term Storage ....................... 26
Maintenance ...................................................... 27-28
Wiring Diagram (GA-4.5R) ...................................... 30
Wiring Diagram (GA-4.5RA) ................................... 31
Troubleshooting (Engine) ................................... 32-33
Troubleshooting (Generator) .................................. 34
Explanation Of Codes In Remarks Column ............ 36
Suggested Spare Parts ........................................... 37
GA-4.5R/GA-4.5RA A.C. GENERATOR — OPERATION & PARTS MANUAL — REV. #1 (11/27/06) — PAGE 5
PARTS ORDERING PROCEDURES
www.multiquip.com
Ordering parts has never been easier!
Choose from three easy options:
WE ACCEPT ALL MAJOR CREDIT CARDS!
When ordering parts, please supply:
Dealer Account Number
Dealer Name and Address
Shipping Address (if different than billing address)
Return Fax Number
Applicable Model Number
Quantity, Part Number and Description of Each Part
Specify Preferred Method of Shipment:
Fed Ex/UPS
DHL
Priority One
Tr u ck
Ground
Next Day
Second/Third Day
Unless otherwise indicated by customer, all orders are treated as
Standard Orders
and will ship
within 24 hours. We will make every effort to ship
Air Shipments
the same day the order is received,
if received prior to 2PM PST.
Stock Orders
must be noted on fax or web order form.
If you have an MQ Account, to obtain a
Username and Password, E-mail us at:
To obtain an MQ Account, contact your
District Sales Manager for more information.
Order via Internet (Dealers Only):
Order parts on-line using Multiquip’s SmartEquip website!
View Parts Diagrams
Order Parts
Print Specification Information
Note: Discounts Are Subject To Change
Goto www.multiquip.com and click on
Order Parts
to log in and save!
Use the
internet
and qualify for a 5% Discount
on
Standard orders
for all orders which include
complete part numbers.*
Order via Fax (Dealers Only):
All customers are welcome to order parts via Fax.
Domestic (US) Customers dial:
1-800-6-PARTS-7 (800-672-7877)
Fax
your order in and qualify for a 3% Discount
on
Standard orders
for all orders which include
complete part numbers.*
Order via Phone:
Domestic (US) Dealers Call:
1-800-427-1244
Best Deal!
International Customers
should contact
their local Multiquip Representatives for
Parts Ordering information.
Non-Dealer Customers:
Contact your local Multiquip Dealer for
parts or call 800-427-1244 for help in
locating a dealer near you.
Note: Discounts Are Subject To Change
NOTE
PAGE 6 — GA-4.5R/GA-4.5RA A.C. GENERATOR— OPERATION & PARTS MANUAL — REV. #1 (11/27/06)
GA-4.5R/GA-4.5RA — SAFETY MESSAGE ALERT SYMBOLS
Safety precautions should be followed
at all times when operating this
equipment. Failure to read and
understand the Safety Messages and
Operating Instructions could result in
injury to yourself and others.
FOR YOUR SAFETY AND THE SAFETY OF OTHERS!
This Owner's Manual has been
developed to provide complete
instructions for the safe and efficient
operation of the MQ Model GA-4.5R/
GA-4.5RA
Portable Generators
.
Refer to the engine manufacturers
instructions for data relative to its safe
operation.
NOTE
Lethal Exhaust Gases
Before using this generator, ensure that the operating
individual has read and understands all instructions in this
manual.
SAFETY MESSAGE ALERT SYMBOLS
The three (3) Safety Messages shown below will inform you
about potential hazards that could injure you or others. The
Safety Messages specifically address the level of exposure
to the operator, and are preceded by one of three words:
DANGER, WARNING, or CAUTION.
You WILL be KILLED or SERIOUSLY injured if you
do not follow directions.
You COULD be KILLED or SERIOUSLY injured if
you do not follow directions.
You CAN be injured if you do not follow directions
WARNING
DANGER
CAUTION
Gasoline engine exhaust gases contain
poisonous carbon monoxide. This gas is
colorless and odorless, and can cause
DEATH
if inhaled. NEVER operate this
equipment in a confined area or enclosed structure that
does not provide ample free flow air.
WARNING - LETHAL EXHAUST GASES
Engine components can generate extreme
heat. To prevent burns, DO NOT touch these
areas while the engine is running or
immediately after operations. NEVER
operate the engine with heat shields or heat
guards removed.
WARNING - BURN HAZARDS
During operation of these generators, there
exists the possibility of
electrocution,
electrical shock or burn,
which can cause
severe bodily harm
or even
DEATH!
DANGER - ELECTROCUTION HAZARDS
HAZARD SYMBOLS
Potential hazards associated with the operation of this
equipment will be referenced with "
Hazard Symbols
" which
appear throughout this manual, and will be referenced in
conjunction with Safety "
Message Alert Symbols
".
Gasoline
is extremely flammable, and
its vapors can cause an explosion if
ignited. DO NOT start the engine near
spilled fuel or combustible fluids.
DO NOT fill the fuel tank while the engine
is running or hot.
DO NOT overfill tank, since spilled fuel could ignite if it
comes into contact with hot engine parts or sparks from
the ignition system. Store fuel in approved containers, in
well-ventilated areas and away from sparks and flames.
NEVER use fuel as a cleaning agent.
WARNING - EXPLOSIVE FUEL
GA-4.5R/GA-4.5RA A.C. GENERATOR — OPERATION & PARTS MANUAL — REV. #1 (11/27/06) — PAGE 7
ALWAYS place the Engine ON/OFF
switch in the OFF position and remove
the ignition key when the pump is not in
use.
ALWAYS wear approved
respiratory
protection.
ALWAYS wear approved
eye
and
hearing
protection.
Other important messages are provided throughout this
manual to help prevent damage to your generator, other
property, or the surrounding environment.
This generator, other property,
or the surrounding environment
could be damaged if you do not
follow instructions.
NOTE
NEVER tamper with the factory settings
of the engine governor or settings.
Personal injury and damage to the engine
or equipment can result if operating in
speed ranges above maximum allowable.
CAUTION - OVER-SPEED CONDITIONS
CAUTION - ACCIDENTAL STARTING
CAUTION - RESPIRATORY HAZARDS
CAUTION - SIGHT AND HEARING HAZARDS
CAUTION - EQUIPMENT DAMAGE MESSAGES
NEVER operate equipment with covers,
or guards removed. Keep
fingers
,
hands
,
hair
and clothing away from all moving
parts to prevent injury.
WARNING - ROTATING PARTS
GA-4.5R/GA-4.5RA — SAFETY MESSAGE ALERT SYMBOLS
PAGE 8 — GA-4.5R/GA-4.5RA A.C. GENERATOR— OPERATION & PARTS MANUAL — REV. #1 (11/27/06)
GA-4.5R/GA-4.5RA — RULES FOR SAFE OPERATION
The following safety guidelines should always be used when
operating the GA-4.5R/GA-4.5RA Portable Generators:
GENERAL SAFETY
DO NOT operate or service this
equipment before reading this entire
manual.
This equipment should not be operated by persons under
18 years of age.
NEVER operate this equipment without proper protective
clothing, shatterproof glasses, steel-toed boots and other
protective devices required by the job.
The engine section of this generator requires an adequate
free flow of cooling air.
NEVER
operate the generator in
any enclosed or narrow
area where free flow of the
air is restricted. If the air
flow is restricted it will
cause serious damage to
the generator or engine and
may cause injury to
people. Remember the
generator's engine gives
off
DEADLY
carbon
monoxide gas.
NEVER operate this equipment under the influence of
drugs
or
alcohol
.
NEVER touch the hot exhaust
manifold, muffler or cylinder. Allow
these parts to cool before servicing
engine or generator.
ALWAYS wear proper respiratory (mask),
hearing and eye protection equipment when
operating the generator.
Whenever necessary, replace nameplate, operation and
safety decals when they become difficult read.
Manufacturer does not assume responsibility for any
accident due to equipment modifications.
NEVER use accessories or attachments, which are not
recommended by Multiquip for this equipment. Damage
to the equipment and/or injury to user may result.
NEVER operate this equipment when not
feeling well due to fatigue, illness or taking
medicine.
ALWAYS refuel in a well-ventilated area, away from sparks
and open flames.
ALWAYS use extreme caution when
working with flammable liquids. When
refueling, stop the engine and allow it to
cool. DO NOT
smoke
around or near the
machine. Fire or explosion could result
from fuel vapors, or if fuel is spilled on a
hot engine.
NEVER operate the generator in an
explosive atmosphere or near
combustible materials. An explosion or
fire could result causing severe
bodily
harm or even death.
NEVER disconnect any
"emergency or safety devices"
.
These devices are intended for operator safety. Disconnection
of these devices can cause severe injury, bodily harm or even
death! Disconnection of any of these devices will void all
warranties.
Failure to follow instructions in this manual may lead to
serious injury
or even
DEATH
! This equipment is to be
operated by trained and qualified personnel only! This
equipment is for industrial use only.
DANGER - READ THIS MANUAL!
GA-4.5R/GA-4.5RA A.C. GENERATOR — OPERATION & PARTS MANUAL — REV. #1 (11/27/06) — PAGE 9
GA-4.5R/GA-4.5RA — RULES FOR SAFE OPERATION
ALWAYS be sure the operator is familiar with proper safety
precautions and operation techniques before using generator.
NEVER leave the generator unattended, turn off engine when
unattended.
Unauthorized equipment modifications will void all
warranties.
ALWAYS ensure generator is on level ground before use.
DO NOT place hands or fingers inside generator engine
compartment when engine is running.
NEVER run engine without air cleaner. Severe engine damage
may occur.
NEVER change or adjust the engine speed which has been
set at the factory prior to shipping.
Removing the engine oil drain plug while
the engine is hot will result in hot oil to gush
out of the oil drain plug, therefore causing
severe scalding to any persons in the general
area of the generator.
Power Cord Safety
NEVER let power cables or cords
lay in wate
r.
NEVER
stand in water
while AC power from the generator
is being transfer to a load.
NEVER use a defective or frayed power cable. Check the
cable for cuts in the insulation.
NEVER use a extension cord that is frayed or damaged where
the insulation has been cut.
ALWAYS make certain that proper power or extension cord
has been selected for the job See Table 3.
Grounding Safety
ALWAYS make sure that electrical circuits are properly
grounded
per the
National Electrical Code
(NEC) and
local codes before operating generator. Severe
injury
or
death!
by electrocution can result from operating an
ungrounded generator.
ALWAYS make sure generator is properly grounded to a
suitable earth ground (GROUND ROD). See installation
section in this manual.
NEVER use
gas piping
as an electrical ground.
Maintenance Safety
NEVER lubricate components or attempt service on a running
machine.
High Temperatures – Always stop engine and
allow the engine to cool before adding fuel, oil
or performing service and maintenance
functions. Contact with
hot!
components can
cause serious burns.
Keep the machinery in proper running condition.
Fix damage to the machine immediately and replace any
broken parts immediately.
ALWAYS replace any worn or damaged warning decals.
ALWAYS store equipment properly when it is not being used.
Equipment should be stored in a clean, dry location out of the
reach of children and un-authorized personnel.
The electrical voltage required to operate the generator can
cause severe injury or even death through physical contact
with live circuits.
Turn all circuit breakers OFF before
performing maintenance on the generator.
Dispose of hazardous waste properly. Examples of potentially
hazardous waste are used motor oil, fuel and fuel filters.
DO NOT use food or plastic containers to dispose of
hazardous waste.
DO NOT pour waste, oil or fuel directly onto the ground,
down a drain or into any water source.
PAGE 10 — GA-4.5R/GA-4.5RA A.C. GENERATOR— OPERATION & PARTS MANUAL — REV. #1 (11/27/06)
GA-4.5R/GA-4.5RA — RULES FOR SAFE OPERATION
Backfeed to a utility system can cause
electrocution
and or property damage.
NEVER connect the generator to a
building's electrical system without a
transfer switch or other approved device.
All installations should be performed by
a
licensed electrician
in accordance
with all applicable laws and electrical
codes. Failure to do so could result in
electrical shock or burn causing serious
injury or even death!
Emergencies
ALWAYS know the location of the
nearest
fire extinguisher
.
ALWAYS know the location of the nearest
first aid kit
.
In emergencies
always
know the location of the
nearest phone or
keep a phone on the job site
.
Also know the phone numbers of the nearest
ambulance
,
doctor
and
fire department
. This
information will be invaluable in the case of an
emergency.
DANGERDANGER
DANGERDANGER
DANGER
-
ELECTROCUTION HAZARDSELECTROCUTION HAZARDS
ELECTROCUTION HAZARDSELECTROCUTION HAZARDS
ELECTROCUTION HAZARDS
During operation of this generation, there
exists the possibility of
electrocution
,
electrical shock or burn
, which can
cause
severe bodily harm
or even
DEATH!
To avoid these hazards:
NEVER use
damaged
or
worn
cables when connecting
equipment to the generator. Make sure power connecting
cables are securely connected to the generator’s output
receptacles, incorrect connections may cause damage
to the generator and electrical shock.
NEVER insert any objects into
the output receptacles during
operation. This is extremely
dangerous. ALWAYS turn-off
the generator and place all circuit breakers in the “OFF
position when contact with the output receptacles is
required. There exist the possibility of
electrocution,
electrical shock or burn, which can cause severe
bodily harm or even death
!
NEVER grab or touch a live
power cord with wet hands, the
possibility exist of electrical
shock, electrocution, and even
death!
GA-4.5R/GA-4.5RA A.C. GENERATOR — OPERATION & PARTS MANUAL — REV. #1 (11/27/06) — PAGE 11
Effects of Altitude and Heat
The maximum output of the engine listed above is applicable to supplying electrical power for continuous service at ambient
conditions in accordance with SAE Test cord J607. The above ambient conditions are at standard sea level, with a barometric
reading of 29.92 inches and a temperature of 60 degrees fahrenheit.
Generally, the engine output power will decrease 3 1/2% for each 1000 feet of altitude above sea level, and 1% for each 10
°°
°°
°
F
fahrenheit above the standard temperature of 60
°°
°°
°
F
GA-4.5R/GA-4.5RA — SPECIFICATIONS
snoitacificepS.1elbaT
LEDOMAR5.4-AG/R5.4-AG
ROTARENEG
epyT dleiFgnivloveRepyTsselhsurB,eloP-2
)zH(ycneuqerF06
)Wk(tuptuOsuounitnoC07.3
)Wk(tuptuOmumixaM5
.4
)CAV(segatloV042/021
CAV021spmAsuounitnoC/xaM8.03/5.73
CAV042spmAsuounitnoC/xaM4.51/57.81
)MPR(deepSdetaR0
063
rotcaFrewoP0.1
)mm(.ni)HxWxL(noisnemiD
52.02X5.81X32
)515X074X595(
)gk(.sblthgieWteNyrD
enignEsedulcnI
)86(941
ENIGNE
)noitacificepSenignE(ledoM
)R5.4-AG(01102DO72XENIBOR
)AR5.4-AG(02202DO72XENIBOR
epyT
daehrevO,
rednilyCelgniS,ekorts-4,delooc-riA
enignEenilosaG,tfahsmaC
)cc(tnemecalpsiD562
)nim/Wk(tuptuOsuounitnoC006
3@1.5
)nim/Wk(tuptuOmumixaM0004@0.9
)L(.laGyticapaCknaTleuF)91(2.4
leuF enilosaGelibomotuAdedael-noN
)L(.stQ
yticapaCliOebuL)1.1(61.1
dohteMlortnoCdeepS epyTthgiew-ylFlagufirtneC
dohteMgnitratStratSlioceR
)mm(.ni)HxW
xL(noisnemiD
41.61X5.61X79.31
)014X024X553(
)gk(.sblthgieWteNyrD)12(3.64
PAGE 12 — GA-4.5R/GA-4.5RA A.C. GENERATOR— OPERATION & PARTS MANUAL — REV. #1 (11/27/06)
Figure 1. Dimensions
GA-4.5R/GA-4.5RA — DIMENSIONS
GA-4.5R/GA-4.5RA A.C. GENERATOR — OPERATION & PARTS MANUAL — REV. #1 (11/27/06) — PAGE 13
GA-4.5R/GA-4.5RA — GENERAL INFORMATION
GA-4.5R/GA-4.5RA Familarization
General Inspection Prior to Operation
This generator has been thoroughly inspected and accepted
prior to shipment from the factory. However, be sure to check
for damaged parts or components, or loose nuts and bolts,
which could have become disloged in transit.
The
MQ Model GA-4.5R
and
GA-4.5RA
generators have been
designed as a portable lightweight power source for 60 Hz
(single-phase) vibrators, lighting facilities, power tools,
submersible pumps and other industrial and construction
machinery.
These generators are powered by a 9.0 HP ROBIN air-cooled
gasoline engine. The alternator, a brushless revolving-field
type, is permanently aligned to the engine through rigid
coupling.
These generators are mounted on rubber vibration isolators
that have a steel base backplate which is attached to the
protective steel pipe carrying frame. The protective carrying
frame is made of steel tubing and fully wraps around the
generator to protect against damage.
This portable generator is supplied with a electrical
control
panel
. The control panel includes items as listed below.
Control Panel
The generator control panel has the following componets:
NEMA 5-20R GFCI duplex receptacle, (120V, 20 amps),
GA-4.5RA has two.
NEMA L5-20R, twist-lock receptacle, (125V, 20 amps)
NEMA L5-30R, twist-lock receptacle, (125V, 30 amps)
NEMA L14-20R , twist-lock receptacle, (125/250V, 20 amps)
Circuit Breaker, 2-pole, 15 amps
AC Voltmeter
Operation Switch
Idle Control Switch
Full Power Switch
Excitation System
The GA-4.5R/GA-4.5RA generator uses a magnet attached
to a flywheel to produce AC voltage from a lamp coil beneath
the flywheel. As the magnet passes the coil it produces
approximately 19-22 AC volts.
This voltage (19-22 VAC) is then sent to the control box that
contains three rectifying diodes:
z
Excitation (diode 1)
z
Battery (diode 2)
z
Slow Down (diode 3)
The AC voltage will pass through the excitation diode that
converts the voltage to DC power.
This DC power is then sent to the excitation windings housed
within the main windings commonly called the "stator".
This voltage is then transferred into the rotor through
induction. The rotor contains two diodes within it which rectify
the DC voltage and send it out through the main windings,
as AC voltage.
Engine
The four-cycle air-cooled
ROBIN
gasoline engine is designed
to meet every performance requirement of this generator.
Reference Table 1, for engine specifications.
Figures 2A through 2E show the basic controls and
indicators for the GA-4.5R/ GA-4.5RA generators.
NOTE
In keeping with
Multiquip's
policy of constantly
improving its products, the
specifications quoted herein
are subject to change without
prior notice.
Before connecting this generator to any building’s electrical
system, a
licensed
electrician
must install an
isolation
(transfer)
switch
. Serious damage to the building’s
electrical system may occur without this transfer switch.
DANGER - ELECTRICAL SYSTEM HAZARDS
PAGE 14 — GA-4.5R/GA-4.5RA A.C. GENERATOR— OPERATION & PARTS MANUAL — REV. #1 (11/27/06)
Single Phase Load
Always be sure to check the nameplate on the generator
and equipment to insure the wattage, amperage and
frequency requirements are satisfactorily supplied by the
generator for operating the equipment.
Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require 130—
150% more wattage than the rating on the nameplate, as
the wattage is influenced by the efficiency, power factor and
starting system of the equipment.
If wattage is not given on the equipment's
name plate, approximate wattage may be
determined by multiplying nameplate
voltage by the nameplate amperage.
WATTS = VOLTAGE x AMPERAGE
The power factor of this generator is 1.0 See Table 2 below
when connecting loads.
NOTE
GA-4.5R/GA-4.5RA — LOAD APPLICATION
To determine the running wattage for your load, multiply
the running wattage as indicated by steps 1, 2, and 3 below:
1. INCANDESCENT LOADS
Lights, heaters and similar appliances.
Total the running wattage and multiply by 1.
Example:
29 light bulbs @ 100W each = 2.9 KW
use a 3 KW generator.
2. SMALL MOTORS
Drills and other small power tools.
Total the running wattage and multiply by 2.
Example:
A 1 inch drill runs at 1 KW
use a 2 KW generator.
3. LARGE MOTORS
Submersible pumps, table saws etc.
Total the running wattage and multiply by 3.
Example:
A conveyor belt runs at 8 KW
use a 24 KW generator.
NOTE
When using a combination of dual
receptacles, total load
should not
exceed
the rated capacity of the
generator.
Extension Cables
When electric power is to be provided to various tools or
loads at some
distance
from the generator, extension cords
are normally used.
Cables should be sized to allow for
distance in length and amperage so that the voltage drop
between the generator and point of use (load) is held to
a
minimum
. Use the cable selection chart (Table 3 ) as a
guide for selecting proper cable size.
The idle control device is operated at a
minimum load capacity of 100W. If the
load capacity is less than 100W, place
the idle control switch in the OFF position.
NOTE
daoLyBrotcaFrewoP.2elbaT
daoLfOepyTrotcaFrewoP
srotomnoitcudniesahp-elgniS57.0-4.0
tnecsednacni,sretaehcirtcelE
spmal
0.1
yrucem,spma
ltnecseroulF
spmal
9.0-4.0
,secivedcinortcelE
tnempiuqenoitacinummoc
0.1
slootrewopnommoC8.0
Motors and motor-driven equipment draw much greater
current for starting than during operation.
Always
use an
adequate size
extension cable
which can carry the
required load.
CAUTION - ADEQUATE EXTENSION CABLE
GA-4.5R/GA-4.5RA A.C. GENERATOR — OPERATION & PARTS MANUAL — REV. #1 (11/27/06) — PAGE 15
GA-4.5R/GA-4.5RA — CONTROLS AND INDICATORS
Figure 2A. Generator Controls and Components
1. Lifting Bail Eye – Attach a rope or chain to this lifting eye
when lifting of the generator is required. Never stand
underneath the generator while it is being lifted. Place lifting
eye in down position when not in use.
2. AC-Voltmeter – This voltmeter indicates (with a mark) the
rated 60 Hz, single phase output voltage. In addition the
voltmeter can also be used as a diagnostic tool. If the
voltmeter indicator (needle) is below the rated voltage,
engine problems may exist (low/high RPM's). To prevent
damage to the generator or power tools turn the generator
OFF and consult your authorized MQ service dealer.
3. Idle Control Switch – This unit is provided with an
automatic idle control for noise suppression and reduced
fuel consumption. The automatic idle control automatically
engages under a no-load condition. With the automatic
idle control switched “ON”, the engine revolutions will
automatically drop to about 2600 rpm (low-speed
operation) within 3 seconds after the load stops. When the
operation is resumed, the engine speed is automatically
increased to about 3600 rpm (high-speed operation) as
soon as the load is connected.
4. Operation Switch – Place this
rocker
switch in the "RUN"
position (up) for normal operation. To turn-off the generator
place this switch in the "STOP" position (down).
5. GFCI Duplex Receptacle – NEMA 5-20R receptacle will
provide 120V, 20 amps. The position of the full power switch
does not effect the voltage output at the receptacle. The
GA-4.5RA has two GFCI receptacles.
6. 120 VAC Receptacle NEMA L5-20R twist-lock
receptacle will provide 120V, 20 amps when the full power
switch is placed in either the 120 or 240 volt position.
7. 120 VAC Receptacle – NEMA L5-30R twist-lock
receptacle will provide 120V when the full power switch is
placed in either the 120 or 240 volt position.
8. 240 VAC Receptacle NEMA L14-20R twist-lock
receptacle will provide 240V when the full power switch is
placed in the 240/120 volt position (down). When the full
power switch is placed in the 120 volt position (up), 120V
will be available.
9. Main Circuit Breaker – 2-pole circuit breaker (240V/18.75
amps or 120V/30.8 amps) protects the generator from short
circuiting or overloading. When starting the generator
always
have the circuit breaker placed in the "OFF"
position.
10. Frame Ground – This ground connection point should
be connect to a good earth ground (ground rod).
PAGE 16 — GA-4.5R/GA-4.5RA A.C. GENERATOR— OPERATION & PARTS MANUAL — REV. #1 (11/27/06)
GA-4.5R/GA-4.5RA — CONTROLS AND INDICATORS
Figure 2C. Full Power Switch 120VAC (Up)
Simplified Wiring Diagram
Figure 2D. Full Power Switch 120/240 VAC (Down)
Simplified Wiring Diagram
11. Full Power Switch – The generators are provided with a
full power switch. Figures 2C and 2D show simplified wiring
diagrams of the dual voltage system.
When the full power switch is in the 120 volt (up) position,
you can access the
full rated power
of the generators at
120 volts from the GFCI duplex receptacle and the120V
twist-lock receptacle, or a combination of both receptacles
as long as the total load does not exceed the generating
set capacity.
When the switch is in the 240 volt (down) position, you can
acess
half of the rated power
of the generating set at 120
volts from the GFCI duplex receptacle and up to half of the
rated power of the set at 120 volts from 120V twist-lock
receptacle; or full rated power of the set at 240 volts from
the 240V twist-lock receptacle.
When the
full power switch
is in the
120V position, the 240V twist-lock
receptacle
cannot be used
.
NOTE
Figure 2B. Generator Controls and Components (continued)
GA-4.5R/GA-4.5RA A.C. GENERATOR — OPERATION & PARTS MANUAL — REV. #1 (11/27/06) — PAGE 17
12. Choke Lever – Used for starting the engine.
Close
the
choke lever when starting a cold engine or in cold weather
conditions. The choke enriches the fuel mixture.
Open
the
choke lever if starting a warm engine or in warm weather
conditions.
13. Fuel Cock Lever – Turn this lever
downward
to
start
(down)the flow of fuel to the carburetor. Turn
upward
to
stop (
up
)
the flow of fuel.
14. Throttle Lever – Used to adjust engine RPM speed. This
unit is set at the factory and is not adjustable.
15. Engine – This generator uses a 9.0 HP ROBIN air-
cooled, 4-stroke , single cylinder, overhead camshaft
gasoline engine. Engine uses unleaded fuel.
16. Recoil Starter (Pull Rope) – Used for manual-starting of
the engine. Pull the starter grip until resistance is felt, then
pull briskly and smoothly.
17. Air Cleaner – Prevents dirt and other debris from entering
the fuel system. Remove wing-nut on top of air filter
cannister to gain access to filter element. NEVER run the
engine without an air cleaner.
18. Muffler/Heat Shield – Used to reduce noise and emissions.
NEVER touch this
heat shield
when the generator is in
use. Always allow time for the generator to cool down before
performing maintenance.
19. Oil Dipstick/ Filler Cap– Remove the filler cap dipstick
when checking the engine oil level. Add engine oil through
this filler port. See Table 4 for recommended type engine
oil.
20. Oil Drain Plug – Remove this plug to drain engine oil from
the crankcase.
21. Carburetor Fuel Cup – Inspect the fuel cup weekly for
water and dirt. Clean as referenced in the maintenance
section of this manual.
22. Spark Plug – Provides spark to the ignition system. Set
spark plug gap to 0.6 - 0.7 mm (0.024 - 0.028 inch). Clean
spark plug once a week
23. Generator Housing – Contains the rotor, rectifer field
coil assembly, aramature, bearings and other components
that make up generator asembly.
24. Fuel Gauge – Read this gauge to determine when fuel is
low
.
25. Fuel Gauge/Tank – Remove this cap to add unleaded
gasoline to the fuel tank.
Replenish
with
clean unleaded
gasoline. Make sure cap is tightened securely. DO NOT
over fill. Fuel tank capacity is 5 gallons (19 liters).
GA-4.5R/GA-4.5RA — CONTROLS AND INDICATORS
Figure 2E. Generator Controls and Components (continued)
PAGE 18 — GA-4.5R/GA-4.5RA A.C. GENERATOR— OPERATION & PARTS MANUAL — REV. #1 (11/27/06)
GA-4.5R/GA-4.5RA — GENERATOR REFUELING
Figure 3. Generator Refueling
Adding fuel to the tank should be done only when
the engine is stopped and has had an opportunity
to cool down. In the event of a fuel spill, DO NOT
attempt to start the engine until the fuel residue
has been completely wiped up, and the area
surrounding the engine is dry. If generator is placed
in a truck bed with a plastic liner, REMOVE generator from truck
bed and place on ground (Figure 3) to refuel. This possibility
exist of
fire
or
explosion
due to static electricity.
DANGER - REFUELING HAZARD
GA-4.5R/GA-4.5RA A.C. GENERATOR — OPERATION & PARTS MANUAL — REV. #1 (11/27/06) — PAGE 19
GA-4.5R/GA-4.5RA — INSTALLATION
Outdoor Installation
Install the generator in a area that is free of
debris
,
bystanders
, and
overhead obstructions
. Make sure the
generator is on secure level ground so that it cannot slide
or shift around. Also install the generator in a manner so
that the exhaust will not be discharged in the direction of
nearby homes.
The installation site must be relatively free from moisture
and dust. All electrical equipment should be protected from
excessive moisture. Failure to do will result in deterioration
of the insulation and will result in short circuits and
grounding.
Foreign materials such as dust, sand, lint and abrasive
materials have a tendency to cause excessive wear to
engine and alternator parts.
Indoor Installation
Exhaust gases from gasoline engines are extremely
poisonous. Whenever an engine is installed indoors the
exhaust fumes must be vented to the outside. The engine
should be installed at least two feet from any outside wall.
Using an exhaust pipe which is too long or too small can
cause excessive back pressure which will cause the engine
to heat excessively and possibly burn the valves.
Eliminate the danger of deadly carbon monoxide gas.
Remember that exhaust fumes from any gasoline engine
are very poisonous if discharged in a closed room, but
harmless if allowed to mix with the outside air. If the generator
is installed indoors, you must make provisions for venting
the engine exhaust to the outside of the building.
Generator Grounding
To guard against electrical shock and possible damage to
the equipment, it is important to provide a good EARTH
ground. Always use the ground terminal on the generator to
ground the generator.
Article 250 (Grounding) of the National Electrical Code (NEC)
provides guide lines for proper grounding and specifies that
the cable ground shall be connected to the grounding system
of the building as close to the point of cable entry as
practical.
NEC articles 250-64(b) and 250-66 set the following
grounding requirements:
1. Use one of the following wire types to connect the
generator to earth ground.
a. Copper - 10 AWG (5.3 mm
2
) or larger.
b. Aluminum - 8 AWG (8.4 mm
2
) or larger.
2. When grounding the generator (Figure 4) connect the
ground cable between the lock washer and the nut on
the generator and tighten the nut fully. Connect the other
end of the ground cable to earth ground.
3. NEC article 250-52(c) specifies that the earth ground
rod should be buried a minimum of 8 ft. into the ground.
Mounting
The generator should always be mounted on a flat level
surface to isolate vibration of the generator when it is
running. DO NOT place the generator on slopes, the
possibility exists that the generator could slide.
Pay close attention to ventilation when
operating the generator inside tunnels and
caves. The engine exhaust contains
noxious elements.
WARNING - LETHAL EXHAUST GASES
PAGE 20 — GA-4.5R/GA-4.5RA A.C. GENERATOR— OPERATION & PARTS MANUAL — REV. #1 (11/27/06)
Connecting the Ground
The nut and ground terminal on the generator should always be used to connect the generator to a suitable ground. The
ground cable should be #8 size wire minimum.
At the generator, connect the terminal of the ground cable between the lock washer and the nut (Figure 4) and tighten the
nut fully. Connect the other end of the ground cable to a suitable earth ground (ground rod).
GA-4.5R/GA-4.5RA — INSTALLATION
Figure 4. Generator Grounding
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68

MQ Multiquip GA4.5R User manual

Category
Power generators
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI