Eaton 17KW Owner's manual

Category
Power generators
Type
Owner's manual
Owners Manual
8, 10, 14, 17 & 20kW Air-cooled,
Automatic Standby Generators
DANGER
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
Not intended for use as Primary Power in place of utility
or in l ife-support applications.
L
I
S
T
E
D
C
U
S
DO NOT LIFT UNIT BY ROOF!
INTRODUCTION
Thank you for purchasing this co
m
pact, high per for
m
ance, air-
c ooled, engine-dr iven generator. It is designed to auto
m
atical ly
supply electr ical power to operate critical loads dur ing a uti lity
power failure.
This unit is factory installed in an all-weather,
m
et al enclosure that
is intended exclusively for outdoor installation. This generator
will operate using either vapor withdrawn liquid propane
(
L
P
)
or
natural gas
(
N
G
)
.
NOTE:
This generator is suitable for supplying typic al
residential loads such as Induction Motors (sump
pumps, ref rigerators, air conditioners, furnaces, etc.),
Electronic Components (computer, monitor, TV, etc.),
Lighting Loads and Microwaves.
READ THIS MANUAL THOROUGHLY
If any por tion of this
m
anual is not understood, contact the n earest
D
ealer for star ting, operating and servicing procedures.
Throughout this publication, and on tags and decals affi xed to the
g enerator,
D
A
N
G
E
R
,
W
A
R
N
I
N
G
, CA
U
TI
O
N
and
N
O
TE blocks are
used to aler t personnel to special instructions about a par ticular
operation that
m
a y be hazardous if perfor
m
ed incorrectly or care-
lessly.
O
bser ve the
m
carefully. Their definitions are as follows:
DANGER
After this heading, read i nstructions that, if not
strictly complied with, will result in serious per-
sonal injury, incl uding death, in addition to prop-
erty damage.
After this heading, read instructions that, if not
strictly complied with, may result in serious per-
sonal injury or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to
equipment and/or property.
NOTE:
After this heading, read explanatory statements that
require special emphasis.
These safety warnings cannot eliminate the hazards that they
indicate. Common sense and strict compliance with the special
instructions while performing the service are essential to pre-
venting accidents.
Four co
mm
only used safety sy
m
bols acco
m
pany the
D
A
N
G
E
R
,
W
A
R
N
I
N
G
and CA
U
TI
O
N
blocks. The type of infor
m
ation each
indicates follows:
This symbol points out important safety informa-
tion that, if not followed, could endanger per-
sonal safety and/or property of others.
This symbol points out potential explosion haz-
ard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use of the equip-
m
ent. The
m
anufacturer strongly reco
mm
end s that the operator
read this
O
wner
'
s Manual
and thoroughly und erstand all instruc-
tions before using this equip
m
ent. The
m
anufacturer also strongly
reco
mm
end s instructing other users t o properly star t and operate
the unit. Thi s prepares the
m
if they n eed to operate the equip
m
ent
in an e
m
ergency.
CONTENTS
This
m
anual c ontains per tinent owners infor
m
ation for these
m
odels:
7 k
W
N
G
, 8 k
W
L
P, single-cylinder
G
H
-410 Engine
9 k
W
N
G
, 10 k
W
L
P, V-twin
G
T-530 Engine
13 k
W
N
G
, 14 k
W
L
P, V-twin
G
T-990 Engine
16 k
W
N
G
, 17 k
W
L
P, V-twin
G
T-990 Engine
18 k
W
N
G
, 20 k
W
L
P, V-twin
G
T-999 Engine
OPERATION AND MAINTENANCE
It is the operator
'
s responsibility to per f or
m
all safety ch ecks, to
m
ake sure that all
m
aintenance for safe oper ation is perfor
m
ed
pro
m
ptly, and to have the equip
m
ent check ed periodically by a
D
ealer.
N
or
m
al
m
aintenance service and replace
m
ent of par ts
are the responsibility of the owner/operator and, as such, are not
c onsidered defects in
m
aterials or work
m
an ship within the ter
m
s
of the warranty. Individual operating habi ts and usa ge contribute to
the need for
m
aintenance service.
Proper
m
aintenance and care of the generator ensures a
m
ini
m
u
m
nu
m
ber of proble
m
s and keep operating expenses at a
m
ini
m
u
m
.
S
ee a
D
ealer for se rvice aids and accessories.
HOW TO OBTAIN SERVICE
W
hen the generator requires servicing or repairs, contact a
D
ealer
for assistan ce.
S
ervice technicians are factory-traine d and are
capable of handling all service needs.
W
hen contacting a
D
ealer about par ts and service, always supply
the co
m
plete
m
odel nu
m
ber and serial nu
m
ber of the unit as given
on its data decal, which is located on the generator.
S
ee sec tion
"
The
G
enerator
"
for decal location.
Model No. _________________ Serial No. ______________
Table of Contents
Air-cooled Generators
1
Introduction . .. .. .. .. .. .. .. .. .. . Inside Front Cover
R
ead This Manual Thoroughly ........ .................................. ...IFC
Contents ............................................................................IFC
O
peration and Maintenance............................. ....................IFC
H
ow to
O
btain
S
ervice ....................................................... .IFC
Table of Contents . .. .. .. .. .. .. .. .. .. . . .. .. . . .. .. . . .. . . .. . 1
Safety Rules .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 2
S
tandards Index ................ .....................................................3
Section 1 General Information . .. .. .. .. .. .. .. .. 4
1.1
U
npacking/Inspection .................. ...................................4
1.2 Protec tion
S
yste
m
s ........................................................4
1.3
N
EC
R
eq uire
m
ent for Arc Fault Circuit
Inte rruption Breaker for Bedroo
m
s ..................................4
1.4 E
m
ission Infor
m
ation........................... ...........................5
1.5 The
G
enerator .................. ..............................................6
1.6
S
pecifications . ......................................................... ......7
1.7
S
yste
m
S
et
L
E
D
........ .....................................................8
1.8 Fuel
R
eq uire
m
ents and
R
ec o
mm
endations ................... ...8
1.9 Fuel Consu
m
ption ........ ........... .......................................8
1.10
R
ec onf iguring the Fuel
S
yste
m
................................ ........9
1.11
L
ocation .......... .............................................................10
1.12 Battery
R
eq uire
m
ents ...................................................13
1.13 Battery Installation .......................................... ..............13
1.14 The Battery ..................................................................13
1.15 Battery Charger ............................................................14
Section 2 Post Installation Start-up
and Adjustments .. .. .. .. .. .. .. .. . . .. 14
2.1 Before Initial
S
tar tup ................................................. ....14
2.2 Electrical Checks .............................. ............................14
2.3
G
enerator Tests
U
nder
L
oad ..........................................15
2.4 Checki ng Auto
m
atic
O
peration ......... .............................15
2.5 Engine
G
overnor Adjust
m
ent .. ........... ...........................16
2.6 Voltage
R
egulator Adjust
m
ent ................... ....................16
Section 3 Operation .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 17
3.1 Control Panel Inter face ... .................................. ............17
3.2 Auto
m
atic Transfer
O
peration ........... .............................18
3.3
S
eq uence of Auto
m
atic
O
peration .................................18
3.4 Manual Transfer
O
peration ............................................19
3.5
S
ide Co
m
par t
m
ent
(
V-twin
O
nly
)
..................................20
3.6 Protec tion
S
yste
m
s ......................................................21
Section 4 Maintenance . .. .. .. .. .. .. .. .. .. .. .. .. .. 22
4.1 Fuse .... ......................................................... ................22
4.2 Checki ng the Engine
O
il
L
evel .......................................22
4.3 Changing the Engine
O
il .................. ........... ...................23
4.4 Changing the Engine Air Cleaner ........... ........................24
4.5
S
par k Plug
(
s
)
.......................................... .....................25
4.6 Battery Maintenance ...................... ...............................25
4.7 Adjusting
G
H
-410/
G
T-530/990/999 Va lve Clearance ......25
4.8 Cooling
S
yste
m
............................................................26
4.9 Att ention After
S
ub
m
ersion ...........................................27
4.10 Corrosion Protection.....................................................27
4.11
O
ut of
S
ervice Procedure ..............................................27
4.12
S
ervice
S
c hedule ...... ...................................................28
Section 5 Troubleshooting . .. .. .. .. .. .. .. .. .. .. 29
5.1 Troubleshooting
G
uide ..................................................29
Section 6 Appendix . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 30
6.1 Menu
S
yste
m
N
avigation ........ ........... ...........................30
Section 7 Installation Diagrams .. .. .. .. .. .. . 32
Section 8 Warranty . .. .. .. .. .. .. .. .. .. .. . . .. . . .. .. . . 36
2
S
tudy these
S
AFETY
R
U
L
E
S
carefully before insta lling, ope rating
or servicing this equip
m
ent. B eco
m
e fa
m
iliar with this
O
wner s
Manual
and with the unit. The generator can operat e safely, effi-
ciently and reliably only if it is properly installed, ope rated and
m
aintained. Many accidents are caused by failing to foll ow si
m
ple
and funda
m
ent al rules or precautions.
The
m
anufacturer cannot anticipate every possible circu
m
stance
that
m
ight involve a hazard. The wa rning s in this
m
anual, and on
tags and decals affixed to the unit are, therefore, not all-inclusive. If
using a procedure, work
m
ethod or operating technique the
m
anu-
facturer do es not specifically reco
mm
end, ensure that it is safe for
ot hers. Also
m
ake sure the procedure, work
m
ethod or operating
technique utilized does not render the generator unsafe.
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglecting
its maintenance or being careless can cause
possible injury or death. Permit only responsible
and capable persons to install, operate and main-
tain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
Installation must always comply with applicable
codes, standards, laws and regulations.
A running generator gives off carbon monoxide,
and odorless, colorless poison gas. Breathing in
carbon monox ide can cause headaches, fatigue,
di ziness, nausea, vomitting, confusion, fainting,
siezures or death.
GENERAL HAZARDS
For safety reasons, the
m
anufact urer reco
mm
ends that this equip-
m
ent be installed, serviced and repaired by a
S
ervice
D
ealer or
othe r co
m
petent, qualified electrician or installation technician who
is fa
m
iliar with applicable codes, standards and regulations. The
operator also
m
ust co
m
ply with all such codes, standards and
regulations.
The engine exhaust fu
m
es contain carbon
m
onoxide, which
can b e
D
EA
D
L
Y. This dange rous gas, if breathed in sufficient
c oncentra tions, can cause unconsciousness or even death.
D
o
N
O
T alter or add to the exhaust syste
m
or do anything that
m
ight render the syste
m
unsafe or in nonco
m
pliance with appli-
cable c odes and standards.
Install a batte ry operated carbon
m
onoxide alar
m
indoors,
according to
m
anufacturer
'
s instructions/reco
mm
endations.
Adequate, unobstr ucted flow o f cooling and ventilating air is
c ritical to correct generator operation.
D
o not alter the instal-
lation or per
m
it even par tial blockage of ventilation provisions,
a s this can seriously affec t safe operation of the generator. The
generator MUST be installed and operated outdoors only.
Keep hands, feet , clothing, etc., away fro
m
drive belts, fans,
and other
m
oving or hot parts.
N
ever re
m
ove any dr ive belt or
fan guard while the unit is operating.
W
hen working on this equip
m
ent, r e
m
ain ale r t at all ti
m
es.
N
ever work on the equip
m
ent wh en physically or
m
ent ally
fatigued.
Inspect the generator regularly, and contact the nearest
D
ealer
for par ts needing repair or replace
m
ent.
Before perfor
m
ing any
m
aintenance on the generator, di scon-
nect its battery cables to prevent accidental start up.
D
isconnect
the cable fro
m
the battery post indi cated by a
N
E
G
ATIVE,
N
E
G
or
(
)
first, then re
m
ove th e P
O
S
ITIVE, P
O
S
or
(
+
)
cable.
W
hen
reconnecting the cables, connect the P
O
S
ITIVE cable first, the
N
E
G
ATIVE cable last.
N
ever use the generator or any of its par ts as a step.
S
tepping
on the unit can stress and break par ts, and
m
a y result in dan-
g erous operating conditions fro
m
leaking exhaust gases, fuel
leakage, oil leakage, etc.
ENGINE EXHAUST HAZARDS
G
enerator engine exhaust contains
D
EA
D
L
Y carbon
m
onox-
ide, an odorless, colorless poisonous gas. Brea thing carbon
m
onoxide can cause: dizziness, throbbing te
m
ples, nausea,
m
uscular twitching, headache, vo
m
iting, weakness and sleepi-
ness, inability to think clearly, fainting, unconsciousness or
even death. If you experience any carbon
m
onoxide poisoning
sy
m
pto
m
s,
m
ove i nto fresh air and i
mm
edi ately seek
m
edical
attention.
N
ever operate the generator set with the vehicle inside any
garage or other enclosed area.
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
SAVE THESE INSTRUCTIONS The manufacturer suggests that these rules for safe operation be copied and posted near
the units installation site. Safety should be stressed to all operators and potential operators of this equipment.
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals
known to the state of California t o cause
cancer, birth defects or other reproductive harm.
WARNING:
3
ELECTRICAL HAZARDS
All genera tors covered by this
m
anual produce dangerous
elect rical voltages and can cause fatal electrical shock.
U
tility
power delivers extre
m
ely high and da ngerous volt ages to the
transfer switch as does the standby generator when it is i n
operation. Avoid contact with bare wire s, ter
m
inals, connec-
tions, etc., while the un it is runni ng. Ensure all appropriate
c overs, guards and barriers are in place, secured and/or locked
bef ore operating the generator. If work
m
ust be done around
an operating unit, stand on a n insulated, dry surface to reduce
shock hazard.
D
o not handle any kind of ele ctrical device while stand-
ing in water, while barefoot, or while hands or feet are wet.
D
A
N
G
E
R
O
U
S
E
L
ECT
R
ICA
L
S
HO
CK MAY
R
E
S
U
L
T.
The
N
ational Electrical Code
(
N
EC
)
requires the fra
m
e and external
electrically conductive par ts of the generator to be connected to
an approved ear th ground.
L
ocal electrical codes also
m
ay require
proper grounding of the generator electrical syste
m
.
After installi ng this ho
m
e standby electrical syste
m
, the gener a-
tor
m
a y crank a nd star t at any ti
m
e without warning.
W
hen this
occurs, load circuits are transferred to the
S
TA
N
D
BY
(
g enera-
tor
)
power source. To prevent possible injury if such a star t and
transfer occur, always set the generators A
U
T
O
/
O
FF/MA
N
U
A
L
switch to its
O
FF position before working on equip
m
ent and
re
m
ove the 15A fuse fro
m
the generator control panel.
In case of acciden t caused by electric shock, i
mm
ediately shut
down the source of electrical power. If this is not possible,
atte
m
pt to free the victi
m
fro
m
the live conductor. AV
O
I
D
D
I
R
ECT
C
O
N
TACT
W
IT
H
T
H
E VICTIM.
U
se a nonconducting i
m
ple
m
ent,
such as a dry rope or board, to free the victi
m
fro
m
the live
conductor. If th e victi
m
is unconscious, apply first aid and get
i
mm
ediate
m
edical help.
N
ever wear jewelry when working on this equi p
m
ent. Jewelry
can conduct electricity resulting in electric shock, or
m
a y get
caught in
m
oving co
m
ponents causing injury.
FIRE HAZARDS
For fire safety, the generator
m
ust be installed and
m
aintained
properly. Installation must always comply with applicable
codes, standards, l aws a nd regul ations. Adhere strictly
to local, state and national electrical and building codes.
Co
m
ply with reg ulations the
O
ccupational
S
afety and
H
ealt h
Ad
m
inistration
(
O
S
H
A
)
has establish ed. Also, ensure that the
g enerator is installed in accordance with th e
m
anufacturers
instructions and reco
mm
endations. Fo llowi ng prop er installa-
tion, do nothing that
m
ight alter a safe insta llation and render
the un it in nonco
m
pliance with the afore
m
entioned codes,
standards, laws a nd regulations.
Kee p a fire extinguisher near the gene rator at all ti
m
es.
Extinguishers rated ABC by the
N
ational Fire Protection
Association are appropriate for use on the standby electric
syste
m
. Keep the extinguisher properly charged and be fa
m
iliar
with its use. Consult the local fire d epar t
m
ent with any ques-
tions per taining to fire extinguishers.
EXPLOSION HAZARDS
D
o not s
m
oke a round the generator.
W
ipe up any fuel or oil
spills i
mm
edi ately. Ensur e that no co
m
bustible
m
aterials are left
in the generator co
m
par t
m
ent, or on or near the generator, as
FI
R
E or EXP
L
O
S
I
O
N
m
a y result. Keep the area surrounding the
g enerator clean and free fro
m
debris.
G
a seous fluids such as nat ural ga s and liquid propane
(
L
P
)
gas are extre
m
ely EXP
L
O
S
IVE . Install the fuel supply syste
m
according to applicable fuel-gas codes. Before placing the
ho
m
e standby electric syste
m
into service, fuel syste
m
lines
m
ust be properly purged and leak tested according to applica-
ble code . After installation, inspect the fuel syste
m
period ically
for leaks.
N
o leakage is per
m
itted.
STANDARDS INDEX
In the absence of per tinent st andards, codes, regula tions and
laws, the published infor
m
ation listed below
m
a y be used for
instal lation g uidance for this equip
m
ent.
1.
N
FPA
N
o. 37,
S
TATI
O
N
A
R
Y C
O
MB
U
S
TI
O
N
E
N
G
I
N
E
S
A
N
D
G
A
S
T
U
R
BI
N
E
S
, available fro
m
the
N
ational Fire Protection
Association, 470 Atlantic Avenue, Boston, MA 02210.
2.
N
FPA
N
o. 76A, E
SS
E
N
TIA
L
E
L
ECT
R
ICA
L
S
Y
S
TEM
S
F
O
R
H
EA
L
T
H
CA
R
E FACI
L
ITIE
S
, available sa
m
e as Ite
m
1.
3.
N
FPA
N
o. 54,
N
ATI
O
N
A
L
F
U
E
L
G
A
S
C
O
D
E , available sa
m
e as
Ite
m
1.
4.
N
FPA
N
o. 58, AME
R
ICA
N
N
ATI
O
N
A
L
S
TA
N
D
A
R
D
F
O
R
S
T
O
R
A
G
E A
N
D
H
A
N
D
L
I
N
G
O
F
L
I
Q
U
EFIE
D
PET
R
O
L
E
U
M
G
A
S
,
available sa
m
e as Ite
m
1.
5.
N
FPA
N
o. 70,
N
FPA
H
A
N
D
B
OO
K
O
F
N
ATI
O
N
A
L
E
L
ECT
R
IC
C
O
D
E , available sa
m
e as Ite
m
1.
6. Ar ticle X,
N
ATI
O
N
A
L
B
U
I
L
D
I
N
G
C
O
D
E , av ailable fro
m
the
A
m
erican Insurance Assoc iation, 85 John
S
treet,
N
ew York,
N
.Y. 10038.
7. A
G
R
IC
U
L
T
U
R
A
L
W
I
R
I
N
G
H
A
N
D
B
OO
K, available fro
m
the Food
and Energy Council, 909
U
niversity Avenue, Colu
m
bia, M
O
65201.
8. A
S
AE EP-3634, I
N
S
TA
LL
ATI
O
N
A
N
D
MAI
N
TE
N
A
N
CE
O
F
FA
R
M
S
TA
N
D
BY E
L
ECT
R
ICA
L
S
Y
S
TEM
S
, available fro
m
the
A
m
erican
S
ociety of Agricultural Engineers, 2950
N
ile s
R
oad,
S
t. Joseph, MI 49085.
9.
N
FPA
N
o. 30, F
L
AMMAB
L
E A
N
D
C
O
MB
U
S
TIB
L
E
L
I
Q
U
I
D
S
C
O
D
E , available sa
m
e as Ite
m
1.
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled Generators
DANGER
Only qualified electricians or contractors should
attempt such installations, which must comply
strictly with applicable codes, standards and regu-
l ations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for d a
m
age.
This standby generator set is ready for installation with a factory
supplied and pre-
m
ounted base pad and h as a weather protec-
tive enclosure that is intended for outdoor installation only.
If this generat or is used to power electrical load
circuits normally powered by a utility power
source, it i s required by code to install a transfer
switch. The transfer switch must effectively isolate
the electrical system from the utility distribution
system when the generator is operating (NEC 700,
701 & 702). Failure to isolate an electrical system
by such means will result i n damage to the gen-
erator and also may result in injury or death to
utility power workers due to backfeed of electrical
energy.
If any loss or da
m
age is noted at ti
m
e of delivery, have the
person
(
s
)
m
aking the delivery note all da
m
age on the freight bill
or affix their signature under the consignor
'
s
m
e
m
o of loss or
da
m
age.
If a loss or d a
m
age is noted after delivery, separate the da
m
aged
m
aterials and contact the carrier for clai
m
procedures.
Concealed da
m
age is understood to
m
ean da
m
age to the con-
tents of a package that is not in evidence at the ti
m
e of delivery,
but is discovered later.
To properly open the roof, press down on the center top lip and
release the latch. If pressure is not applied fro
m
the top, the roof
m
a y appear stuck. Always verify that the side lock is unlocke d
bef ore atte
m
pting to lift the roof.
1.2 PROTECTION SYSTEMS
U
nlike a n auto
m
obile engine, the generator
m
a y have to run for
long periods of ti
m
e with no oper ator present to
m
onitor engine
c onditions. For that reason, the engine is equipped with the fol-
lowi ng syste
m
s that prot ect it against potentially da
m
aging condi -
tions:
1.
L
ow
O
il Pressure
S
ensor
2.
H
igh Te
m
perature
S
ensor
3.
O
vercran k
4.
O
versp eed
5.
R
PM
S
ensor
6.
L
ow Batter y
There are readouts on the control panel to notify personnel that one
of these failures has occurred . There is also a
S
yste
m
S
et
L
E
D
(
single cylinder
)
or a
S
tatus
m
essage on the display
(
V-twins
)
that
displays when all of the conditions described in the
"
S
yste
m
S
et
L
E
D
"
section are true.
1.3 NEC REQUIREMENT FOR ARC FAULT
CIRCUIT INTERRUPTION BREAKER FOR
BEDROOMS
In 2001, the
N
ational Electric Code
(
N
EC
)
introduced a require
m
ent
for new construct ion. This new require
m
ent indicates the nee d for
Arc Fault Circuit Interrupters to be used to protect the co
m
plete
branch circuit that feeds a dwelling bedroo
m
. The actual
N
EC
require
m
ent is ind icate d b elow.
1.3.1 SECTION 210.12 ARC FAULT CIRCUIT INTER-
RUPTER PROTECTION
1.
D
efinition: An arc fault circ uit i nterrupt er is a device intended
to provide protection fro
m
the effects of arc fault s by recog-
nizing characteristics unique to arcing and by functioning to
de-energize the circuit when an arc fault is detected.
2.
D
welling
U
nit Bedroo
m
s: All branch circuits that supply 125
volt , single-phase, 15 and 20 a
m
pere outlets installed in
dwelling unit bedroo
m
s shall be protected by an arc fault cir-
c uit interrupter listed to provi de protection of the entire branch
cir cuit.
S
ection 210.12 requires that AFCI protect ion be provided on branch
cir cuits that supply outlets
(
receptacle, lighting, etc.
)
in dwell-
ing bedroo
m
s. The require
m
ent is li
m
ited to 15 and 20 a
m
pere,
125 volt circuit s. There is no prohibition against providing AFCI
protection on other circuits or in locations oth er than b edroo
m
s.
Because circuits are often shared between a bedroo
m
and other
areas such as closets and hallways, providing AFCI protection on
the co
m
plete circuit would co
m
ply with 210.12.
If during the installation of the ho
m
e standby syste
m
the decision
is
m
ade to provi de back up power to a bedroo
m
branch circuit,
then the circuit breaker in the transfer switch should be replaced
with an Arc Fault Circui t Int errupter.
It is
m
ost i
m
por tant that breakers only be switched like for like.
For instance, if replacing a 15A breaker, it M
U
S
T be replaced wi th
a 15A AFCI breaker.
L
ikewise, a 20A breaker M
U
S
T be replaced
with a 20A AF CI.
These AFCI breakers are available at the nearest hardware store.
Eaton Cat #
D
esc ription
B
R
115AF 1
"
15A
S
ing le Pole AFCI
C
H
115AF 3/4
"
15A
S
ing le Pole AFCI
B
R
120AF 1
"
20A
S
ing le Pole AFCI
C
H
120AF 3/4
"
20A
S
ing le Pole AFCI
Section 1 General Information
Air-cooled Generators
4
Section 1 General Information
Air-cooled Generators
5
1.4 EMISSION INFORMATION
The Environ
m
ent al Protection Agency requires that this generator
c o
m
plies with exhaust e
m
ission standards. This generator is cer ti-
fied to
m
eet the applicable EPA e
m
ission levels. Additional infor-
m
ation regarding the require
m
ents set by the EPA is as fo llows:
The generator is cer tified for use as a stationary engine for standby
power generation. Any other use
m
a y be a violation of federal
and/or local laws. It is i
m
por tant that to follow the
m
aintenance
spe cifications in the
"
Maintenance
"
section to ensure that the
engine co
m
plies with the applicable e
m
ission stand ards for the
dur ation of the engines life. This engine is certified to operate on
L
iquid Propane fuel and pipeline
N
atural
G
a s. The e
m
ission control
syste
m
on the generator consists of the following:
Fuel Metering
S
yste
m
Carburetor/
m
ixer asse
m
bly
Fuel regulator
Air Induction
S
yste
m
Intake pipe/
m
anifold
Air cleaner
Ignition
S
yste
m
S
par k plug
Ignition
m
odule
The E
m
issions Co
m
pliance Period referred to on the E
m
issions
Co
m
pliance
L
abel indica tes the nu
m
ber of operating hours for
which the engine has been shown to
m
eet Federal e
m
ission
require
m
ents.
S
ee the table below to deter
m
ine t he co
m
pliance
period f or the generator. The displace
m
ent of the gene rator is listed
on the E
m
issions Co
m
pliance
L
abel.
D
isplace
m
ent Category Co
m
pliance Period
< 66 cc
A 300
H
ours
B 125
H
ours
C 50
H
ours
66 cc -
< 225 cc
A 500
H
ours
B 250
H
ours
C 125
H
ours
225 cc
A 1000
H
ours
B 500
H
ours
C 250
H
ours
6
Section 1 General Information
Air-cooled Generators
1.5 THE GENERATOR
Data Label
(see sample)
Oil
Dipstick
Exhaust
Enclosure
Composite Base Oil Filter Battery Compartment
Fuel
Regulator
Fuel Inlet
(back)
Air Filter
Circuit
Breaker
Control
Panel
Data Label
(see sample)
Oil
Dipstick
Exhaust
Enclosure
Composite Base Oil Filter Battery Compartment
Fuel
Regulator
Fuel Inlet
(back)
Air Filter
Circuit Breakers
GFCI Outlet
(All 17 & 20kW)
Control
Panel
Figure 1.3 14, 17 and 20k W, V-twin,
GT-990/GT-999 Engine (door removed)
Figure 1.1 8kW, Single Cylinder, GH-410 Engine
(door removed)
Data Label
(see sample)
Oil
Dipstick
Exhaust
Enclosure
Composite Base Oil Filter Battery Compartment
Fuel
Regulator
Fuel Inlet
(back)
Air
Filter
Circuit
Breaker
Control
Panel
Figure 1.2 10kW, V-t win, GT-530 Engine
(door removed)
Data Label Sample
7
Section 1 General Information
Air-cooled Generators
1.6 SPECIFICATIONS
1.6.1 GENERATOR
Model 8kW 10kW 14kW 17kW 20kW
R
ated Maxi
m
u
m
Power Capacity
(
W
atts*
)
7,000
N
G
8,000
L
P
9,000
N
G
10,000
L
P
13,000
N
G
14,000
L
P
16,000
N
G
17,000
L
P
18,000
N
G
20,000
L
P
R
ated Voltage 120/240
R
ated Maxi
m
u
m
L
oad Current
(
A
m
ps
)
120 Volts**
(
N
G
/
L
P
)
58.3/66.6 75.0/83.3 108.3/116.6 133.3/141.6 150.0/166.6
240 Volts
(
N
G
/
L
P
)
29.2/33.3 37.5/41.6 54.2/58.3 66.6/70.8 75.0/83.3
Main Circuit Breaker 35 A
m
p 45 A
m
p 60 A
m
p 65 A
m
p 100 A
m
p
Phase 1
N
u
m
ber of
R
otor Poles 2
R
ated AC Frequen cy 60
H
z
Battery
R
equ ire
m
ent
G
roup 26
R
, 12 Vol ts and
350 CCA Mini
m
u
m
G
roup 26
R
, 12 Vol ts and 525 CCA Mini
m
u
m
W
eight
(
unit only in lbs.
)
340 387 439 455/421 450
Enclosure
S
teel
S
teel
S
teel
S
teel/Alu
m
inu
m
Alu
m
inu
m
N
or
m
al
O
perating
R
ange -20
°
F
(
-28.8
°
C
)
to 77
°
F
(
25
°
C
)
* Maxi
m
u
m
wattage and current are subject to a nd li
m
ited by such factors as fuel Btu content, a
m
bient te
m
perature, altitude, engine power and condition, etc. Maxi
m
u
m
power de creases about 3.5
percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6 C
(
10 F
)
above 16 C
(
60 F
)
a
m
bient te
m
perature.
**
L
oad curr ent values shown for 120 volts are
m
axi
m
u
m
T
O
TA
L
values for two separate circuits. The
m
axi
m
u
m
current in each circuit
m
ust not exceed the value stated for t he 240 volts.
*** Circ uits to be
m
oved
m
ust be prot ected by sa
m
e size breaker. F or exa
m
ple, a 15 a
m
p circu it in the
m
a in panel
m
ust be a 15 a
m
p circu it in the transfer switch.
1.6.2 ENGINE
Model 8 kW 10 kW 14/17 kW 20 kW
Type of Engine
G
H
-410
G
T-530
G
T-990
G
T-999
N
u
m
ber of Cylinders 1 2 2 2
R
ated
H
orse power @ 3,600 rp
m
14.8 18 32 36
D
isplace
m
ent 410cc 530cc 992cc 999cc
Cylinder Block Alu
m
inu
m
w/Cast Iron
S
leeve
Valve Arrange
m
ent
O
verhead Valves
Ignition
S
yste
m
S
olid-state w/Magneto
R
eco
mm
ended
S
park Plug
R
C14YC BP
R
6
H
S
R
C14YC
R
C12YC
S
park Plug
G
ap 0.76
mm
(
0.030 inch
)
0.76
mm
(
0.030 inch
)
1.02
mm
(
0.040 inch
)
0.76
mm
(
0.030 inch
)
Co
m
pression
R
atio 8.6:1 9.5:1 9.5:1 9.5:1
S
tar ter 12 V
D
C
O
il Capacity Including Filter Approx. 1.5
Q
ts Approx. 1.7
Q
ts Approx. 1.7
Q
ts Approx. 1.7
Q
ts
R
eco
mm
ended
O
il Filter Par t # 070185F
R
eco
mm
ended Air Filter Par t # 0
G
3332 Par t # 0E9581 Par t # 0C8127 Par t # 0
G
5894
O
perating
R
PM 3,600
1.7 SYSTEM SET LED
The
S
yste
m
S
et
L
E
D
(
single cylinder
)
or
"
R
eady to
R
un
"
on the
display
(
v-twin
)
is ready when all of the fol lowing conditions are
true:
1. The A
U
T
O
/
O
FF/MA
N
U
A
L
switch is set to the A
U
T
O
position.
2. The utility voltage being supplied to the unit is being sensed
by the PCB. If the utility sense voltage is not connected to the
unit or if it is below approxi
m
ately 150-160 volts AC, then the
syste
m
set light will flash rapidly
(
8k
W
)
. This indicat es that if
the A
U
T
O
/
O
FF/MA
N
U
A
L
switch is placed in the Auto position,
the generator will star t.
3.
N
o alar
m
s are present, for exa
m
ple, low oil pressure, hi gh
te
m
perature, etc.
1.8 FUEL REQUIREMENTS
AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal system. This type of
syste
m
uses the vapors for
m
ed above the liquid fuel in t he storage
tank.
The engine has been fitted with a fuel carburetion syste
m
th at
m
eets the specifications of the 1997 California Air
R
esources
Board for ta
m
per-proof du al fuel syste
m
s. Th e unit will run on
natural ga s or
L
P gas, but it has been factory set to run on natural
gas.
S
hould the pri
m
ary fuel need to be changed to
L
P gas, the
fuel syste
m
needs to be reconfigured.
S
ee the reconfig uring the
Fuel
S
yste
m
section for instructions on reconfiguration of the fuel
syste
m
.
R
ec o
mm
ended fuels should have a Btu content of at least 1,000
Btus per cubic foot for natural gas; or at least 2,520 Btus per
c ubic foot for
L
P ga s. Ask the fuel supplier for the Btu content of
the fuel.
R
eq uired fuel pressure for natural gas is five (5) inches to seven
(7) inches water column (0.18 to 0.25 psi); and for liquid pro-
pane, 10 inches to 12 inches of water column (0.36 to 0.43 psi).
The primary regulator for the propane supply is NOT INCLUDED
with the generator.
NOTE:
All pipe sizing, construction and layout must comply
with NFPA 54 for natural gas applications and NFPA
58 for liquid propane applications. Once the genera-
t or is installed, verify that the fuel pressure NEVER
drops below four (4) inches w ater column for natural
gas or 10 inches water column for liquid propane.
Prior to install ation of the generator, the installer should consult
loca l fuel suppliers or the fire
m
arshal to check codes and regula-
tions for proper installation.
L
ocal codes will
m
andate correct rout-
ing of gaseous fuel line piping around gardens, shrubs and other
landscaping to prevent any d a
m
age.
S
pecial considerations should be given when installing the unit
where local conditions include flooding, torn ados, hurricanes,
ear thquakes a nd unstable ground for the flexibility and strength of
piping and their connecti ons.
U
se an approved pipe sealant or joint co
m
pound on all threaded
fitting.
All installed gaseous fuel piping
m
ust be purged and leak tested
pri or to initial star t-up in accord ance with local codes, standards
and regulations.
1.9 FUEL CONSUMPTION
Unit
Nat. Gas LP Vapor
1/2 Load Full Load 1/2 Load Full Load
7/8 k
W
77 140 0.94/34 1.68/62
9/10 k
W
102 156 1.25/46 1.93/70
13/14 k
W
156 220 1.56/58 2.30/84
16/17 k
W
183 261 1.61/59 2.57/94
18/20 k
W
206 294 1.89/69 2.90/106
*
N
atural gas is in cubic feet per hour.
**
L
P is in gallons per hour/cubic feet per hour.
*** Values given are approxi
m
ate.
Verify t hat g as
m
eter is capable of provid ing enough fuel flow to
include household appliances.
1.9.1 BTU FLOW REQUIREMENTS -
NATURAL GAS
BT
U
flow req uired for each unit based on 1000 BT
U
per c ubic
foot.
7k
W
140,000 BT
U
/
H
our
9k
W
156,000 BT
U
/
H
our
13k
W
220,000 BT
U
/
H
our
18k
W
294,000 BT
U
/
H
our
DANGER
Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause
an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to
collect in high areas. LP gas is heavier than air
and tends to settl e in low areas.
NOTE:
A minimum of one approved manual shut-off valve
must be installed in the gaseous fuel supply line. The
valve must be easily accessible. Local codes deter-
mine the proper location.
Section 1 General Information
Air-cooled Generators
8
9
1.10 RECONFIGURING THE FUEL SYSTEM
1.10.1 8 KW, 410CC ENGINE
To reconfigure the fuel syste
m
fro
m
N
G
to
L
P, follow these steps
(
Figur e 1.4
)
:
NOTE:
The primary regulator for the propane supply is NOT
INCLUDED with the generator. A fuel pressure of 10
t o 12 inches of water column (0.36 to 0.43 psi) to the
fuel inlet of the generator MUST BE SUPPLIED.
1. Turn off the
m
ain gas supply
(
i f connected
)
.
2.
O
pen the roof and re
m
ove the door.
3.
R
e
m
ove the battery
(
i f installed
)
.
4. Take the plast ic T-handle fuel selector in th e poly bag supplied
with the generator.
5.
L
ocat e the selector knob on the air box cover, behind the
yel low air filter door and power bulge. The unit co
m
es fro
m
the factory in the
N
G
(
N
atural
G
a s
)
position.
G
rasping the
T-handle, inser t the pin end into the hole in the selector knob
and pull out to overco
m
e spring pressure and then twist
clockwise 90 degrees and allow th e selector to retur n in once
alig ned with the
L
P
(
L
iquid Propane
)
position.
6.
S
ave this tool with the
O
wner
'
s Manual.
7. Install the battery, door and close the roof.
8.
R
everse the procedure to conv er t back to natural gas.
Figure 1.4 Fuel Selector
NOTE:
Use an approved pipe sealant or joint compound on
all threaded fittings to reduce the possibility of leak-
age.
1.10.2 10, 14, 17 AND 20KW, V-TWIN ENGINES
To reconfigure the fuel syste
m
fro
m
N
G
to
L
P, follow these steps:
NOTE:
The primary regulator for the propane supply is NOT
INCLUDED with the generator. A fuel pressure of 10
t o 12 inches of water column (0.36 to 0.43 psi) to the
fuel inlet of the generator MUST BE SUPPLIED.
1.
O
pen the roof.
2. For 10kW units:
L
oosen cla
m
p and slide back the air inlet
hose.
S
lide fuel selector on carburetor out towards the back of the
enclosure
(
Figur es 1.5 and 1. 6
)
.
R
eturn the inlet hose and tighten cla
m
p securely.
For 14, 17 and 20kW units: re
m
ove the air cleaner cover.
S
lide the selector lever out towards the back of the enclosure
(
Figur es 1.7 and 1. 8
)
.
R
eturn the ai r cleaner cover and tighten the two thu
m
b
screws.
Figure 1.5 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "In"
Position for
Natural Gas
Fuel
Figure 1.6 - 10kW, GT-530 (Inlet Hose Slid Back)
Fuel Selection
Lever - "Out"
Position for
Liquid Propane
(Vapor) Fuel
Section 1 General Information
Air-cooled Generators
10
3. Close the roof.
4.
R
everse the procedure to conv er t back to natural gas.
Figure 1.7 - 14, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "In" Position for Natural Gas Fuel
Figure 1.8 - 14, 17, & 20kW,
GT-990/GT-999 (Airbox Cover Removed)
Fuel Selection Lever - "Out" Position for Liquid Propane
(Vapor) Fuel
1.11 LOCATION
1.11.1 GENERATOR
Install the generator set, in its protective enclosure, outdoors,
where adequate cooling and ventilating ai r is always available
(
Figur e 1.9
)
. Consider these factors:
The installation of the generator must comply strictly with
NFPA 37, NFPA 54, NFPA 58, and NFPA 70 standards.
Install the unit where air inlet and outlet openings will not
beco
m
e obstructed by l eaves, grass, snow, etc.. If prevailing
winds will cause blowing or drifting, consider using a wind-
break to protect the unit.
Install the generat or on high ground where water levels will not
rise and endanger it.
Allow suf ficient roo
m
on all sides of the g enerator for
m
ainte-
nance and servicing. This unit
m
ust be installed in accordance
with curr ent applicable
N
FPA 37 and
N
FPA 70 standards; as
well as any other federal, state and local codes for
m
ini
m
u
m
distances fro
m
other structures.
D
O
N
O
T install under wooden
decks or structures unless there is at least four
(
4
)
feet of clear-
ance above the generator, three
(
3
)
feet of clearance on sides
and front, and 18 inches of clearance at back of unit.
Install the unit where ra in gutter down spouts, roof run-off,
landscape irrigation, water sprinklers or su
m
p pu
m
p discharge
does not f lood the un it or spray th e enclosure, including any air
inlet or outlet openings.
Install the unit where services will not be a ffected or obstructed,
including concealed, underground or covered services such as
elect rical, fuel, phone , air conditioning or irrigation.
W
here strong prevailing winds blow fro
m
on e d irection, face the
g enerator air inlet openings to the prevailing winds.
Figure 1.9 Generator Clearances
Install the g enerator as close as p ossible t o the fuel supply, to
reduce the length of piping.
Install the generator as close as possible to the transfer switch.
R
EMEMBE
R
T
H
AT
L
A
W
S
O
R
C
O
D
E
S
MAY
R
E
G
U
L
ATE T
H
E
D
I
S
TA
N
CE A
N
D
L
O
CATI
O
N
.
The genset
m
ust be installed on a le vel surface. The base fra
m
e
m
ust be level within two
(
2
)
in ches all around.
The generator is typically placed on pea gravel or crushed
stone. Check local codes if a concrete slab is required. If a
c oncrete base slab is required, all fede ral, state and local codes
should be followed.
S
pecial attention should be given to the
c oncrete base slab which should exceed the length and width
of the generator by a
m
ini
m
u
m
of six
(
6
)
inches
(
0.152
m
eters
)
on all sides.
Section 1 General Information
Air-cooled Generators
11
DANGER
The engine exhaust fumes contain carbon mon-
ox ide, whi ch can be DEADLY. This dangerous
gas, if breathed in sufficient concentrations,
can cause unconsciousness or even death. This
generator must be instal led properly, in strict
compliance with applicable codes and stan-
dards. Following installation, do nothing that
might render the system unsafe or in noncom-
pliance with such codes and standards.
Operate the generator outdoors ONLY.
Keep exhaust gases from ent ering a confined
area through windows, doors, ventilation, crawl
spaces or other openings (Figure 1.9).
Generac Power Systems as a responsible manu-
facturer highly recommends that carbon monox-
ide detector(s) be installed indoors according to
the manufacturer
'
s instructions/recommendations.
The generator must me mounted safely per appli-
cable codes and the manufacturer
'
s specifica-
tions. Do NOT alter or add to the exhaust syst em,
or do anything that might render the exhaust sys-
tem unsafe or in noncompliance with applicable
codes and standards.
1.11.2 INSTALLATION GUIDELINES FOR EATON
STATIONARY AIR-COOLED 8, 10, 14, 17 AND
20 KW GENERATORS.
The
N
ational Fire Protection Association has a standard for the
inst allation and use of st ationary co
m
bustion engines. That
standard is
N
FPA 37 and its require
m
ents li
m
it the spacing of an
enclosed gene rator set fro
m
a structure or wall
(
Figur e 1.10
)
.
N
FPA 37,
S
ection 4.1.4, E ngines
L
ocat ed
O
utdoors. Engines, and
their weatherproof housings if provid ed, t hat are inst alled outdoors
shall be locate d at least 5 ft. fro
m
openings in walls and at least 5
ft. fro
m
structures having co
m
bustible walls. A
m
ini
m
u
m
separa-
tion shall not be requ ired where the following conditions exist:
1. The adjacent wall o f t he structure has a fire resistance rating
of at least 1 hour.
2. The weatherproof enclosure is constructed of nonco
m
bus-
tible
m
aterials and it has been de
m
onstrated that a fire within
the en cl osure will not ignite co
m
bustible
m
aterials outside t he
enclosure.
Annex A Explanatory Material
A4.1. 4
(
2
)
Means of de
m
onst rating co
m
pliance are by
m
eans
of full scale fire test or by calculation procedures.
Because of the li
m
ited spaces that are freque ntly available for
instal lation, it has beco
m
e apparent that exception
(
2
)
would be
beneficial for
m
an y residential and co
mm
ercial installations.
W
ith
that in
m
ind, the
m
anufacturer contracted with an inde pendent
testing laboratory to run full sca le fire tests to assure that the
Eaton enclosure woul d not ignite co
m
bustible
m
aterials outside
the enclosure.
The criteria was to d eter
m
ine the worst ca se fire scenario within
the generator and to deter
m
ine the ignitability of ite
m
s outside
the engine enclosure at various distances. The Eaton enclosure
is constructed of non-co
m
bustible
m
aterials and the results and
c onclusi ons fro
m
the independent testing lab indicated that any
fire within the generator enclosure would not pose any ignition risk
to nearby co
m
bustibles or structures, with or without fire service
personnel response.
Based on this testing and the require
m
ents of
N
FPA 37,
S
ec 4.1.4,
the gu idelines for installation of the generators listed above are
c hanged to 18 inches
(
457
mm
)
fro
m
the back side of the genera-
tor t o a stationary wall or building. For adequate
m
aintenance a nd
air flow clearance, the area above the generator should be at least
4 feet with a
m
ini
m
u
m
of 3 feet at the front and ends of the enclo-
sure. This would include trees, shrubs and vegetation that could
obstruct air flow.
S
ee the diagra
m
on the reverse of this page and
the installation drawing within the owners
m
anual for detail s.
G
enerator exhaust contains
D
EA
D
L
Y carbon
m
onoxide gas. This
dangerous gas can cause unconsciousness or death.
D
o not place
the un it near windows, doors, fresh air in takes
(
furnaces, etc.
)
or
an y openings in the building or str ucture, including windows and
doors of an attached garage.
Section 1 General Information
Air-cooled Generators
12
Section 1 General Information
Air-cooled Generators
Figure 1.10 Install ation Guidelines
18 inches
Minimum Distance
36 inches
36 inches
36 inches
60 inches 60 inches
Existing Wall
No windows or openings in the wall permitted
within 5 feet from any point of the generator.
Top o f Ge n er a to r
48” Minimum
60” Recommended
Minimum From Ends
18 inches
Minimum
Generator
Clearance from windows,
doors, any openings in the
wall, shrubs or vegetation
over 12” in height
Clearance from the ends and front of the
generator should be 36 inches. This
would include shrubs, trees and any
kind of vegetation. Clearance at the top
should be a minimum of 48 inches from
any structure, overhang or projections
from the wall. The generator should not
be placed under a deck or other
structure that is closed in and would limit
or contain air flow.
These guidelines are based upon fire
testing of the generator enclosure and
the manufacturers requirement for air
flow for proper operation. Local codes
may be different and more restrictive
than what is described here.
This drawing supersedes installation instructions in all Carrier air-cooled installation and owner’s manuals dated
previous to May 26, 2007.
13
1.12 BATTERY REQUIREMENTS
S
ee the
S
pecifications section for correct battery size and rating
If the AUTO/OFF/MANUAL switch is not set to its
OFF position, the generator can crank and start
as soon as the battery cables are connected. If
the utility pow er supply is not turned off, spark-
ing can occur at the battery posts and cause an
explosion.
1.13 BATTERY INSTALLATION
Fill the battery with the prope r electrolyte fluid if necessary and
have the battery fully charged before installing it.
Before instal ling and connecting the battery, co
m
plete the follow-
ing steps:
1.
S
et the generator
'
s A
U
T
O
/
O
FF/MA
N
U
A
L
switch to
O
FF.
2. Turn off utility power supply to the transfer switch.
3.
R
e
m
ove the 7.5A fuse fro
m
the generator control panel.
Battery cables were factory connected at the generator
(
Figur e
1.11
)
. Connect cables to battery posts as follows:
4. Connect the red battery cab le
(
fro
m
star ter contactor
)
to the
battery post indicated by a p ositive, P
O
S
or
(
+
)
.
5. Connect the black battery cable
(
fro
m
fra
m
e ground
)
to the
battery post indicated by a negative,
N
E
G
or
(
)
.
Figure 1.11 Battery Cable Connections
NOTE:
Dielectric grease should be used on battery posts to
aid in the prevention of corrosi on.
NOTE:
Damage will result if battery connec ti ons are made
in reverse.
NOTE:
In areas where temperatures regularly fall below 10
°
F (-12
°
C) it is recommended that a pad type battery
heater be installed to aid in cold climate starting.
1.14 THE BATTERY
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and hi gh short circuit current. The following pre-
cautions are to be observed when working on
batteries:
Remove the 7.5A fuse from the generator control
panel.
Remove watches, rings or other metal objects;
Use tools with insulated handles;
Wear rubber gloves and boots;
Do not lay tools or metal parts on top of the
battery; and
Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.
The electrolyte is a dilute sul furic acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive.
The following procedures are to be observed:
Wear full eye protection and prot ective clothing;
Where electrolyte contacts the skin, wash it off
immediately with water;
Where electrolyte contacts the eyes, flush thor-
oughly and immediately with water and seek medi-
cal attention; and
Spilled electrolyte is to be washed down wi th an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) of water. The bicar-
bonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead-acid batteries present a risk of fire
because they generate hydrogen gas. The fol-
lowing
procedures are to be followed:
DO NOT SMOKE when near the battery;
DO NOT cause flame or spark i n battery area; and
Discharge static electricity from body before
t ouching the battery by first touching a grounded
metal surface.
Section 1 General Information
Air-cooled Generators
14
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as
the battery cables are connected.
Be sure the utility power supply is turned off
and the 7.5A fuse is removed from the generator
control panel, or sparking may occur at the bat-
tery posts as the cables are attached and cause
an explosion.
S
ervicing of the battery is to be per for
m
ed or supervised by per-
sonnel knowledgeable o f batteries and the required precautions.
Keep unauthorized personnel away fro
m
batteries.
S
ee the
S
pecifications section for the correct size and rating when
replacing the battery.
H
ave these procedures per for
m
ed at the
intervals spe cified in the
S
ervice
S
c hedule. A nega tive ground
syste
m
is used. Battery connections are shown on the wiring dia-
gra
m
s. Make sure t he battery is correctly connected and ter
m
inals
are tight.
O
bser ve batt ery polarity when connecting the battery to
the generator set.
1.15 BATTERY CHARGER
NOTE:
These generators DO NOT contain an internal battery
charger.
NOTE:
The manufacturer provides a battery trickle charger
that is active when the unit is set up for automatic
operation. With the battery installed and ut ility power
source voltage available to the transfer switch, the
battery recei ves a trickle charge to prevent self-
discharge. The trickle charger is designed to help
extend the life of the battery by maint aining the bat-
tery. The trickle charge feature cannot be used to
recharge a discharged battery.
A separate bat tery charger
m
odule is included with the generator.
(
For battery charger installation, see th e
G
enerator Install
G
uidelines
included with the unit.
)
2.1 BEFORE INITIAL START-UP
NOTE:
These units have been run and tested at the factory
prior to being shipped and do not require any type
of break-in.
Before star ting, co
m
plete the following:
1.
S
et the generators
m
ain circuit bre aker to its
O
FF
(
or
O
PE
N
)
position.
2.
S
et the genera tor
'
s A
U
T
O
/
O
FF/MA
N
U
A
L
switch to the
O
FF
position.
3. Turn
O
FF all loads connected to the transf er switch ter
m
inals
T1 and T2.
4. Check the engine cra nkcase oil level and, if necessary, fi ll to
the d ipstick F
U
LL
m
ark with the r eco
mm
ended oil.
D
o not fill
above the F
U
LL
m
ark.
5. Check the fuel sup ply.
G
a seous fuel lines
m
ust ha ve been
properly purged and leak tested in accordance with applicable
fuel-gas codes. All fuel shutoff valves in the fuel supply lines
m
ust be open.
D
uring initial star t up only, the generat or
m
a y exceed the nor
m
al
nu
m
ber of star t atte
m
pts and experience an ove r crank fault
(
S
ee
the
"
O
vercran k
"
section
)
. This is due to accu
m
ulated air in the fuel
syste
m
during installation.
R
eset the control board and restar t up
to two
m
ore ti
m
es, if necessary. If unit fails to star t, contact the
loca l dealer for assistance.
Never operate the engine with t he oil level
below the Add mark on the dipstick. Doing this
could damage the engine.
2.2 ELECTRICAL CHECKS
Co
m
plete electrical checks as follows:
1.
S
et the g enerator
'
s
m
ain circuit breaker to its
O
FF
(
or
O
PE
N
)
position.
2.
S
et the genera tor
'
s A
U
T
O
/
O
FF/MA
N
U
A
L
switch to the
O
FF
position.
3. Turn
O
FF all loads connected to the transf er switch ter
m
inals
T1 and T2.
4. Turn on the utilit y power supply to the transfer switch using
the
m
eans provided
(
such as a utility
m
ain line circuit break-
er
)
.
DANGER
The transfer switch is now electrically hot.
Contact with hot parts will result in extremely
hazardous and possibl y fatal electrical shock.
Proceed with caution.
5.
U
se an accurate AC volt
m
eter to check uti lity power source
volt age across transfer switch ter
m
inals
N
1 and
N
2.
N
o
m
inal
line -to-line voltage shoul d be 240 volts AC.
6. Check utility power source voltage across ter
m
inals
N
1 and
the transfer switch neutral lug; then across ter
m
inal
N
2 and
neutral.
N
o
m
inal li ne-to-neutral voltage should be 120 volts
AC.
7.
W
hen cer tain that utility supply voltage is co
m
patible with
transfer switch and load circuit ratings, turn
O
FF the utility
power supply to the transfer swit ch.
8.
O
n the generator panel, set the Auto/
O
ff/ Ma nual switc h to
MA
N
U
A
L
. The engine should crank and star t.
9.
L
et the e ngine war
m
up for about five
m
inutes to allow inte r-
nal te
m
peratures to stabilize. Then, set the generators
m
ain
cir cuit breaker to its
O
N
(
or closed
)
position.
DANGER
Proceed with caution! Generator power voltage
is now supplied to the transfer switch. Contac t
with live transfer switch parts wi ll result in dan-
gerous and possibly fatal electrical shock.
Section 2 Post Installation Start-up and Adjust ments
Air-cooled Generators
15
10. Connect an accurat e AC volt
m
eter and a frequency
m
eter
across transfer switch ter
m
inal lugs E1 and E2. 8k
W
voltage
should be 230-240 volts at a frequency of 61-63
H
er tz. 14,
17 and 20k
W
voltage should be 247-249 at a frequency of
59.5-60.5
H
er tz. 10k
W
voltage should be 220-230 volts at a
frequency of 59.5-60.5
H
er tz.
11. Connect the AC volt
m
eter test leads across ter
m
inal l ugs E1
and neutral; then across E2 and neutral. In both cases, volt-
age reading should be 121-126 volts AC
(
8k
W
)
, and 125-126
volts AC
(
10, 14, 17 and 20k
W
)
.
12.
S
et the generators
m
ain circuit bre aker to its
O
FF
(
or
O
PE
N
)
position.
L
et the engine run at no-load for a few
m
inutes to
stabilize internal engine generat or te
m
peratures.
13.
S
et the generat or
'
s A
U
T
O
/
O
FF/MA
N
U
A
L
switch to
O
FF. The
engine should shut down.
NOTE:
It is important not to proceed unt il certain that gener-
ator AC voltage and frequency are correct and within
the stated limits. Generally, if both AC frequency and
voltage are high or low, the engine governor requires
adjustment* (*GH410 only). If frequency is correct,
but voltage is high or low, the generators voltage
regulator requires adjustment.
2.3 GENERATOR TESTS UNDER LOAD
To test the generator set with electrical loads app lied, proceed as
follows:
1.
S
et generators
m
ain circuit breaker to its
O
FF
(
or
O
PE
N
)
posi -
tion.
2. Turn
O
FF all loads connected to the transf er switch ter
m
inals
T1 and T2.
3.
S
et the generator
'
s A
U
T
O
/
O
FF/MA
N
U
A
L
switch to
O
FF.
4. Turn
O
FF the utility power supply to the transfer switch,
using the
m
eans provided
(
such as a utility
m
ain lin e circuit
breaker
)
.
Do not attempt manual transfer switch operation
until all power voltage supplies to the transfer
switch have been positively turned off. Failure to
turn off all power voltage supplies will result in
extremely hazardous and possibly fatal electri-
cal shock.
5. Manually set the transfer switch to the
S
TA
N
D
BY posi tion, i.e.,
load ter
m
inals connected to the generator
'
s E1/E2 ter
m
inals.
The transfer switc h operating lever should be down.
6.
S
et the generator
'
s A
U
T
O
/
O
FF/MA
N
U
A
L
switch t o MA
N
U
A
L
.
The engine should crank and star t i
mm
edi ately.
7.
L
et the engine stabilize and war
m
up for a few
m
inutes.
8.
S
et th e generators
m
ain cir cuit breaker to its
O
N
(
or C
L
O
S
E
D
)
position.
L
oads are now powered by the sta ndby generator.
9. Turn
O
N
the load center fed by the transfer switch
(
T1 and
T2
)
.
10. Connect an accurat e AC volt
m
eter and a frequency
m
eter
across ter
m
inal lugs E1 and E2.
8k
W
volt age should be g reater than 230 volts and frequency
should be greater than 58
H
z.
10, 14, 17 and 20k
W
voltage should be greater than 240 volts
and frequency should be 60
H
z.
11.
L
et the generator run at full rated load for 20-30
m
inutes.
L
isten for unusual noises, vibration or other indications of
abnor
m
al operation. Check for oil leaks, evidence of overheat-
ing, etc.
12.
W
hen testing under l oa d is co
m
plete, turn
O
FF el ectrical
loads.
13.
S
et the g enerator
'
s
m
ain circuit breaker to its
O
FF
(
or
O
PE
N
)
position.
14.
L
et the engine run at no-load for a few
m
inutes.
15.
S
et the A
U
T
O
/
O
FF/MA
N
U
A
L
switch to
O
FF. The engine should
shut down.
2.4 CHECKING AUTOMATIC OPERATION
To check the syste
m
for proper auto
m
atic operation, proceed as
follows:
1.
S
et generators
m
ain circuit breaker to its
O
FF
(
or
O
PE
N
)
posi -
tion.
2. Check that the A
U
T
O
/
O
FF/MA
N
U
A
L
switch is set to
O
FF.
3. Turn
O
FF the utility power supply to the transfer switch, using
m
eans provided
(
such as a utility
m
ain line circuit breaker
)
.
4. Manually set the transfer switch to t he
U
TI
L
ITY position, i.e.,
load ter
m
inals connected to the utility power source side.
5. Turn
O
N
the utility power supply to the transfer switch,
using the
m
eans provided
(
such as a utility
m
ain line circuit
breaker
)
.
6.
S
et the generator
'
s
m
ain circuit breaker to its
O
N
(
or C
L
O
S
E
D
)
position.
7.
S
et the A
U
T
O
/
O
FF/MA
N
U
A
L
switch to A
U
T
O
. The syste
m
is
now read y for auto
m
atic operati on.
8. Turn
O
FF the utili ty p ower supply to the transfer switch.
W
ith the A
U
T
O
/
O
FF/MA
N
U
A
L
switch at A
U
T
O
, the engine should
c rank and star t when the utility source power is turned
O
FF after a
10 second delay. After sta r ting, the transfer switch should connect
load circuits to the standby side after a 20 to 50 second selectable
dela y.
L
et t he syste
m
go through its entire auto
m
atic sequence of
operation.
W
ith the generator running and load s powe red by generator AC
output, turn
O
N
the utility power supply to the transfer switch. The
following should occur:
After about 10 seconds, the switch should transfer loads back
to the utility power source.
About one
m
inute after re-transfer, the engine should shut
down.
Section 2 Post Installation Start-up and Adjust ments
Air-cooled Generators
16
2.5 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly high or low,
adjust th e engine governor as follows:
2.5.1 8 KW UNITS
The engine must be OFF to perform steps 1 and
2.
1.
L
oosen the governor cla
m
p bolt
(
Figur e 2.1
)
.
2.
H
old the governor lever at its wide open throttle position
(
clockwise
)
, and rotate the governor sha ft clockwise as far
a s it will go. Then, tighten the governor lever cla
m
p bolt to 70
inch-pounds
(
8
N
-
m
)
.
3.
S
tar t t he gen erator; let it stabilize and wa r
m
up at no-load.
4. Connect a f req uency
m
eter across t he generators AC output
leads.
Figure 2. 1 Engine Governor Adjustment
Single Cylinder Engines
GOVERNOR
SHAFT
PRIMARY
ADJUST
SCREW
GOVERNOR
CLAMP
BOLT
SECONDARY
ADJUST SCREW
5. Turn the p ri
m
ary adjust screw to obtain a frequency reading
of 61.5
H
er tz. Turn the sec ondar y adjust screw to obtain a
frequency of 62.5
H
z.
2.5.2 10, 14, 17 & 20KW UNITS
NOTE:
All V-twin units DO NOT require an engine governor
adjustment due to t heir design.
2.5.3 ADDITIONAL CORROSION
PROTECTION
Periodically spray all engine linkage par ts and brackets with corro-
sion inhibiting spray such as
W
D
-40 or a co
m
parable product.
2.6 VOLTAGE REGULATOR
ADJUSTMENT
2.6.1 8 & 10KW UNITS
D
ue to the brushless de sign of these two alternators, no voltage
regulator is use d and therefore no voltage adjust
m
ent is re quired.
2.6.2 14, 17 & 20KW UNITS
W
ith the f req uency between 59.5 -60.5
H
er tz at no-load, slowly
turn the slot ted p otentio
m
eter
(
Figur e 2.2
)
until line voltage reads
247-249 volts.
Figure 2. 2 Voltage Adjust ment Potentiometer
Turn to
adjust voltage.
NOTE:
The access panel on top of t he control panel must be
removed to adjust the voltage regulator.
NOTE:
The voltage regulator is housed behind the genera-
t or
'
s control panel. The regulator maintains a voltage
in direct proportion to frequency at a 2-to-1 ratio. For
example, at 60 Hertz, line-to-neutral vol tage will be
124 volts.
Section 2 Post Installation Start-up and Adjust ments
Air-cooled Generators
17
Section 3 Operation
Air-cooled Generators
3.1 CONTROL PANEL INTERFACE
3.1.1 USING THE AUTO/ OFF/MANUAL SWITCH
(FIGURES 3.1 & 3.2)
1. A
U
T
O
Position
S
electing this switch activates fully auto-
m
atic syste
m
operation. It also allows the unit to auto
m
ati-
cally star t and exercise the engine every seven days with the
setting of the exercise ti
m
er
(
see the
S
etting the Exercise
Ti
m
er section
)
.
2.
O
FF Position This switch position shuts down the engine.
This position also preven ts auto
m
atic operati on.
3. MA
N
U
A
L
Position
S
et the switch to MA
N
U
A
L
to cra nk
and star t the engine. Transfer to standby power will not occur
unless there is a utility failure.
Figure 3. 1 8kW Generator Control Panel
SET
EXERCISE
SYSTEM READY
LOW BATTERY
LOW OIL PRESSURE
HIGH OIL TEMPERATURE
OVERSPEED
RPM SENSOR LOSS
OVERCRANK
With the switch set to AUTO, the engine may
crank and start at any time without warning.
Such automati c starting occurs when utility
power source voltage droops below a preset
level or during the normal exercise cycle. To
prevent possible injury that might be c aused
by such sudden starts, always set t he switch to
OFF and remove the fuses before working on or
around the generator or transfer switch. Then,
place a DO NOT OPERATE tag on the genera-
t or panel and on the transfer switch.
Figure 3. 2 10/14/17 & 20kW Generator Control
Panel
ENTER
ECS
3.1.2 SETTING THE EXERCISE TIMER
This generator is equipped with an exercise ti
m
er.
O
nce it is set,
the generator will star t and exerci se every seven d ays, on the day
of the week and at the ti
m
e of day specified.
D
uring this exe rcise
period, the unit runs for approxi
m
ately 12
m
inutes and then shuts
down. Transfe r of loads to the generator outpu t doe s not occur
duri ng the exercise cycle unless utility powe r is lost.
8kW
A switch on the control panel
(
see Fig ure 3.1
)
per
m
its selection of
the day and ti
m
e for the syste
m
to exercise. At the chosen ti
m
e,
per for
m
the f ollowing sequence to select the desired day and ti
m
e
of day the syste
m
will exercise.
R
e
m
e
m
ber season al ti
m
e changes
affect the exercise settings.
1. Verify that the A
U
T
O
/
O
FF/MA
N
U
A
L
switch is set to A
U
T
O
.
2. Press and hold the
S
et Exercise switch for several seconds.
All the red
L
E
D
s will stop flashing i
mm
edi ately and the ge n-
erator will star t.
3. The gen erator will star t and run for approxi
m
ately 12
m
inutes
and then shut down. The exerciser is now set to run at this
ti
m
e of day each week.
Example: If the
S
et Exercise pressed on
S
aturday afternoon at
2:00 p.
m
., the generator will star t and exercise for approxi
m
ately
12
m
inutes every
S
aturday at 2:00 p.
m
.
NOTE:
The exerciser will only work in the AUTO mode and
will not work unless this procedure is performed.
The exerciser will need to be reset every time the 12
volt battery is disconnected and then reconnected,
and when the fuse is removed and/or replaced.
18
10 to 20 KW - INSTALLATION ASSISTANT
U
pon f irst power up of the generator, the display inter face will
begin an installation assistant. The assistant will pro
m
pt the user
to set the
m
ini
m
u
m
settings to operate. These settings are si
m
-
ply: Cur rent
D
ate/Ti
m
e and Exercise
D
a y/Ti
m
e. The
m
aintenance
intervals will be initialized when the exercise ti
m
e is entered
(
Figur e
3.2
)
.
The exe rcise settings can be changed at any ti
m
e via t he
"
E
D
IT
"
m
enu
(
see Appendix,
"
Menu
S
yste
m
"
)
.
If the 12 vo lt battery is disconnected or t he fuse re
m
oved, the
Installation Assistant will operate upon powe r restoration. The
only difference is the di splay will only pro
m
pt the custo
m
er for the
c urrent Ti
m
e and
D
ate.
IF THE INSTALLER TESTS THE GENERATOR PRIOR
TO INSTALLATION, PRESS THE ENTER KEY TO
AVOID SETTING UP THE EXERCISE TIME. THIS WILL
ENSURE THAT WHEN THE CUSTOMER POWERS UP
THE UNIT, HE WILL STILL BE PROMPTED TO ENTER
AN EX ERCI SE TIME.
NOTE:
The exerciser will only work in the AUTO mode and
will not work unless this procedure is performed.
The current date/time will need to be reset every ti me
the 12 volt battery is disconnected and then recon-
nected, and/or when the fuse is removed.
3.1.3 DISPLAY INTERFACE
8 kW LED Display
S
even
(
7
)
L
E
D
s are p rovided f or user status indications. The
L
E
D
functions are:
1.
S
yste
m
R
eady
(
green
)
2.
L
ow Batter y
(
red
)
3.
L
ow
O
il Pressure
(
red
)
4.
H
igh
O
il Te
m
perature
(
red
)
5.
O
ver
S
peed
(
red
)
6.
R
PM
S
ensor
L
oss
(
red
)
7.
O
ver Crank
(
red
)
S
ee the Protection
S
yste
m
s section for details.
10 to 20KW DISPLAY INTERFACE MENUS
The
L
C
D
display is organized as detailed below:
The
H
o
m
e page, t his page is the default page which will be
displayed if no keys are pressed for 30 seconds. This page
nor
m
ally shows the current
S
tatus
m
essage and the current
date and ti
m
e. The highest priority activ e Alar
m
and/or
W
arning
will be auto
m
atical ly post ed on this page as well as flashing
the backlight when suc h a n event is detected. In the case of
m
ultipl e Alar
m
s or
W
arning s, only the first
m
essage will be
displayed. To clear an Alar
m
or
W
arning, see the Protection
S
yste
m
s section - Clear Alar
m
.
The display backlight is nor
m
ally o ff. If the user presses any
key, the backlight will co
m
e on auto
m
atical ly and r e
m
ain on for
30 seconds after the last ke y was pressed.
The Main Menu page will allow the user to navigate to all other
pages or sub-
m
enus by using the
L
eft/
R
ight and Ente r keys.
This page ca n be accessed at any ti
m
e with several presses of
the dedicated Escape key. Each press of the Escape key takes
you back to the previous
m
enu until the
m
ain
m
enu is reached.
This page displays the following options:
H
I
S
T
O
R
Y;
S
TAT
U
S
;
E
D
IT; A
N
D
D
EB
U
G
.
(
S
ee the Appendix -
"
Menu
S
yste
m
"
.
)
3.2 AUTOMATIC TRANSFER OPERATION
To select auto
m
atic operati on, do the following:
1. Make sure the transfer swit ch
m
ain contacts are set to their
U
TI
L
ITY position, i.e., loads connected to the utility power
source
(
Figur e 3.2
)
.
2. Be sure that nor
m
al
U
TI
L
ITY power sour ce voltage is avail -
able to transfer switch ter
m
inal lugs
N
1 and
N
2
(
R
efer to the
Electrical
D
ata section
)
.
3.
S
et the generators A
U
T
O
/
O
FF/MA
N
U
A
L
switch to A
U
T
O
.
4.
S
et th e generators
m
ain cir cuit breaker to its
O
N
(
or C
L
O
S
E
D
)
position.
W
ith the preceding steps co
m
plete, the generator will star t auto-
m
atical ly when utility source voltage drops be low a preset level.
After the unit star ts, loads are transferred to the standby power
source.
R
efer to the
S
eq uence of Au to
m
atic
O
peration section.
3.3 SEQUENCE OF AUTOMATIC OPERATION
3.3.1 UTILITY FAILURE
Initial Conditions:
G
enerator in Auto, ready to run, load being sup-
plied by utility source.
W
hen utility fails
(
below 70% of no
m
inal
)
,
a 10 second line interrupt delay ti
m
e is star ted. If the utility is stil l
gone when the ti
m
er expires, the engine will crank and star t.
O
nce
star ted, a 20 to 50 second selectable engine wa r
m
-up ti
m
er will be
initiated.
W
hen the war
m
-up ti
m
er expir es, the control will transfer
the load to the ge nerator. If the utility power is restored
(
above 80%
of no
m
inal
)
at any ti
m
e f ro
m
the initiation of the engine star t until
the generator is r eady to accept load
(
and the war
m
-up ti
m
e has
not elapsed
)
, the controller will co
m
plete the star t cycle and run
the generator through its nor
m
al cool down cycle ; however, the
load will re
m
ain on the utility source.
3.3.2 CRANKING
The syste
m
will control the c yclic cranking as follows: 16 se cond
c rank, seven
(
7
)
sec ond rest, 16 second crank, seven
(
7
)
sec ond
rest followed by three
(
3
)
addi tional cycles of seven
(
7
)
second
c ranks followed by seven
(
7
)
second rests.
Choke Operation
1. The 990/999cc engines have an electric choke in the air
box that is auto
m
atical ly controlled by the electronic control
board.
2. The 530cc engines have an el ectric choke on the divid er panel
air inlet hose that is auto
m
atical ly controlled by the electronic
c ontrol board.
3. The 410cc engines have a choke behind the air box that is
auto
m
atical ly control led by the electronic control board.
Section 3 Operation
Air-cooled Generators
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

Eaton 17KW Owner's manual

Category
Power generators
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI