Danfoss 013-7045 Installation guide

Type
Installation guide
1 Installation in Convector
Built-in valve, type RA-N, code no. 013G8370
Max.
70°C
Min. 120 mm
Lubricate valve insert by dipping in water. Insert the built-in valve into the steel valve housing
x 12
30Nm
10Nm
Fasten built-in valve with a torque of 30 Nm +/- 10%. 21M spanner. Fasten air-vent with a torque of 10 Nm +/- 10%. 13M spanner.
5. Fit protection cap. Tighten cap.
Installation Guide
Steel Valve with Air-Vent for Convectors
Danfoss Heating Solutions VIFOF102
1
2 Replacement of Gland Seal
1)
2)
10 Nm
Replace the gland seal, code no. 013L0669. Can be done without draining the
heating system.
1)
17M spanner for fixing the setting dial,
2)
10M spanner.
Test operation of valve spindle, by pushing the pin.
Installation Guide Steel Valve with Air-Vent for Convectors
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective
companies. Danfoss Heating Solutions and the Danfoss Heating Solutions logotype are trademarks of Danfoss A/S. All rights reserved.
013R9570 & VIFOF102 Produced by Danfoss Heating Solutions © 11/2012
  • Page 1 1
  • Page 2 2

Danfoss 013-7045 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI