HP AT517A User manual

Category
Rack accessories
Type
User manual

This manual is also suitable for

The new HP Data Center Environmental Edge technology helps you address one of the most critical issues in today's data centers -
power and cooling. HP Data Center Environmental Edge is an affordable approach to monitoring your data center environment,
resulting in optimal use of data center capacity and a reduction in energy costs. HP Data Center Environmental Edge measures,
analyzes and visualizes data center environmental parameters, ensuring complete confidence that you're running a much more
efficient data center.
Why HP Data Center Environmental Edge?
Resiliency: Real-time feedback on environmental changes in your data center through data center environmental visualization
and customer defined alarms
Energy savings: Reduces data center cooling energy up to 18% by enabling customers' data center optimization
Provides insight into data center infrastructure over-provisioning
Supports higher rack operating temperature and chilled water temperature through the data center environmental
measurements
Increased Flexibility: Adapt /upgrade the HP Data Center Environmental Edge hardware and HP Insight Environmental
Observer software to meet the changing needs of your data center
HP Data Center Environmental Edge bridges the gap between IT and facilities. HP Data Center Environmental Edge enables both
facilities and IT manager's deeper insight into their current data center environment.
For additional information, please visit:
www.hp.com/go/edge
HP Data Center Environmental Edge Base Stations
HP Data Center Environmental Edge Base StationsHP Data Center Environmental Edge Base Stations
HP Data Center Environmental Edge Base Stations
1.
Air Pressure Base Station
2.
Environmental Base Station
3.
Base Station Gateway
What's New
What's NewWhat's New
What's New
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Overview
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 1
Data center power visualization, including PUE
Current per phase (Wye only)
Power Factor per phase (Wye only)
Voltage per phase (Wye L-N and Delta L-L)
Total Power
Average Power (period = 5min sampling interval)
THD
Branch circuit monitoring
Current per circuit with breaker capacity and warning status
Power Factor per circuit
Voltage per phase
Chilled water Energy Monitoring
Modbus Gateway
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Overview
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 2
Wireless Network and
Wireless Network andWireless Network and
Wireless Network and
Network and Network
Network and NetworkNetwork and Network
Network and Network
Security
SecuritySecurity
Security
HP Data Center Environmental Edge sensor and networking devices use 802.15.4 based radios that
operate in the 2.4 GHz industrial and scientific and medical (ISM) unlicensed band. The HP Data Center
Environmental Edge wireless communications low bandwidth will not interfere with other wireless
communications. The HP Data Center Environmental Edge wireless communications uses a mesh
network topology to transfer information.
HP Data Center Environmental Edge wireless systems achieve security at multiple levels: First HP Data
Center Environmental Edge wireless communications are not IP-enabled; they therefore are not
susceptible to external IP-based passive and active attacks. Second, HP Data Center Environmental Edge
network stack uses 128bit-AES cryptograph to provide authentication and data encryption, thereby
providing security against rogue admissions and snooping.
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Server
ServerServer
Server
At the centre of the solution is the HP Data Center Environmental Edge Server. This is a HP ProLiant
DL180 G6 running Microsoft Windows Server 2008, HP Insight Environmental Observer software
components.
NOTE:
NOTE:NOTE:
NOTE:
One server can support multiple HP Data Center Environmental Edge data center locations.
HP Insight Environmental
HP Insight EnvironmentalHP Insight Environmental
HP Insight Environmental
Observer S/W
Observer S/WObserver S/W
Observer S/W
HP Insight Environmental Observer S/W key features include: data center environmental visualization;
metrics tracking, alarming and historical information, including 1 year of 24x7 Technical Support and
Updates.
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Environmental Base
Environmental BaseEnvironmental Base
Environmental Base
Station
StationStation
Station
HP Data Center Environmental Edge Environmental Base Stations are attached to individual racks or
CRAH units and collect temperature and humidity data. The HP Data Center Environmental Edge
Environmental Base Station is battery powered and reports temperature and humidity information either
once every minute or up to once every 5 minutes based on user desired preferences. Environmental Base
Stations are simple to mount or attach within the data center environment with a couple of different
Mounting Options techniques, and include a one year parts only warranty (excluding batteries).
Server Racks
Server RacksServer Racks
Server Racks
Environmental Base stations will be combined with the HP Data Center Environmental Edge Rack
Sensor Array
Environmental Base Stations and Rack Sensor Array can be mounted either inside the rack on
outside the rack. The Rack Sensor Array is mounted down the center of both the front and rear of
the rack
The minimum recommended configuration is to install the base stations once every third rack.
Customers can install the base station on every other rack or every rack for increased granularity
of data
CRAH/CRAC (Computer Room Air Handlers / Computer Room Air Conditioning)
CRAH/CRAC (Computer Room Air Handlers / Computer Room Air Conditioning)CRAH/CRAC (Computer Room Air Handlers / Computer Room Air Conditioning)
CRAH/CRAC (Computer Room Air Handlers / Computer Room Air Conditioning)
One Environmental Base Station and the Plenum Rated Sensor Array will be installed in each
CRAH unit
Environmental Base Stations do not require the customers' CRAH/CRAC units to be modified
Other Locations
Other LocationsOther Locations
Other Locations
Environmental Base Stations can be located anywhere that the customers wants to gain insight into
a specific locations' temperature and humidity
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Standard Features
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 3
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge Rack
Environmental Edge RackEnvironmental Edge Rack
Environmental Edge Rack
Sensor Array
Sensor ArraySensor Array
Sensor Array
HP Data Center Environmental Edge Rack Sensor Array contains 3 thermistors to measure rack intake
and 3 thermistors to measure rack exhaust.
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty.
NOTE:
NOTE:NOTE:
NOTE:
Must be combined with AT516A Environmental Base Station
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Plenum Rate Sensor Array
Plenum Rate Sensor ArrayPlenum Rate Sensor Array
Plenum Rate Sensor Array
HP Data Center Environmental Edge Plenum Rated Sensor Array contains 2 plenum rated thermistors
and plenum rated wiring.
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty.
NOTE:
NOTE:NOTE:
NOTE:
Must be combined with AT516A Environmental Base Station
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge Air
Environmental Edge AirEnvironmental Edge Air
Environmental Edge Air
Pressure Base Station
Pressure Base StationPressure Base Station
Pressure Base Station
HP Data Center Environmental Edge Air Pressure Base Station assesses the air pressure differential in
raised floor environments. HP recommends one Air Pressure Base Station per 50 m2 / 500 ft2 of data
center floor space.
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge Base
Environmental Edge BaseEnvironmental Edge Base
Environmental Edge Base
Station Gateway
Station GatewayStation Gateway
Station Gateway
HP Data Center Environmental Edge Base Station Gateway provides the wireless communication with the
HP Data Center Environmental Edge Base Stations and transmits the data to the HP Data Center
Environmental Edge server. HP recommends at least two Base Station Gateways per solution. One Base
Station Gateway pair supports up to 200 base stations. Multiple Base Station Gateway pairs can co-exist
in one data center.
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
NOTE:
NOTE:NOTE:
NOTE:
Regional SKU exists
Recommended Base
Recommended BaseRecommended Base
Recommended Base
Configuration
ConfigurationConfiguration
Configuration
NOTE:
NOTE:NOTE:
NOTE:
The installation of the HP Data Center Environmental Edge recommended base configuration
does not require any data center downtime to implement.
One HP Data Center Environmental Edge Server or server with minimum 4 GB of memory and
250GB of RAID 1 storage
One HP Insight Environmental Observer S/W
One Base Station Gateways per 200 base stations, N+1 configuration
One Environmental Base Station and Plenum Rated Sensor Array per CRAH/CRAC
One Environmental Base Station and Rack Sensor Array per three racks
One Air Pressure Base Station per 500 ft2/50 m2 of data center floor space
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Standard Features
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 4
HP Data Center Environmental Edge Optional Base Stations
HP Data Center Environmental Edge Optional Base StationsHP Data Center Environmental Edge Optional Base Stations
HP Data Center Environmental Edge Optional Base Stations
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Energy Base Station
Energy Base StationEnergy Base Station
Energy Base Station
HP Data Center Environmental Edge Energy Base Station measures kWh (Kilowatt Hours) consumed,
Power, Power Factor, Voltage, Current, THD on each electrical line where installed. Two variants of the
energy meter exist, 208v or 277/480v version with either 200A or 600A split core CTs.
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
NOTE:
NOTE:NOTE:
NOTE:
Energy Base Stations must be installed by a local licensed electrician.
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge 200A
Environmental Edge 200AEnvironmental Edge 200A
Environmental Edge 200A
Current Base Station
Current Base StationCurrent Base Station
Current Base Station
HP Data Center Environmental Edge 200A Current Base Station measures an electrical line true RMS
current from 0 - 200A.
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge Flow
Environmental Edge FlowEnvironmental Edge Flow
Environmental Edge Flow
Meter Base Station
Meter Base StationMeter Base Station
Meter Base Station
HP Data Center Environmental Edge Flow Meter Base Station is a non-intrusive ultrasonic flow meter to
measure chilled water flow.
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Water Leak Detection
Water Leak DetectionWater Leak Detection
Water Leak Detection
Base Station
Base StationBase Station
Base Station
HP Data Center Environmental Edge Water Leak Detection Base Station detects liquid leakage.
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge Rack
Environmental Edge RackEnvironmental Edge Rack
Environmental Edge Rack
Door Position Base
Door Position BaseDoor Position Base
Door Position Base
Station
StationStation
Station
HP Data Center Environmental Edge Rack Door Position Base Station will alarm the customer when the
rack door is accessed.
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge Three
Environmental Edge ThreeEnvironmental Edge Three
Environmental Edge Three
Point Sensor Array
Point Sensor ArrayPoint Sensor Array
Point Sensor Array
HP Data Center Environmental Edge Rack Sensor Array contains 3 thermistors to be place anywhere the
customer wants detailed thermal information
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
NOTE:
NOTE:NOTE:
NOTE:
Must be combined with AT516A Environmental Base Station
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Standard Features
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 5
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Universal Base Station
Universal Base StationUniversal Base Station
Universal Base Station
HP Data Center Environmental Edge Universal Base Station can be attached to any monitoring device
which produces a 4-20mA signal / 0-10v signal.
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
NOTE:
NOTE:NOTE:
NOTE:
This product can only be procured through the HP specials process, please contact your local HP
Pre-sales or EAM.
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Branch Circuit Monitoring
Branch Circuit MonitoringBranch Circuit Monitoring
Branch Circuit Monitoring
Base Station
Base StationBase Station
Base Station
HP Data Center Environmental Edge Branch Circuit Monitoring Base Station comes in up to 208v or
240v, and 42 circuit and 84 circuit wall mount, or 42 circuit sub-floor panels
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
NOTE:
NOTE:NOTE:
NOTE:
BCM Base Stations must be installed by a local licensed electrician.
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Chilled Water Energy
Chilled Water EnergyChilled Water Energy
Chilled Water Energy
Base Station
Base StationBase Station
Base Station
HP Data Center Environmental Edge Chilled Water Energy Base Station measures chilled water flow rate
and temperature of both the supply and return lines
NOTE:
NOTE:NOTE:
NOTE:
One year parts only warranty (excluding batteries).
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Standard Features
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 6
HP Data Center Environmental Edge Configuration
HP Data Center Environmental Edge ConfigurationHP Data Center Environmental Edge Configuration
HP Data Center Environmental Edge Configuration
Step 1: Determine base quantity needed for the base recommended configuration
Step 1: Determine base quantity needed for the base recommended configurationStep 1: Determine base quantity needed for the base recommended configuration
Step 1: Determine base quantity needed for the base recommended configuration
:
One HP Data Center Environmental Edge Server
One HP Insight Environmental Observer S/W
Two HP Base Station Gateways minimum, one per 200 base stations, N+1 configuration
One Environmental Base Station and Plenum Rated Sensor Array per CRAH/CRAC
One Environmental Base Station and Rack Sensor Array per three racks
One Air Pressure Base Station per 500 ft2/50 m2 of data center floor space
One HP Data Center Edge Installer kit per 10,000 ft2/1000 m2
Step 2: Determine extra base stations required for increased granularity
Step 2: Determine extra base stations required for increased granularityStep 2: Determine extra base stations required for increased granularity
Step 2: Determine extra base stations required for increased granularity
Step 3: Determine optional base stations
Step 3: Determine optional base stationsStep 3: Determine optional base stations
Step 3: Determine optional base stations
HP Data Center Environmental Edge Base SKUs
HP Data Center Environmental Edge Base SKUsHP Data Center Environmental Edge Base SKUs
HP Data Center Environmental Edge Base SKUs
Models
ModelsModels
Models
HP Data Center Environmental Edge Server
NOTE:
NOTE:NOTE:
NOTE:
Includes HP ProLiant DL180 G6, 6 GB Memory, Microsoft Server 2008
standard.
NOTE:
NOTE:NOTE:
NOTE:
HP Data Center Environmental Edge Server can manage several Base Station
gateway networks, deployment license based on installed floor space.
NOTE:
NOTE:NOTE:
NOTE:
For additional information on the HP ProLiant DL180 G6, please see the
following:
http://h18000.www1.hp.com/products/quickspecs/13248_div/13248_div.html
AV865A
HP Insight Environmental Observer S/W
NOTE:
NOTE:NOTE:
NOTE:
Includes 1 year of 24x7 SW Technical Support and Updates.
AT515A
HP Data Center Environmental Edge Environmental Base Station
AT516A
HP Data Center Environmental Edge Rack Sensor Array
AT517A
HP Data Center Environmental Edge Air Pressure Base Station
AT518A
HP Data Center Environmental Edge Base Station Gateway
AT519A
HP Data Center Environmental Edge Installer Kit
AT533A
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Configuration Information
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 7
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Optional SKUs
Optional SKUsOptional SKUs
Optional SKUs
HP Data Center Environmental Edge 208v/200A Energy Base Station
AT521A
HP Data Center Environmental Edge 200A Current Base station
AT520A
HP Data Center Environmental Edge Flow Meter Base Station
AT522A
HP Data Center Environmental Edge Water Leak Detection Base Station
AT524A
HP Data Center Environmental Edge 208V/600A Energy Base Station
AT527A
HP Data Center Environmental Edge Rack Door Position Base Station
AT525A
HP Data Center Environmental Edge Three Point Sensor Array
AT514A
HP Data Center Environmental Edge Plenum Rated Sensor Array
AT526A
HP Data Center Environmental Edge 480v/200A Energy Base Station
AT530A
HP Data Center Environmental Edge 480v/600A Energy Base Station
AT531A
HP Data Center Environmental Edge Modbus Base Station
AT532A
HP Data Center Environmental Edge Chilled Water Energy Base Station
AT534A
HP Data Center Environmental Edge Dual Chilled Water Energy Base Station
AT535A
HP Data Center Environmental Edge 208v 42 Circuit Wall Mount BCMS Base Station
AT536A
HP Data Center Environmental Edge 208v 84 Circuit Wall Mount BCMS Base Station
AT537A
HP Data Center Environmental Edge 208v 42 Circuit Subfloor BCMS Base Station
AT538A
HP Data Center Environmental Edge 240v 42 Circuit Wall Mount BCMS Base Station
AX723A
HP Data Center Environmental Edge 240v 84 Circuit Wall Mount BCMS Base Station
AX724A
HP Data Center Environmental Edge 240v 42 Circuit Subfloor BCMS Base Station
AX725A
HP Data Center Environmental Edge Current Sensing Relay Base Station
AX726A
HP Data Center Environmental Edge Base Station Gateway (EU)
AT519A#B19
HP Data Center Environmental Edge Base Station Gateway (APJ:UK)
AT519A#ARS
HP Data Center Environmental Edge Base Station Gateway (AUS)
AT519A#ABG
HP Data Center Environmental Edge Base Station Gateway (CN)
AT519A#AKM
HP Data Center Environmental Edge Base Station Gateway (JPN)
AT519A#ABJ
HP Data Center Environmental Edge Base Station Gateway (UK)
AT519A#ACC
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Configuration Information
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 8
Service and Support
Service and SupportService and Support
Service and Support
Offerings
OfferingsOfferings
Offerings
(HP Care Pack Services)
NOTE:
NOTE:NOTE:
NOTE:
The HP Care Pack service part numbers below for the HP Data Center
Environmental Edge system, cover the server blade and all HP branded hardware
options qualified for the server, purchased at the same time or afterwards, internal to
the server.
Support Plus
Support PlusSupport Plus
Support Plus
Support Plus 24, 1 Year
HA110A1
Support Plus 24, 3 Years
HA110A3
Installation & Startup
Installation & StartupInstallation & Startup
Installation & Startup
HP Installation & Startup Service for HP Data Center Environmental Edge
HA114A1
NOTE:
NOTE:NOTE:
NOTE:
Provides for an integrated hardware and software implementation that
includes remote service planning, onsite deployment of hardware and software,
installation verification testing and customer orientation. Hardware deployment covers
the installation of a single HP Data Center Environmental Edge server, Ethernet
network interconnect, and specified sensor options. Software deployment covers the
installation and configuration of sensors in the HP Data Center Environmental Edge
Software.
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Support & Service
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 9
Wireless RF Specifications
Wireless RF SpecificationsWireless RF Specifications
Wireless RF Specifications
Band
BandBand
Band
2.4 GHz, ISM unlicensed band
IEEE 802.14.5 MAC
Data rate maximum
Data rate maximumData rate maximum
Data rate maximum
250 Kbps
Maximum RF output
Maximum RF outputMaximum RF output
Maximum RF output
power
powerpower
power
0dBm
+0 dBi omni-directional antenna
Base Station Gateway
Base Station GatewayBase Station Gateway
Base Station Gateway
Antenna
AntennaAntenna
Antenna
+2.2dBi
Node to Node Distance
Node to Node DistanceNode to Node Distance
Node to Node Distance
Typical 15m/ 50ft
Regulatory Notices
Regulatory NoticesRegulatory Notices
Regulatory Notices
FCC Part 15, Subpart C, 15.247
U62-SRS100 and U62-THERM
Industry Canada
7265A-SRS100 and 7265A-THERM
CE Marking
EN 300 328; V1.7.1 (2006-05) and EN 300 440-2 V1.1.2 (2004-07)
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Environmental Base
Environmental BaseEnvironmental Base
Environmental Base
Station
StationStation
Station
Housing
HousingHousing
Housing
ABS plastic L 3.6" x W 2.5" x H 1.2" (L 91.5mm x W 63.5mm x H 30.5mm)
Mounting Options
Mounting OptionsMounting Options
Mounting Options
Zip Tie: (4 holes) Accommodates up to 0.18" (4.6mm) width
3M Command Strips
Screws: (4 holes) 1.25" x 1.7" (31.75mm x 43.2mm) - - fits up to #6
Machine Screws
Connectors
ConnectorsConnectors
Connectors
HP 14 position I/O connector for use with HP Data Center Environmental
Edge Rack Sensor Array
Power Requirements
Power RequirementsPower Requirements
Power Requirements
4 Approved Batteries (see Approved Batteries Technical Spec)
Typical Life @ 5 min Sample Rate: 5 to 7 years
Typical Life @ 1 min Sample Rate: 4 years
Internal Sensed Data:
Internal Sensed Data:Internal Sensed Data:
Internal Sensed Data:
Dew Point
Dew PointDew Point
Dew Point
Operating Range: 50ºF-95ºF (10ºC - 35ºC), 20%RH - 80%RH
Accuracy: Nominal +0.86ºF -0.82ºF (+0.48ºC - 0.46ºC)
Accuracy over time: After 1 year +0.92ºF - -0.88ºF (0.51ºC - -0.49ºC)
After 2 years +0.99ºF - -0.94ºF (.0.55ºC - -0.52ºC)
After 3 years +1.06ºF - -0.99ºF (0.59ºC - -0.55ºC)
Internal Sensed Data:
Internal Sensed Data:Internal Sensed Data:
Internal Sensed Data:
Temperature Sensor
Temperature SensorTemperature Sensor
Temperature Sensor
Accuracy: ±0.5ºF (±0.3ºC)
Stability: Negligible
Operating Range: 32ºF to 122ºF (0ºC to 50ºC)
Time Constant: 231sec moving air (typical)C5
Environmental
EnvironmentalEnvironmental
Environmental
Operating: 32 to 104degF (0 to 40degC)
Storage: 14ºF to 140ºF (-10ºC to 60ºC)On-board AC/DC
Operating Temperature: 32ºF to 122ºF (0ºC to 50ºC)
Storage Temperature: 14ºF to 140ºF (-10ºC to 60ºC)
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Technical Specifications
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 10
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge Base
Environmental Edge BaseEnvironmental Edge Base
Environmental Edge Base
Station Gateway
Station GatewayStation Gateway
Station Gateway
Connectors
ConnectorsConnectors
Connectors
RJ45 Ethernet Connection;
2.1x5.5mm 5.0VDC Jack
RPSMA Antenna connector
Power requirements
Power requirementsPower requirements
Power requirements
Gateway node requires 5.0VDC (±5%) via supplied power adapter requiring
110-240VAC (50~60Hz) power source (<2W)
Supplied with 2 approved batteries (See Approved Battery Technical Spec) for
battery backup during 5V power loss.
Ethernet
EthernetEthernet
Ethernet
RJ45 Ethernet 10Base-T or 100Base-TX (auto-sensing)
Ethernet Network Security:SSL v3, SSH2, Rijndael 256-bit encryption,
password protection, IP address filtering, locking features, hardened OS and
stack
Environmental
EnvironmentalEnvironmental
Environmental
Operating: 32 to 104ºF (0 to 40ºC)
Storage: 14ºF to 140ºF (-10ºC to 60ºC)
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge Rack
Environmental Edge RackEnvironmental Edge Rack
Environmental Edge Rack
Sensor Array & Three
Sensor Array & ThreeSensor Array & Three
Sensor Array & Three
Point Sensor Array
Point Sensor ArrayPoint Sensor Array
Point Sensor Array
Connectors
ConnectorsConnectors
Connectors
HP 14 position I/O connector for use with HP Data Center Environmental
Edge Rack Sensor Array
Mounting Options
Mounting OptionsMounting Options
Mounting Options
Rack Sensor Array: 3M Command strips to front and rear rack doors. If no
doors then side of rack
Three Point Sensor Array: 3M Command strips to attach where the customer
needs temperature and humidity visualization
External Temperature
External TemperatureExternal Temperature
External Temperature
Sensors
SensorsSensors
Sensors
Rack Sensor Array: 6 external thermistors
Three Point Sensor Array: 3 external thermistors
Temperature Range: 32ºF to 122ºF (0ºC to 50ºC)
Temperature Accuracy 10 to 43ºC: ±0.5ºF (±0.3ºC)
Temperature Accuracy 0 to 10 and 43 to 50ºC: ±1.2ºF (±0.7ºC)
Time Constant: 30sec moving air; 60sec static air (typical)
Resolution:
±0.02ºF at 77ºF (±0.01ºC at 25ºC)
Stability: Typically ± 0.0056ºF (0.0031ºC) over 5 years
Thermistors: 10k ohm, Type J Curve
Thermistor Time Constant: 60sec static air; 30sec moving air (typical)
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Plenum Rated Sensor
Plenum Rated SensorPlenum Rated Sensor
Plenum Rated Sensor
Array
ArrayArray
Array
Connectors
ConnectorsConnectors
Connectors
HP 14 position I/O connector for use with HP Data Center Environmental
Edge Rack Sensor Array
Mounting Options
Mounting OptionsMounting Options
Mounting Options
3M Command strips to front and rear rack doors. If no doors then side of
rack
External Temperature
External TemperatureExternal Temperature
External Temperature
Sensors
SensorsSensors
Sensors
2 plenum rated thermistors attached to plenum rated wire
Temperature Range: 32ºF to 122ºF (0ºC to 50ºC)
Temperature Accuracy 10 to 43ºC: ±0.5ºF (±0.3ºC)
Temperature Accuracy 0 to 10 and 43 to 50ºC: ±1.2ºF (±0.7ºC)
Time Constant: 30sec moving air; 60sec static air (typical)
Resolution:
±0.02ºF at 77ºF (±0.01ºC at 25ºC)
Stability: Typically ± 0.0056ºF (0.0031ºC) over 5 years
Thermistors: 10k ohm, Type J Curve
Thermistor Time Constant: 60sec static air; 30sec moving air (typical)
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Technical Specifications
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 11
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge Air
Environmental Edge AirEnvironmental Edge Air
Environmental Edge Air
Pressure Base Station
Pressure Base StationPressure Base Station
Pressure Base Station
Housing
HousingHousing
Housing
ABS plastic L 4.5" x W 2.6" x H 1.4" (L 114.3mm x W 66.1mm x H 35.6mm)
Mounting Options
Mounting OptionsMounting Options
Mounting Options
Screw: (4 holes) 1.7" x 1.3" (43.2mm x 33.1mm) - fits up to #6 Machine
Screws
Zip Tie: (4 holes) Accommodates up to 0.18" width
3M Command Strips
Connectors
ConnectorsConnectors
Connectors
1/8" Barbed Hose Fitting for High and Low Pressure Differential connections
Power Requirements
Power RequirementsPower Requirements
Power Requirements
4 Approved Batteries (see Approved Batteries Technical Spec)
Typical battery life @ 5 min Sample Rate: 5 to 7 years
Typical battery Life @ 1 min Sample Rate: 4 years
Sensed Data
Sensed DataSensed Data
Sensed Data
Pressure Sensor
Pressure SensorPressure Sensor
Pressure Sensor
Performance
PerformancePerformance
Performance
Internal 0 to 0.5 in-H2O Air Pressure Differential (room vs. plenum)
Sensed Data
Sensed DataSensed Data
Sensed Data
High and Low Pressure
High and Low PressureHigh and Low Pressure
High and Low Pressure
Ports
PortsPorts
Ports
Differential Pressure Range: 0 to 0.5" H2O (0 to 125 Pa)
Zero point accuracy: 0.002" H2O (0.5Pa)
Span Accuracy: ±3.0% of reading
Resolution:
±0.001"H2O (±0.25 Pa)
Offset Stability: <0.1 Pa per year
0.170 inch inner diameter tubing; use with up to
6 feet of tubing, cut to length as required during installation (supplied with
node; plenum rated UL94V2 tubing). Longer tubing length is allowable, but
sensor accuracy and response time may increase; use pressure diffuser tip to
prevent foreign contaminates entering sensor (supplied with node)
Environmental
EnvironmentalEnvironmental
Environmental
Operating: 32 to 104ºF (0 to 40ºC)
Storage: 14ºF to 140ºF (-10ºC to 60ºC)
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Universal Base Station
Universal Base StationUniversal Base Station
Universal Base Station
Housing
HousingHousing
Housing
ABS plastic L 3.6" x W 2.5" x H 1.2" (L 91.5mm x W 63.5mm x H 30.5mm)
Mounting Options
Mounting OptionsMounting Options
Mounting Options
Screws: (4 holes) 1.25" x 1.7" (31.75mm x 43.2mm) - fits up to #6 Machine
Screws
Power Requirements
Power RequirementsPower Requirements
Power Requirements
Zip Tie: (4 holes) Accommodates up to 0.18" width
3M Command Strips
4 Approved Batteries (see Approved Batteries Technical Spec)
Analog inputs
Analog inputsAnalog inputs
Analog inputs
Typical Battery Life @ 5 min Sample Rate: 5 to 7 years
Typical Battery Life @ 1 min Sample Rate: 4 years
4-20mA:
Accuracy: ±1.15% Full Scale
Resolution 0.03%v
0-10V:
Accuracy: ±1.53% Full Scale
Resolution 0.03%
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Technical Specifications
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 12
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge 200A
Environmental Edge 200AEnvironmental Edge 200A
Environmental Edge 200A
Current Base Station
Current Base StationCurrent Base Station
Current Base Station
Accuracy
AccuracyAccuracy
Accuracy
±0.5% (from 1 - 100% FSO)
Range
RangeRange
Range
0 - 200A RMS
Console Display
Console DisplayConsole Display
Console Display
2 significant digits for volumetric flow
Environmental
EnvironmentalEnvironmental
Environmental
10°C to 40°C / 20% to 95% RH, non-condensing
Installation
InstallationInstallation
Installation
Licensed electrician, circuit downtime not required
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge Flow
Environmental Edge FlowEnvironmental Edge Flow
Environmental Edge Flow
Meter Base Station
Meter Base StationMeter Base Station
Meter Base Station
Flow Range
Flow RangeFlow Range
Flow Range
0 to 400fps (based on typical industrial pipe applications this equates to no
limitation in terms of volumetric flow)
Installation
InstallationInstallation
Installation
Non-intrusive ultrasonic flow measurement
Console Display
Console DisplayConsole Display
Console Display
Volumetric Flow, range adjusted at installation for min/max
Limits
Resolution
ResolutionResolution
Resolution
1/3200th of the installed range
Console Display
Console DisplayConsole Display
Console Display
0 significant digits for volumetric flow
Pipe materials
Pipe materialsPipe materials
Pipe materials
Steel, Copper, Plastic (2-16" diameter)
Accuracy
AccuracyAccuracy
Accuracy
±2.8%
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Water Leak Detection
Water Leak DetectionWater Leak Detection
Water Leak Detection
Base Station
Base StationBase Station
Base Station
Leak Detection
Leak DetectionLeak Detection
Leak Detection
Optical sensor detects liquid contacting surface
Adjustable Height
Sensor Operating
Sensor OperatingSensor Operating
Sensor Operating
Temperature
TemperatureTemperature
Temperature
-13ºF to 176ºF (-25ºC to 80ºC)
HP Data Center
HP Data CenterHP Data Center
HP Data Center
Environmental Edge
Environmental EdgeEnvironmental Edge
Environmental Edge
Installer kit
Installer kitInstaller kit
Installer kit
Kit Contents
Kit ContentsKit Contents
Kit Contents
Barcode Scanner
Label Maker
Wire Strippers
Plenum Rated Zip Ties
Command Strips
Cable routing clips
Thermistor mounting clips
Return shipping label
Battery Technical
Battery TechnicalBattery Technical
Battery Technical
Information
InformationInformation
Information
Approved Battery
Approved BatteryApproved Battery
Approved Battery
ENERGIZER AA LITHIUM, MODEL# L91, 1.5VDC
Battery Life Expectations
Battery Life ExpectationsBattery Life Expectations
Battery Life Expectations
Typical Battery Life @ 5 min Sample Rate: 5 to 7 years
Typical Battery Life @ 1 min Sample Rate: 4 years
HP BCMS
HP BCMSHP BCMS
HP BCMS
Components
Includes 42 or 84 Split Core CT's, 60 amp rated each
Includes 2 or 4 CT to Ribbon Cable Interface Box
Includes 1 data acquisition board
Mounting and Installation
Install data acquisition module inside electrical box or in remote electrical
box. Voltage connections are routed to data acquisition module. Split Core
CT's are connected to Ribbon Cable Interface boxes, which then convert to
ribbon cables connected to the data acquisition board. Modbus connection
uses Modbus RTU 4wire multi-drop.
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Technical Specifications
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 13
Power Requirements
110-240VAC, 4 wire
Data acquisition board can be powered in parallel or separately.
Sensed Data
HP EIO software will provide the following data points:
Current per circuit with breaker capacity and warning status
Power Factor per circuit
Voltage per phase
Power per circuit, per phase, and total with warning status
Accuracy
*
Current (amperage): +/-2%
Voltage (volts): +/-2%
Power (kw): +/-3%
Installation
Local licensed electrician required for installation and
*
onsite calibration
HP Energy Meter
HP Energy MeterHP Energy Meter
HP Energy Meter
Components
Includes HP wireless base station, SquareD ION6200 in single HDM
enclosure, and 3 Split Core CT's, both UL and CE rated
Mounting and Installation
HDM Dimensions: 11.92"x7.5"x7.88"
Wall mount ION6200 enclosure. Voltage and CT connections are routed
from source to HDM enclosure.
Power Requirements
110-480VAC
*
, 50/60Hz, up to 2400amps per circuit
*
, 3 or 4 wire, Wye or
Delta.
* Depending on model ordered
Sensed Data
HP EIO software will provide the following data points:
Current per phase (Wye only)
Power Factor per phase (Wye only)
Voltage per phase (Wye L-N and Delta L-L)
Total Power
Average Power (period = 5min sampling interval)
THD
Accuracy
*
Current (amperage): +/-1%
Voltage (volts): +/-1%
Power (kw): +/-2%
Installation
Local licensed electrician required for installation and
*
onsite calibration
HP Chilled Water Energy
HP Chilled Water EnergyHP Chilled Water Energy
HP Chilled Water Energy
Meter
MeterMeter
Meter
Components
Includes HP wireless base station, Ultrasonic Flow Meter with remote
transducers, and 2 pipe temperature RTD's
Mounting and Installation
Ultrasonic transducers are clamped directly to the chilled water pipe surface.
Pipe temperature RTD's are clamped directly to the chilled water pipe
surfaces.
Control box and wireless node mounted remotely.
Power Requirements
110-240VAC, 50/60Hz
Sensed Data
HP EIO software will provide the following data points:
Supply Volumetric Flow Rate
Supply Temperature
Return Temperature
Accumulated Energy
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Technical Specifications
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 14
Accuracy
Volumetric Flow: +/-3%
Temperature: +/-0.2degC
Energy: +/-3%
Environment-friendly
Environment-friendlyEnvironment-friendly
Environment-friendly
Products and Approach
Products and ApproachProducts and Approach
Products and Approach
End-of-life Management
End-of-life ManagementEnd-of-life Management
End-of-life Management
and Recycling
and Recyclingand Recycling
and Recycling
Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling
programs in many geographic areas. For trade-in information, please go to:
http://www.hp.com/go/green
. To recycle your product, please go to:
http://www.hp.com/go/green
or contact your nearest HP sales office.
Products returned to HP will be recycled, recovered or disposed of in a
responsible manner.
The EU WEEE directive (2002/95/EC) requires manufacturers to provide
treatment information for each product type for use by treatment facilities.
This information (product disassembly instructions) is posted on the Hewlett
Packard web site at:
http://www.hp.com/go/green
. These instructions may
be used by recyclers and other WEEE treatment facilities as well as HP OEM
customers who integrate and re-sell HP equipment.
© Copyright 2009 Hewlett-Packard Development Company, L.P.
The information contained herein is subject to change without notice.
Microsoft and Windows NT are US registered trademarks of Microsoft Corporation. Intel is a US registered trademark of Intel
Corporation.
The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and
services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial
errors or omissions contained herein.
QuickSpecs
HP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP InsightHP Data Center Environmental Edge and HP Insight
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Environmental ObserverEnvironmental Observer
Environmental Observer
Technical Specifications
DA - 13392 Worldwide — Version 2 — November 16, 2009
Page 15
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

HP AT517A User manual

Category
Rack accessories
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI