8820030 - REV B 9/15 PAGE 1 OF 3
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
AIR
COMPRESSOR
CABINET
NITROGEN
STORAGE TANK
NITROGEN
DEVICE
MAINTENANCE
AIR
AIR
STORAGE TANK
Description
The Potter Nitrogen Generator, NGP-2200D-M5, is specically
designed to provide on-site, high purity nitrogen for use in re
protection sprinkler systems. When used as a supervisory gas in re
sprinkler systems, nitrogen slows corrosion, improves the life of your
system, and lowers maintenance costs. The NGP-2200D-M5 includes
a tank mounted air compressor, nitrogen cabinet, and a nitrogen
storage tank. These systems include all air ltration equipment, an
air compressor, nitrogen membrane, as well as tanks required to keep
the generator operating at peak efciency. Potter Nitrogen Generator
Systems provide a low cost, reliable, and efcient method of producing
a minimum of 98% nitrogen at the point of usage.
The NGP-2200D-M5 utilizes nitrogen membrane technology for
gas separation. Nitrogen membranes are highly effective and a cost
conscious way of producing on-site nitrogen. Acting as a lter, the
smaller oxygen and water vapor molecules can pass through the
membrane quickly. The larger nitrogen molecules are less likely
to diffuse through the separator tubes; therefore, they continue
downstream to the separator outlet, through the air maintenance device
and into the re protection system. As the system lls with nitrogen,
the remaining oxygen molecules in the re protection system are
exhausted by using the Potter IntelliPurge® Nitrogen Purge Valve. The
Potter IntelliPurge® Nitrogen Purge Valve will periodically monitor
the re protection system to ensure high purity nitrogen is consistent
throughout the sprinkler system.
Installation
The Potter NGP-2200D-M5 should be installed in a dry, clean, and
well-ventilated room with ambient temperatures above 50°F at all times.
Allow access to the front of the nitrogen cabinet for service and place the
unit in a location that is conveniently located near re sprinkler system
connections and a drain.
The Potter Nitrogen Generator should always be installed in an
adequately ventilated room. Nitrogen is nontoxic and largely inert.
Rapid release of nitrogen gas into an enclosed space displaces the
oxygen and can cause an asphyxiation hazard. Inhalation of nitrogen
in excessive concentrations can result in unconsciousness without any
warning symptoms.
For detailed installation and operation instructions please refer to the
Potter Nitrogen Generator Manual #5401550.
Technical Specications
Compressor Package Size
(HxWxD) 75” x 34” x 29”
Nitrogen Cabinet Size
(HxWxD) 72” x 30” x 15”
Nitrogen Tank Size (HxØ) 70” x 20”
Compressor Package
Weight 500 lbs
Nitrogen Cabinet Weight 250 lbs
Nitrogen Tank Weight 200 lbs
Power Supply Available in 208V (13.3A), 230V (12.4A), 460V
(6.2A) three phase
Max Operating Pressure 175 PSI
Temperature Range 50ºF (10ºC) to 110ºF (43ºC)
Air Purity
ISO Class 1.4.1 or better: Free of water 38°F (3°C)
Dew Point, compressor oil (0.008 PPM or .01
mg/m3), hydrocarbons, and particles (<0.01 μm
microns)
Features
7.5 HP lubricated air compressor needed for NFPA 13 required 30
minutes ll for 2200 gallon system at 40 PSI
Handles up to 16,000 gallons of total sprinkler system capacity
(based on NFPA 13 allowable leak rates for a new sprinkler system)
Premium nitrogen membrane
UL 508A listed industrial control panel
Built-in Programmable Logic Controller for leak detection and air
bypass alarm systems
Form C dry contacts for Building Management System (BMS)
notication
80 gallon air tank and 80 gallon nitrogen tank
Includes all lters, relief valves, automatic drains and gauges
firealarmresources.com
8820030 - REV B 9/15 PAGE 2 OF 3
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
NGP-2200D-M5
Nitrogen Generator
Fig 1
Fig 2
Cabinet Dimensions
Tank Dimensions
28 3/8 "
AIR TANK
PRESSURE
GAUGE
PS-1 PRESSURE SWITCH
SEPARATOR
CHECK VALVE
AFTERCOOLER
DRAIN CONNECTION
3/8" OD TUBING,
PUSH TO CONNECT
(PIPE TO FLOOR DRAIN)
74 7/8"
39 1/4"
33 3/8"
26 3/8"
80 GALLON
AIR TANK
MOTOR
COMPRESSOR
DRAIN VALVE
1/4" COMPRESSION FITTING,
CONNECT TO DRAIN SOLENOID INLET
ON REAR OF NITROGEN GENERATOR
CABINET.
B
1/2" NPT OUTLET CONNECTION,
FLEX HOSE CONNECTION TO
NITROGEN GENERATOR
CABINET.
A
15"
15"
24"
MOUNTING SLOTS
4 PLCS
.28 X .88
67 1/8"
30"
2"
1/2" COMPRESSION FITTING,
NITROGEN OUTLET, PIPE TO
NITROGEN STORAGE TANK.
C
1/2" COMPRESSION FITTING
AIR INLET, PIPE TO AIR
COMPRESSOR.
A
DRAIN CONNECTION
1/4" OD TUBING,
PUSH TO CONNECT
(PIPE TO FLOOR DRAIN)
DRAIN SOLENOID INLET
PIPE TO AIR TANK.
B
30"
MEMBRANE PRESSURE
GAUGE
NITROGEN TANK
PRESSURE GAUGE
POWER ON LIGHT
NITROGEN SOLENOID
LIGHT
ALARM LIGHT
ALARM HORN
14 1/2"
72"
13 1/8"
PS-2 PRESSURE SWITCH
1/4" COMPRESSION FITTING
PIPE TO NITROGEN STORAGE TANK.
D
1/2" FNPT OXYGEN ENRICHED
PERMEATE OUTLET
(PIPE TO SAFE LOCATION)
1/2" CONDUIT
CONNECTION
2 PLCS
firealarmresources.com
8820030 - REV B 9/15 PAGE 3 OF 3
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
NGP-2200D-M5
Nitrogen Generator
18"
69 7/8"
9 7/8"
ASME SAFETY RELIEF VALVE
NITROGEN TANK
PRESSURE GAUGE
1/4" FNPT VENT
1/4" FNPT BALL VALVE
1/4" COMPRESSION FITTING
CONNECT TO PS-2 PRESSURE SWITCH
ON CABINET.
D
20"
49 1/8"
55 1/8"
13 1/8"
2 1/8"
80 GALLON NITROGEN STORAGE TANK
3/4" FNPT SYSTEM CONNECTION
CONNECT TO AIR MAINTENANCE DEVICE
1/2" FNPT NITROGEN INLET
CONNECT TO NITROGEN OUTLET
ON CABINET.
C
2" FNPT PLUG
45° TYP
6"
TYP
9/16" X 7/8" MOUNTING SLOTS LOCATED
90
APART ON A
17" BOLT
CIRCLE PATTERN
4 PLCS
Fig 3
Storage Tank Dimensions
Model Description Stock No.
NGP-2200D-M5-2B THREE PHASE 208V 1119540
NGP-2200D-M5-3B THREE PHASE 230V 1119541
NGP-2200D-M5-4B THREE PHASE 460V 1119542
Ordering Information
Model Description Stock No.
NGP-MK Maintenance Kit NGP-M2-M5 1119785
INS-PV Potter IntelliPurge® Nitrogen
Purge Valve 1119478
NGP-SPV Potter Purge Valve 1119784
NGP-AMD-1 Potter Air Maintenance Device 1119787
firealarmresources.com
  • Page 1 1
  • Page 2 2
  • Page 3 3

Potter NGP-2200D-M5 Nitrogen Generator Owner's manual

Category
Fire protection
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI