Carrier 38YSA User manual

Category
Heat pumps
Type
User manual

This manual is also suitable for

38YSA
Heat Pump—Outdoor Section
Installation and Start-Up Instructions
NOTE: Read the entire instruction manual before starting the
installation.
This symbol indicates a change since the last issue.
SAFETY CONSIDERATION
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause personal injury or property damage.
Consult a qualified installer, service agency, or your distributor or
branch for information or assistance. The qualified installer or
agency must use factory-authorized kits or accessories when
modifying this product. Refer to the individual instructions pack-
aged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for brazing operations. Have fire extinguisher
available. Read these instructions thoroughly and follow all
warnings or cautions attached to the unit. Consult local building
codes and the National Electrical Code (NEC) for special instal-
lation requirements.
Recognize safety information. This is the safety-alert symbol
.
When you see this symbol on the unit or in instructions and
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU-
TION. These words are used with the safety-alert symbol. DAN-
GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal
injury or product and property damage.
Before installing or servicing system, always turn off main
power to system. There may be more than 1 disconnect
switch. Turn off accessory heater power if applicable. Elec-
trical shock can cause personal injury or death.
INSTALLATION
Step 1—Check Equipment and Jobsite
UNPACK UNIT Move to final location. Remove carton, taking
care not to damage unit.
INSPECT EQUIPMENT File claim with shipping company,
prior to installation, if shipment is damaged or incomplete. Locate
unit rating plate on unit corner panel.
It contains information needed to properly install unit. Check
rating plate to be sure unit matches job specifications.
Step 2—Install on a Solid, Level Mounting Pad
If conditions or local codes require unit be attached to pad,
tie-down bolts should be used and fastened through knockouts
provided in unit base pan. Refer to unit mounting pattern in Fig. 2
to determine base pan size and knockout hole location.
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30-in. clearance to
service end of unit and 48 in. above unit. For proper airflow, a 6-in.
clearance on 1 side of unit and 12 in. on all remaining sides must
be maintained. Maintain a distance of 24 in. between units.
Position so snow or ice from roof or eaves cannot fall directly on
unit.
On rooftop applications, locate unit at least 6 in. above roof
surface. Place unit above a load-bearing wall and isolate unit and
tubing set from structure. Roof-mounted units exposed to winds
above 5 mph may require wind baffles to achieve adequate defrost.
Consult low-ambient guideline for wind baffle construction.
Arrange supporting members to adequately support unit and
minimize transmission of vibration to building. Consult local
codes governing rooftop applications.
NOTE: Unit must be level to within ± per compressor manu-
facturer specifications.
Step 3—Elevate Unit
For proper drainage, heat pump must be raised off of mounting
surface. Fig. 3 shows unit with accessory heat pump feet installed.
Use accessory heat pump snow rack in areas where prolonged
subfreezing temperatures or heavy snow occur. Refer to separate
Installation Instructions packaged with accessories.
For proper unit operation and reliability, this unit must be
installed with hard shutoff TXV on indoor section. Do not
install with evaporator coils having capillary tube or piston-
type metering devices.
Step 4—Thermostatic Expansion Valve
The outdoor section is factory equipped with a hard shutoff TXV
for metering refrigerant during heating mode. See Fig. 4-6
for location of TXV and sensing bulb in system.
Fig. 1—Model 38YSA
A92446
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 5a 5a
PC 101 Catalog No. 563-811 Printed in U.S.A. Form 38YSA-2SI Pg 1 4-97 Replaces: 38YSA-1SI
Fig. 2—Unit Reference Drawing
Dimensions (In.)
UNIT
SIZE
SERIES
UNIT DIMENSIONS
MINIMUM MOUNTING
PAD DIMENSIONS
A B C D E F G H J K L M Support Feet Snow Stand
024 1 33-13/16 30 34-15/16 4 9-3/4 21-1/2 27-7/8 5/8 8-3/16 16-13/16 20-1/2 14 26 X 32 31 X 35
030 1 39-13/16 30 34-15/16 4 9-3/4 27-1/2 33-7/8 3/4 8-3/16 16-1/2 20-3/8 15 26 X 32 31 X 35
036 1 39-13/16 30 34-15/16 4 9-3/4 27-1/2 33-7/8 3/4 8-3/16 16-1/2 20-3/8 16 26 X 32 31 X 35
042 1 39-13/16 30 34-15/16 4 9-3/4 27-1/2 33-7/8 7/8 8-3/16 16-1/2 20-3/8 15 26 X 32 31 X 35
048 1 33-13/16 38-5/8 45 5-5/16 11-13/16 21-1/2 27-7/8 7/8 8-9/16 19-1/2 25-1/2 16 34 X 42 36 X 46
A96517
2
1
/2
"
1
9
/16
"
AIR DISCHARGE
4
3
/16
"
3
/8 IN.
DIA.
LIQUID LINE
CONN
1
3
/4
"
2
15
/16
"
FIELD POWER SUPPLY CONN
7
/8 IN.
DIA HOLE WITH
1
1
/8 IN. DIA KNOCKOUT
AND
1
3
/8 IN. DIA KNOCKOUT
10
1
/2
"
F
G
A
FIELD CONTROL SUPPLY
CONN
7
/8 IN.
DIA HOLE
AIR DISCHARGE
AIR DISCHARGE
AIR IN
AIR IN
AIR IN
H DIA VAPOR LINE CONN
3
/8 IN. DIA TIEDOWN
KNOCKOUTS (2)
PLACES IN BASEPAN
B
1
1
/4
"
M
ACCESS
PANEL
L
K
C
D
E
J
C
L
1. Allow 30 in.
clearance to service side of unit, 48 in. above unit, 6 in.
on one side, 12 in. on remaining side, and 24 in. between units for proper airflow.
Minimum outdoor operating ambient in cooling mode is 55°F (unless low ambient control is used) max 125°F.2.
Maximum outdoor operating ambient in heating mode is 66°F.3.
Series designation is the 13th position of the unit model number.4.
Center of gravity .5.
NOTES:
2
DO NOT BURY MORE THAN 36 IN. OF REFRIGERANT
TUBING IN GROUND. If any section of tubing is buried,
there must be a 6-in. vertical rise to the valve connections on
the outdoor unit. If more than the recommended length is
buried, refrigerant may migrate to cooler buried section
during extended periods of unit shutdown, causing refrigerant
slugging and possible compressor damage at start-up.
Due to system design, this unit must be installed with a
factory-listed indoor section. Non-approved coils could cause
performance and reliability problems. Refer to pre-sale litera-
ture for approved indoor sections.
Step 5—Check Defrost Thermostat
Check defrost thermostat to ensure it is properly located and
securely attached. There is a liquid header with a brass distributor
and feeder tube going into the outdoor coil. At the end of 1 of the
feeder tubes there is a 3/8-in. OD stub tube approximately 3-in.
long. (See Fig. 7.)
The defrost thermostat should be located on the stub tube. Note
that there is only 1 stub tube used with the liquid header and on
most units it will be the bottom circuit.
Step 6—Make Piping Connections
Outdoor units may be connected to indoor sections using service
parts tubing package or field-supplied refrigerant grade tubing of
correct size and condition. For tubing requirements beyond 50 ft,
substantial capacity and performance losses can occur. Following
the Long-Line Application Guideline, which is available from your
local distributor, will reduce these losses and improve system
reliability. Refer to Fig. 8 for field tubing equivalent line length.
Fig. 3—Accessory Heat Pump Feet
A96419
Fig. 4—TXV Location on Outdoor Section
A96433
TXVTXV
STRAINER
SENSING BULB
DISCHARGE
MUFFLER
Fig. 5—Typical TXV Installation on Indoor Section
A88382
THERMOSTATIC
EXPANSION
VALVE
EQUALIZER
TUBE
SENSING
BULB
COIL
Fig. 6—Positioning of Sensing Bulb
A81032
2 O'CLOCK
10 O'CLOCK
SENSING BULB
STRAP
SUCTION TUBE
8 O'CLOCK
4 O'CLOCK
7
8
IN. OD & SMALLER
LARGER THAN
7
8
IN. OD
DEFROST
THERMOSTAT
FEEDER
TUBE
STUB
TUBE
A96527
Fig. 7—Defrost Thermostat Location
3
NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
INSTALLATION RECOMMENDATIONS
1. Locate unit away from windows, or areas where unit operating
sounds may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate to
capacity of unit. (See Table 1.)
3. Run refrigerant tubes as directly as possible by avoiding
unnecessary turns and bends.
4. Leave some slack between structure and unit to absorb
vibration.
5. When passing refrigerant tubes through wall, seal opening
with RTV or other pliable silicon-based caulk. (See Fig. 9.)
6. Avoid direct lineset contact with water pipes, ductwork, floor
joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with a
rigid wire or strap which comes in direct contact with tubing.
(See Fig. 9.)
8. Ensure that tubing insulation is pliable and it completely
surrounds vapor tube.
9. When necessary, use hanger straps which are 1 in. wide and
conform to shape of tubing insulation. (See Fig. 9.)
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
If refrigerant tubes or indoor coil is exposed to atmospheric
conditions for longer than 5 minutes, it must be evacuated to 500
microns to eliminate contamination and moisture in the system.
OUTDOOR UNITS CONNECTED TO FACTORY-APPROVED
INDOOR UNITS Outdoor unit contains correct system refrig-
erant charge for operation with indoor approved unit when
connected by 15 ft of field-supplied or factory accessory tubing.
Check refrigerant charge for maximum efficiency. (See Step
10—Checking Charge.)
REFRIGERANT TUBING Connect tubing to fittings on out-
door unit vapor- and liquid-service valves. (See Fig. 2.)
Fig. 8—Tube Bend Losses for Long Lines
Fitting Losses in Equivalent Ft
TUBE
SIZE
OD (IN.)
90˚ STD
FIG. 8-A
90˚ L.R.
FIG. 8-B
45˚ STD
FIG. 8-C
5/8 1.6 1.0 0.8
3/4 1.8 1.2 0.9
7/8 2.0 1.4 1.0
1-1/8 2.6 1.7 1.3
A92498
90° LONG RAD
B
90° STD
A
45° STD
C
Table 1—Refrigerant Connections and
Recommended Liquid- and Vapor-Tube Diameters
UNIT
SIZE
LIQUID (IN.) VAPOR (IN.)
VAPOR
(LONG LINE)
(IN.)
Connect
Dia
Tube
Dia
Connect
Dia
Tube
Dia
Connect
Dia
Tube
Dia
024 3/8 3/8 5/8 5/8 5/8 3/4
030, 036 3/8 3/8 3/4 3/4 3/4 7/8
042, 048 3/8 3/8 7/8 7/8 7/8 7/8
Note: Tube diameters are for lengths up to 50 ft. For tubing lengths greater
than 50 ft, consult Long-Line Application Guideline.
Fig. 9—Piping Installation
A92469
OUTDOOR 
WALL
CAULK
INDOOR WALL
NOTE:
AVOID CONTACT BETWEEN TUBING AND STRUCTURE
VAPOR TUBE
LIQUID TUBE
LIQUID TUBE
THROUGH THE WALL
JOIST
HANGER STRAP
(AROUND VAPOR
TUBE ONLY)
VAPOR TUBE
INSULATION
INSULATION
1
MIN
SUSPENSION
4
To avoid valve damage while brazing, service valves must be
wrapped with a heat-sinking material such as a wet cloth.
SWEAT CONNECTION Use refrigerant grade tubing. Service
valves are closed from factory and ready for brazing. After
wrapping service valve with a wet cloth, tubing set can be brazed
to service valve using either silver bearing or non-silver bearing
brazing material. Consult local code requirements. Refrigerant
tubing and indoor coil are now ready for leak testing. This check
should include all field and factory joints. Check factory tubing on
both indoor and outdoor unit to ensure tubes are not rubbing each
other or any sheet metal. Pay particular attention to feeder tubes,
making sure wire ties on feeder tubes are secure and tight.
A brazing shield MUST be used when tubing sets are being
brazed to the service valves to prevent damage to the painted
unit surface.
Relieve all pressure before refrigerant system repair or final
unit disposal to avoid personal injury or death. Use all service
ports and open all flow-control devices, including solenoid
valves.
Do not vent refrigerant to atmosphere. Recover during system
repair or final unit disposal.
Step 7—Make Electrical Connections
To avoid personal injury or death, do not supply power to unit
with compressor terminal box cover removed.
Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.
According to NEC, ANSI/NFPA 70, and local codes, the
cabinet must have an uninterrupted or unbroken ground, to
minimize personal injury if an electrical fault should occur.
The ground may consist of electrical wire or metal conduit
when installed in accordance with existing electrical codes.
Failure to follow this warning could result in electric shock,
fire, or death.
NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage or phase imbalance may
fluctuate above or below permissible limits.
NOTE: Use copper wire only between disconnect switch and
unit.
NOTE: Install branch circuit disconnect per NEC of adequate
size to handle unit starting current. Locate disconnect within sight
from and readily accessible from unit, per Section 440-14 of NEC.
ROUTE GROUND AND POWER WIRES Remove access
panel and control box cover to gain access to unit wiring. Extend
wires from disconnect through power wiring hole provided and
into unit control box. (See Fig. 2.)
CONNECT GROUND AND POWER WIRES Connect ground
wire to ground connection in control box for safety. Connect
power wiring to contactor as shown in Fig. 10.
CONNECT CONTROL WIRING Route 24-v control wires
through control wiring grommet and connect leads to control
wiring pigtails from terminal board. (See Fig. 12.)
Use No. 18 AWG color-coded, insulated (35° C minimum) wires.
If thermostat is located more than 100 ft from unit (as measured
along control voltage wires), use No. 16 AWG color-coded wires
to avoid excessive voltage drop.
Use furnace transformer, fan coil transformer, or accessory trans-
former for control power, 24-v/40-va minimum.
Check factory wires and wire connections to ensure terminations
are secured properly.
Check wire routing to ensure wires are not in contact with tubing,
sheet metal, etc.
NOTE: Use of available 24-v accessories may exceed the mini-
mum 40-va power requirement. Determine total transformer load-
ing and increase the transformer capacity or split the load with an
accessory transformer as required.
NOTE: The defrost timer is factory set for 90-minute cycles. The
timer can be field set for 30- and 50-minute cycles depending on
defrost conditions in your geographical location.
Step 8—Install Electrical Accessories
Refer to individual instructions packaged with kits or accessories
when installing.
Damage may occur to the scroll compressor if operated at a
negative suction pressure during a system pumpdown.
Step 9—Start-Up
1. Fully back seat (open) liquid- and vapor-tube service valves.
2. Unit is shipped with valve stem(s) front seated, and caps
installed. Replace stem caps after system is opened to refrig-
erant flow (back seated). Replace caps finger tight and tighten
an additional 1/6 turn using a backup wrench on valve body
flats to prevent distortion of sheet metal.
3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature.
5. Set room thermostat at HEAT or COOL and fan at ON or
AUTO, as desired. Operate unit for 15 minutes. Check system
refrigerant charge. (See Step 10.)
Fig. 10—Line Power Connections
A91056
DISCONNECT
PER N. E. C. AND/OR
LOCAL CODES
CONTACTOR
GROUND
LUG
FIELD GROUND
WIRING
FIELD POWER
WIRING
5
SEQUENCE OF OPERATION With power supplied to indoor
and outdoor units, transformer is energized.
Cooling
On a call for cooling, the thermostat makes circuits R-O, R-Y, and
R-G. Circuit R-O energizes the reversing valve, switching it to
cooling position. Circuit R-Y energizes contactor, starting outdoor
fan motor and compressor circuit. R-G energizes indoor unit
blower relay, starting indoor blower motor on high speed.
When thermostat is satisfied, its contacts open, de-energizing
contactor and blower relay. Compressor and motors should stop.
Heating
On a call for heating, the thermostat makes circuits R-Y and R-G.
Circuit R-Y energizes contactor, starting outdoor fan motor and
compressor. Circuit R-G energizes indoor blower relay, starting
blower motor on high speed.
Should the temperature continue to fall, R-W2 is made through
second-stage room thermostat bulb. Circuit R-W2 energizes a
sequencer, bringing on first bank of supplemental electric heat and
providing electrical potential to second heater sequencer (if used).
If outdoor temperature falls below the setting of outdoor thermo-
stat, (field-installed option) contacts close to complete circuit and
bring on second bank of supplemental electric heat.
When thermostat is satisfied, its contacts open, de-energizing
contactor and sequencer. All heaters and motors should stop.
Defrost
The defrost control is a time/temperature control which includes a
field-selectable (quick connects located at board edge) time period
between defrost cycles (30, 50, and 90 minutes), factory set at 90
minutes.
The electronic timer and defrost cycle will start only when
contactor is energized and defrost thermostat is closed.
The defrost mode is identical to cooling mode except that the
outdoor fan motor stops and second-stage heat is turned on to
continue warming conditioned space.
To initiate defrost, the defrost thermostat must be closed. This can
be accomplished as follows:
1. Turn off power to outdoor unit.
2. Disconnect outdoor fan motor lead from OF2 on control
board. Tape lead to prevent grounding.
3. Restart unit in heating mode, allowing frost to accumulate on
outdoor coil.
4. After a few minutes in heating mode, liquid-line temperature
should drop below the closing point of defrost thermostat,
approximately 30˚F.
5. Short between speed-up terminals with a flat bladed screw-
driver. (See Fig. 11.) This reduces the timing sequence to
1/256 of the original time.
6. When you hear reversing valve change position, remove
screwdriver immediately. Otherwise the control will terminate
normal 10-minute defrost cycle in approximately 2 sec.
NOTE: Length of defrost cycle will be dependent upon the length
of time it takes to remove screwdriver from test pins after
reversing valve has shifted.
7. Unit will remain in defrost for remainder of defrost cycle time
or until defrost thermostat reopens.
Step 10—Checking Charge
Do not vent refrigerant to atmosphere. Recover during system
repair or final unit disposal.
Factory charge is shown on unit rating plate. (See Fig. 2.)
Service valve gage ports are not equipped with Schrader
valves. To prevent personal injury, make sure gage manifold
is connected to the valve gage ports before moving valves off
fully back seated position. Wear safety glasses and gloves
when handling refrigerant.
Compressor damage may occur if system is overcharged.
Check charge in cooling and heating mode by following procedure
shown on subcooling charging tables located on unit information
plate.
CARE AND MAINTENANCE
For continuing high performance, and to minimize possible
equipment failure, it is essential that periodic maintenance be
performed on this equipment. Consult User’s Manual for proper
frequency of maintenance. Frequency of maintenance may vary
depending upon geographic areas, such as coastal applications.
Step 1—Leave User’s Manual with Homeowner
Explain system operation and maintenance procedures outlined in
User’s Manual.
Fig. 11—Defrost Control
Defrost Control Speed-Up Timing Sequence
for CES0110063/CES0130024
PARAMETER MINIMUM MAXIMUM
SPEED-UP
(NOMINAL)
30-min cycle 27 33 7 sec
50-min cycle 45 55 12 sec
90-min cycle 81 99 21 sec
10-min cycle 9 11 2 sec
5-min cycle 4.5 5.5 1 sec
A91444
OF1
OF2
O
R
T2 Y
TI
DFT
C
TEST
30
50 90
W1
O
R
W2
Y
C
CES0110063,
CES0130024
6
Fig. 12—Typical Circuit Connections
WIRING DIAGRAM NOTES FOR DUAL FUEL THERMOSTAT:
1. Underlined letters on dual terminal indicates its usage.
For Example: O/W2 means O
O/W2 means W2
Outdoor Temperature Sensor must be attached in all dual fuel installations.
Jumper wire between O/W2 and L thermostat terminals MUST be present.
2. Y1 and O connections to 2-stage furnaces MAY NOT EXIST, or may only be a wire rather than a screw terminal.
A95215
Y/Y2
W/W1
R
24 VAC HOT
FAN
FURNACE
COMPRESSOR
RVS COOLING
N/A
DUAL FUEL
THERMOSTAT
SINGLE-SPEED
HEAT PUMP
24 VAC COM
RVS HEATING
RVS SENSING
OUTDOOR
SENSOR
CONNECTION
G
R
R
W
Y
Y
G
C
C
O/W2
Y1/W2
SINGLE-STAGE
FURNACE
W2
O
OUTDOOR
TEMPERATURE
SENSOR
SEE NOTE 1
S2
S1
L
B
C
Y/Y2
W/W1
R
24 VAC HOT
FAN
FURNACE LO
COMPRESSOR
RVS COOLING
FURNACE HI
DUAL FUEL
THERMOSTAT
SINGLE-SPEED
HEAT PUMP
24 VAC COM
RVS HEATING
RVS SENSING
OUTDOOR
SENSOR
CONNECTION
S2
S1
L
B
G
R
R
Y
G
C
C
C
O/W2
Y1/W2
TWO-STAGE OR
VARIABLE SPEED
FURNACE
W2
O
SEE NOTES 1 AND 2
W/W1
Y/Y2
O
W2
Y1
OUTDOOR
TEMPERATURE
SENSOR
A95216
7
FAN COIL
Y/Y2
W/W1
C
R
24 VAC HOT
24 VAC COM
HEAT STAGE 2
COOL/HEAT
STAGE 1
INDOOR FAN
CORPORATE
NON-PROGRAMMABLE
THERMOSTAT
MODEL HP
HEAT
PUMP
RVS COOLING
NOT USED
NOT USED
TROUBLE
OPTIONAL
OUTDOOR
SENSOR
CONNECTION
S2
S1
B
Y1
W3
G
R
L
FK4B
R
W2
Y
Y/Y2
G
W2
C
C
O/W2
O
O
Y1
E
L
A94392
FAN COIL
Y/Y2
W/W1
G
R
24 VAC HOT
INDOOR FAN
HEAT STAGE 2
COOL/HEAT
STAGE 1
RVS COOLING
NOT USED
CORPORATE
PROGRAMMABLE
THERMOSTAT
MODEL HP
HEAT
PUMP
24 VAC COM
NOT USED
TROUBLE
OPTIONAL
OUTDOOR
SENSOR
CONNECTION
S2
S1
B
O/W2
R
L
FK4B
R
W2
Y
Y/Y2
O
W2
G
C
E
L
Y1/W2
W3
O
C
C
A94393
FAN COIL
Y/Y2
W/W1
C
R
24 VAC HOT
24 VAC COM
HEAT STAGE 2
COOL/HEAT
STAGE 1
INDOOR FAN
CORPORATE
NON-PROGRAMMABLE
THERMOSTAT
MODEL HP
HEAT
PUMP
RVS COOLING
NOT USED
NOT USED
TROUBLE
OPTIONAL
OUTDOOR
SENSOR
CONNECTION
S2
S1
B
Y1
W2
G
R
L
FK4C
R
W1
Y
Y/Y2
G
W2
C
C
O/W2
O
O
Y1
A95330
FAN COIL
Y/Y2
W/W1
G
R
24 VAC HOT
INDOOR FAN
HEAT STAGE 2
COOL/HEAT
STAGE 1
RVS COOLING
NOT USED
CORPORATE
PROGRAMMABLE
THERMOSTAT
MODEL HP
HEAT
PUMP
24 VAC COM
NOT USED
TROUBLE
OPTIONAL
OUTDOOR
SENSOR
CONNECTION
S2
S1
B
O/W2
R
L
FK4C
R
W1
Y
Y/Y2
O
W2
G
C
Y1/W2
W2
O
C
C
A95331
Fig. 12—Typical Circuit Connections (continued)
8
FAN COIL
Y
W
C
R
24 VAC HOT
24 VAC COM
HEAT STAGE 2
COOL/HEAT
STAGE 1
INDOOR FAN
NON-CORPORATE
NON-PROGRAMMABLE
THERMOSTAT
MODEL HP
HEAT
PUMP
RVS COOLING
EMERGENCY
HEAT
E
W3
G
R
FK4B
R
W2
Y
Y/Y2
G
W2
C
C
O
O
O
Y1
E
L
A95279
FAN COIL
Y
W
G
R
24 VAC HOT
24 VAC COM
HEAT STAGE 2
COOL/HEAT
STAGE 1
INDOOR FAN
RVS COOLING
EMERGENCY
HEAT
NON-CORPORATE
NON-PROGRAMMABLE
THERMOSTAT
MODEL HP
HEAT
PUMP
E
C
R
G
W2
O
Y
O
W2
R
C
C
FA, FB, FC,
FD, FF
A95280
R
G
W/W1
ODT
Y/Y2
Y1/W2
O/W2
CORPORATE
THERMOSTAT
MODEL HP
INDOOR
SPLICE
CONNECTION
OUTDOOR
SPLICE
CONNECTION
DEFROST
BOARD
W1
W1
Y
W2
E
G
RR
O
CC
C
B
L
S1
S2
24 VAC HOT
FAN
HEAT
STAGE 2
COOL/HEAT
STAGE 1
RVS
COOLING
N/A
24 VAC COM
RVS
HEATING
USED WITH FB4, FB5, FC4, FA4, FH4 FAN COILS
(WITH 1 OUTDOOR TSTAT)
TROUBLE
OUTDOOR
SENSOR
CONNECTION
SYSTEM WITH ONE OUTDOOR THERMOSTAT
A96528
R
G
W/W1
ODT
Y/Y2
Y1/W2
O/W2
CORPORATE
THERMOSTAT
MODEL HP
INDOOR
SPLICE
CONNECTION
OUTDOOR
SPLICE
CONNECTION
DEFROST
BOARD
W1
W2
W1
Y
G
RR
O
CC
C
EHR
B
L
S1
S2
24 VAC HOT
FAN
HEAT
STAGE 2
COOL/HEAT
STAGE 1
RVS
COOLING
N/A
24 VAC COM
RVS
HEATING
USED WITH FB4, FB5, FC4, FA4, FH4 FAN COILS
(WITH 2 OUTDOOR TSTATS)
TROUBLE
OUTDOOR
SENSOR
CONNEC-
TION
E
ODT
EHR
EHR
SYSTEM WITH TWO OUTDOOR THERMOSTATS
A96529
Fig. 12—Typical Circuit Connections (continued)
9
R
G
W/W1
Y/Y2
Y1/W2
O/W2
R
G
CORPORATE
THERMOSTAT
MODEL 2S
FK4C INDOOR
TERMINAL
BOARD
SINGLE-SPEED
HEAT PUMP
W1
C
B
L
S1
S2
O
W2
Y1
C
Y/Y2
24 VAC HOT
FAN
HEAT STAGE 2
COOL/HEAT
STAGE 1
RVS COOLING
HEAT STAGE 3
24 VAC COM
RVS HEATING
TROUBLE
OUTDOOR
SENSOR
CONNECTION
R
Y
O
W2
C
A96532
R
C
Y
G
O
E
W2
L
THERMOSTAT
INDOOR
CONTROL
BOARD
SMART HEAT
WITHOUT OUTDOOR THERMOSTAT
OUTDOOR
SPLICE
DEFROST
BOARD
R
C
Y
G
O
W2D
W2T
W3
Y0
Y
W2
O
C
R
Y
W2
O
C
R
JW1
A96533
R
C
Y
G
O
E
W2
L
THERMOSTAT
INDOOR
CONTROL
BOARD
SMART HEAT
WITH 1 OUTDOOR THERMOSTAT
OUTDOOR
SPLICE
DEFROST
BOARD
R
C
Y
G
O
W2D
W2T
W3
Y0
Y
W2
O
C
R
Y
W2
O
C
R
CUT JW1
ODT
A96534
R
C
Y
G
O
E
W2
L
THERMOSTAT
INDOOR
CONTROL
BOARD
SMART HEAT
WITH SUPPLEMENTAL HEAT RELAY
OUTDOOR
SPLICE
DEFROST
BOARD
R
C
Y
G
O
W2D
W2T
W3
Y0
Y
W2
O
C
R
Y
W2
O
C
R
CUT
JW1
ODT
SHR
SHR
A96535
Fig. 12—Typical Circuit Connections (continued)
10
C
W2
L
ODT
G
Y
THERMOSTAT
SUBBASE
SYSTEM WITH ONE OUTDOOR THERMOSTAT
INDOOR
SPLICE
CONNECTION
OUTDOOR
SPLICE
CONNECTION
DEFROST
BOARD
W3
C
W2
C
W2
E
G
RR
O
Y
E
O
R
USED WITH FB4, FB5, FC4, FA4, FH4 FAN COILS
(WITH 1 OUTDOOR TSTAT)
A96530
C
W2
L
G
Y
THERMOSTAT
SUBBASE
SYSTEM WITH TWO OUTDOOR THERMOSTATS
INDOOR
SPLICE
CONNECTION
OUTDOOR
SPLICE
CONNECTION
DEFROST
BOARD
W3
C
W2W2
C
G
RR
O
Y
E
O
R
USED WITH FB4, FB5, FC4, FA4, FH4 FAN COILS
(WITH 2 OUTDOOR TSTATS)
E
EHR
ODT
ODT
EHR
EHR
A96531
R
G
W/W1
Y/Y2
O/W2
Y1/W2
C
B
24VAC HOT
FAN
HEAT STAGE 2
COOL/HEAT
STAGE 1
RVS COOLING
HEAT STAGE 3
24VAC COMM.
RVS HEATING
LTROUBLE
S1
OUTDOOR
SENSOR
CONNECTION
S2
CORPORATE
THERMOSTAT
MODEL 2S
INDOOR
TERMINAL
BOARD
FK4C
USED WITH FK4C FAN COIL
(CUT J2 JUMPER)
SINGLE-SPEED
HEAT PUMP
R
G
W1
Y/Y2
O
W2
Y1
C
OW
C
W2
O
Y
R
J2
JUMPER
A96536
R
G
W/W1
Y/Y2
O/W2
Y1/W2
C
B
24VAC HOT
FAN
HEAT STAGE 2
COOL/HEAT
STAGE 1
RVS COOLING
N/A
24VAC COMM.
RVS HEATING
LTROUBLE
S1
OUTDOOR
SENSOR
CONNECTION
S2
CORPORATE
THERMOSTAT
MODEL HP
INDOOR
CONTROL
BOARD
WITHOUT OUTDOOR THERMOSTAT
DEFROST
BOARD
OUTDOOR
SPLICE
R
C
Y
G
O
W2D
W2T
W3
Y0
Y
W2
O
C
R
JW1
Y
W2
O
C
R
A96537
Fig. 12—Typical Circuit Connections (continued)
11
R
G
W/W1
Y/Y2
O/W2
Y1/W2
C
B
24VAC HOT
FAN
HEAT STAGE 2
COOL/HEAT
STAGE 1
RVS COOLING
N/A
24VAC COMM.
RVS HEATING
LTROUBLE
S1
OUTDOOR
SENSOR
CONNECTION
S2
CORPORATE
THERMOSTAT
MODEL HP
INDOOR
CONTROL
BOARD
WITH 1 OUTDOOR THERMOSTAT
OUTDOOR
SPLICE
R
C
Y
G
O
W2D
W2T
W3
Y0
Y
W2
O
C
R
Y
W2
O
C
R
CUT
JW1
ODT
DEFROST
BOARD
A96538
R
G
W/W1
Y/Y2
O/W2
Y1/W2
C
B
24VAC HOT
FAN
HEAT
STAGE 2
COOL/HEAT
STAGE 1
RVS
COOLING
N/A
24VAC
COMM.
RVS
HEATING
LTROUBLE
S1
OUTDOOR
SENSOR
CONNEC-
TION
S2
CORPORATE
THERMOSTAT
MODEL HP
INDOOR
CONTROL
BOARD
WITH SUPPLEMENTAL HEAT RELAY
AND WITH 1 OUTDOOR THERMOSTAT
OUTDOOR
SPLICE
DEFROST
BOARD
R
C
Y
G
O
W2D
W2T
W3
Y0
Y
W2
O
C
R
Y
W2
O
C
R
CUT JW1
ODT
SHR
SHR
A96539
R
C
W/W1
Y/Y2
G
O/W2
R
C
CORPORATE
NON-PROGRAMMABLE
THERMOSTAT
MODEL HP
FA, FB, FC,
FD, FF
FAN COIL
HEAT
PUMP
W2
R
E
Y
C
W2
Y1
B
L
S1
S2
O
W3
G
24 VAC HOT
24 VAC COM
HEAT STAGE 2
COOL/HEAT
STAGE 1
INDOOR FAN
RVS COOLING
NOT USED
NOT USED
TROUBLE
OPTIONAL
OUTDOOR
SENSOR
CONNECTION
A96540
R
G
W/W1
Y/Y2
Y1/W2
O/W2
R
G
CORPORATE
PROGRAMMABLE
THERMOSTAT
MODEL HP
FA, FB, FC,
FD, FF
FAN COIL
HEAT
PUMP
W2
R
E
Y
W2
C
B
L
S1
S2
O
C
C
W3
24 VAC HOT
INDOOR FAN
HEAT STAGE 2
COOL/HEAT
STAGE 1
RVS COOLING
NOT USED
24 VAC COM
NOT USED
TROUBLE
OPTIONAL
OUTDOOR
SENSOR
CONNECTION
A96541
Fig. 12—Typical Circuit Connections (continued)
Copyright 1997 CARRIER Corp. 7310 W. Morris St. Indianapolis, IN 46231 38ysa2si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 5a 5a
PC 101 Catalog No. 563-811 Printed in U.S.A. Form 38YSA-2SI Pg 12 4-97 Replaces: 38YSA-1SI
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Carrier 38YSA User manual

Category
Heat pumps
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI