meitav-tec FMH24-PMH-IR Product information

Type
Product information
HT
HT
C
R
CL
COM
Heater (230VAC,5A max)
24VAC
Close
23
ON
OFF
o
C
Set
ON
OFF
Date:
Title:
No. Revision Date File name: fmh24-pmh-ir_belimo.vsd
Print name: Drawn: P.Rechtman
Checked: O.Volovitch
Approved: E.Roy
FMH24-PMH-IR
13.02.2008
ERT340P
OUT-FMH24PMH
OP
Common
Open
Fuse 6A
Temperature
limits button
2 Trimmer Removed – IR Added 04.09.2007
IR Receiver
(option)
Technician Settings
Temperature limits for cool and heat
Adjust the set-point temperature to 10˚C.
Press and hold the [Temperature limits] button (15 seconds) – the word “Cool” will flash.
Using the [+] and [-] buttons adjust the temperature limit for cool.
Press the [Temperature limits] button again – the word “Heat” will flash.
Using the [+] and [-] buttons adjust the temperature limit for heat.
Press the [Temperature limits] button again to return to normal display.
Adjust motor (valve) Open/close time
Adjust the set-point temperature to 10˚C.
Press and hold the [Temperature limits] button (30 seconds) – the numbers will flash.
Using the [+] and [-] buttons adjust the Open/Close time (range 10...400 seconds, default
120 seconds). Note that the number on the display will be multiplied by 10.
Examples: 1 10 seconds, 12 120 seconds, 40 400 seconds
Press the [Temperature limits] button again to return to normal display.
Lock / Unlock the buttons
Make sure the set-point temperature IS NOT 10˚C.
Press and hold the [Temperature limits] button (15 seconds) to lock the thermostat buttons -
“LC” will appear on display.
Press and hold the [Temperature limits] button again (15 seconds) to release the buttons -
“LC” will disappear from display.
Software: 08213102
Checksum: 9DA3
3 Added lock function 13.02.2008
meitav-tec
Tel: +972-3-9626462
Fax: +972-3-9626620