Akai AUS-12H53R130D2 User manual

Category
Split-system air conditioners
Type
User manual

This manual is also suitable for

N13275
3.50kW INVERTER
Reverse Cycle Split
System Air Conditioner
AUS-12H53R150P9(De3)
Instruction Manual
AFTER SALES SUPPORT
NZ: 0800 836 761
AU: 1300 886 649
PROTECT YOUR WARRANTY
This unit must be installed by a registered, licensed installer as required
by Government regulations.
FOR THE INSTALLER
Contents
1 Safety rules and recommendations for the Installer
2 Safety rules and recommendations for the User
4 Safety rules and prohibitions
5 Selecting the
installation place
- Installation diagrams
7 - Location of the Indoor unit
- Location of the Outdoor unit
7 Installation of the
Indoor unit
- Securing the mounting plate
on the wall
8 - Drilling the wall
9- Wiring
10 - Attaching the indoor unit to
the mounting plate
11 - Pipe connection
- Arrangement of the drain hose
12 - Wall sealing and Pipe fastening
13 Installation of the
Outdoor Unit
- Wiring
15 - Connection diagram
16 - Installation of the drain joint
17 - Join the connecting pipe
- Air exhausting
18 - Process of ared tubing
19 - Adding refrigerant
20 Operation test
1
Safety rules and recommendations for the Installer
Please keep this instruction manual in a safe place, along with the warranty card,
purchase receipt and carton for future reference.
• Read this guide before installing and using the appliance.
• During the installation of the indoor and outdoor units, access to
the working area should be forbidden to children.
Unforeseeable accidents could happen.
Make sure that the base of the outdoor unit is rmly xed.
• Check that air cannot enter the refrigerant system and check for refrigerant
leaks when moving the air conditioner.
• Carry out a test cycle after installing the air conditioner and record the
operating data.
• The ratings of the fuse installed in the built in control unit are 3.15A / 250V for
220V type and 3.15A/125V for 110V type.
• The user must protect the indoor unit with a fuse of suitable capacity for the
maximum input current or with another overload protection device.
• Ensure that the mains voltage corresponds to that stamped on the rating
plate. Keep the switch or power plug clean. Insert the power plug correctly and
rmly into the socket, thereby avoiding the risk of electric shock or re due to
insucient contact.
• Check that the socket is suitable for the plug, otherwise have the
socket changed.
• Do not install the appliance at a distance of less than 50cm from inammable
substances (alcohol, etc.). Or from pressurised containers (e.g. spray cans).
• If the appliance is used in areas without the possibility of ventilation,
precautions must be taken to prevent any leaks of refrigerant gas
from remaining in the environment and creating a danger of re.
• The packaging materials are recyclable and should be disposed of in the
separate waste bins. Take the air conditioner at the end of its
useful life to a special waste collection centre for disposal.
• Only use the air conditioner as instructed in this booklet. These instructions are
not intended to cover every possible condition and
situation. As with any electrical household appliance, common sense and
caution are therefore always recommended for installation, operation and
maintenance.
• The appliance must be installed in accordance with applicable
national regulations.
• Before accessing the terminals, all the power circuits must be disconnected
from the power supply.
2
• The appliance must be installed 2.5m above the oor
Safety rules and recommendations for the User
Please keep this instruction manual in a safe place, along with the warranty card,
purchase receipt and carton for future reference.
• Do not try to install the conditioner alone; always contact specialised technical
personnel.
• Cleaning and maintenance must be carried out by specialised technical
personnel. In any case disconnect the appliance from the mains electricity
supply before carrying out any cleaning
or maintenance.
• Ensure that the mains voltage corresponds to that stamped on the rating
plate. Keep the switch or power plug clean. Insert the power plug correctly and
rmly into the socket, thereby avoiding the risk of electric shock or re due to
insucient contact.
• Do not pull out the plug to switch o the appliance when it is in operation,
since this could create a spark and cause a re, etc.
• Never remain directly exposed to the ow of cold air for a long time. The direct
and prolonged exposition to cold air could be dangerous
for your health. Particular care should be taken in the rooms where there are
children, old or sick people.
• If the appliance gives o smoke or there is a smell of burning, immediately cut
o the power supply and contact the Service Centre.
• Have repairs carried out only by an authorised Service Centre of the
manufacturer. Incorrect repair could expose the user to the risk of electric
shock, etc. The prolonged use of the device in such conditions could cause re
or electrocution.
• This appliance has been made for air conditioning domestic environments and
must not be used for any other purpose, such as for drying clothes, cooling
food, etc.
• The packaging materials are recyclable and should be disposed of in the
separate waste bins . Take the air conditioner at the end of its useful life to a
special waste collection centre for disposal.
• Always use the appliance with the air lter mounted. The use of the conditioner
without air lter could cause an excessive accumulation of dust or waste on the
inner parts of the device with possible subsequent failures.
• The user is responsible for having the appliance installed by a qualied
technician, who must check that it is earthed in accordance with current
3
legislation and insert a thermomagnetic circuit breaker.
• Unhook the automatic switch if you foresee not to use the device for a long
time. The airow direction must be properly adjusted.
• The aps must be directed downwards in the heating mode and upwards in
the cooling mode.
• Only use the air conditioner as instructed in this booklet. These instructions
are not intended to cover every possible condition and situation. As with any
electrical household appliance, common sense and caution are therefore
always recommended for installation, operation and maintenance.
• Ensure that the appliance is disconnected from the power supply when it will
remain inoperative for a long period and before carrying out any cleaning or
maintenance.
• Selecting the most suitable temperature can prevent damage to the appliance.
4
Safety rules and prohibitions
• Do not bend, tug or compress the power cord as this could damage it. Electrical
shocks or re are usually due to a damaged power cord. Only specialised
technical personnel must replace a damaged power cord.
• Do not use extensions or gang modules.
• Do not touch the appliance when barefoot or parts of the body are wet or damp.
• Do not obstruct the air inlet or outlet of the indoor or the outdoor unit. The
obstruction of these openings causes a reduction in the operative eciency of
the conditioner with possible consequent failures or damages.
• In no way alter the characteristics of the appliance.
• Do not install the appliance in environments where the air could contain gas, oil
or sulphur or near sources of heat.
• This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
• Do not climb onto or place any heavy or hot objects on top of the appliance.
• Do not leave windows or doors open for long when the air conditioner
is operating.
• Do not direct the airow onto plants or animals.
• A long direct exposition to the ow of cold air of the conditioner could have
negative eects on plants and animals.
• Do not put the conditioner in contact with water. The electrical insulation could
be damaged and thus causing electrocution.
• Do not climb onto or place any objects on the outdoor unit.
• Never insert a stick or similar object into the appliance.
It could cause injury.
• Children should be supervised to ensure that they do not play with the
appliance. If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualied persons in order to avoid a
hazard.
5
Selecting the installation place
Installation diagrams
IMPORTANT: Only persons and/or companies qualied and experienced in the
installation, service and repair of refrigerant products should be permitted to do
so. The purchaser must ensure that the person and/or company who is to install,
service or repair this air conditioner has qualications and experience in refrigerant
products.
NOTE: Installation location notes are found on pg. 7.
NOTE: The gures of the air conditioner and its working parts (above and right) are only
intended to be a simple diagram of the appliance and may not correspond to the appearance
of the units that have been purchased.
Please always refer the actual product purchased while using these instructions.
A
B
TO INDOOR UNIT
above
500mm
above
300mm
above
300mm
above 500mm
Above 500mm
TO
6
While installing the
pipeline on the thin
armor plate or on the
wall of metal mesh, you
should use a wooden
board to clamp between
the wall and the pipeline
or wrap the pipeline with
7–8 layers of insulating
plastic tape.
IMPORTANT: The allowable length of the connecting
pipe is 10m. The allowable distance between the
indoor unit and outdoor unit is 5m.
Cover connecting pipe
with adiabatic material.
Sponge plastic adiabatic
material with the
thickness of 8mm.
Conrm the installation
position by the mark of the
indoor mounting plate.
NOTE: Do not raise the
drain hose.
The connecting pipe can
be led from the back, right,
underside or
back-left side.
front
left
back
left
underside
back
back
right
Indoor unit
7
1. Location of the Indoor unit
• Keep the air inlet and outlet at a far distance from the blockage.
• Keep the height distance between the indoor and outdoor unit at most 5m.
• Mount securely on a wall solid enough to bear the weight of the unit. Ensure
that the wall chosen is not subject to vibration or shaking.
• Avoid direct sunshine.
• Condensate drain must sit comfortably and be easy for connecting with the
outdoor unit.
• Keep a far distance away from uorescent light; it may inuence the operation of
remote controller.
• Keep at least 1m away from the TV or radio and other home appliances.
2. Location of Outdoor unit
• Do not install the outdoor unit near sources of heat, steam or ammable gas.
• Do not install the unit in very windy or dusty places.
• Do not install the unit where people often pass. Select a place where the air
discharge and the operating sound level will not disturb neighbours.
• Avoid installing the unit where it will be exposed to direct sunlight (other wise use
protection, if necessary, that will not interfere with the air ow).
• Leave the spaces as shown in the picture for the air to circulate freely.
• Install the outdoor unit in a safe and solid place.
• If the outdoor unit is subject to vibration, place rubber gaskets onto the feet of
the unit.
Installation of the Indoor unit
1. Securing the mounting plate on the wall
The mounting plate should be xed to the structural part of the wall (stud).
NOTE:
• The holes at solid arrow position must be secured to avoid the mounting plate
shaking or moving.
• When the expansion bolts are used, two holes (11x20 or 11x26) should have the
distance of 450mm between them adopted.
fasten string at the central hole
105mm or more
from sidewall
Tapping screw
ST4×25(5)
plumb
mounting plate
at least 250mm
from sidewall
155mm or more
8
2. Drilling the wall
• The holes at solid arrow position must be secured to avoid the mounting plate
shaking or moving.
• When the expansion bolts are used, two holes (11x20 or 11x26) should have the
distance of 450mm between them adopted.
• Mark the wall to conrm the position of holes and drill holes on the wall.
Center of hole( ) 65mm
Center of hole( ) 65mm
Pipe hole
9
3. Wiring
1. Open the front grille.
2. Remove the screw from electrical
box cover, pull the electrical box
cover away from the unit and set
aside.
3. Remove the screw from fastener,
pull the fastener away from the
unit and set aside.
4. Connect the cable.
5. Replace the fastener and
electrical box cover.
NOTE:
• The appliance shall be installed in accordance with national wiring regulations.
• The appliance must not be installed in the laundry.
• The appliance must be installed 2.5m above the oor.
• The appliance must be positioned so that the plug is accessible.
• For some models whose cooling capacity are above 4600W (17000BTU/h), an all-pole
disconnection device which has at least 3mm separation distance in all pole and a
residual current device (RCD) with the rating of above 10mA shall be incorporated in
the xed wiring according to the national rule.
4. Installation of the drain hose
• The drain hose must be arranged
beneath the connecting pipe.
• The drain hose must not be hunched
or twisted.
• While wrapping up the drain hose,
do not pull it.
• The drain hose through the room must
be wrapped up by thermal insulation
materials.
• The connecting pipe and the drain
hose must be wrapped up by felt strip.
Adiabatic padding should be used at
where the pipe contacts
the wall.
10
Route of pipe
• If pipe comes out of the right side of the
indoor unit, cut part “1” of the unit;
• If pipe comes out of the lower-right side of
the indoor unit, cut part “2” of the unit;
• If pipe comes out of the left side of the
indoor unit, cut part 3” of the unit.
Ret of drain hose
• If pipe comes out of the left side of the indoor
unit, the drain hose must be retted, otherwise
water leakage may occur.
• Readjustment methods: Interchange the position
of drain hose and drain rubber plug.
• Clearance is not allowed after ret, it would lead
to water leakage.
5. Attaching the Indoor unit to the mounting plate
Let the pipe go through the hole you have made in
the wall and attach the indoor unit to the mounting
plate. Press the rib of indoor unit inside the hook of
the mounting plate.
11
6. Pipe connection
• The number of bent position of the pipe in the indoor unit should not exceed 10.
• The number of bent position of the pipe in the indoor unit and the outdoor unit
should not exceed 15.
• The radius of bent position should be more than 10cm.
• Please break the evaporator craft tube with pincers before connecting. After
exhausting the inside air, use the wrench to twist down the nut of the connecting tube
of the evaporator. (Fig. 1) Put some seal oil to cover the joint and the are.
• Align the centre of joint in line with that of are and tighten the nut of connecting
pipe with wrench. (Fig. 2)
IMPORTANT:
• Do not exhaust the inside air just by loosing the nut as there is a certain amount of
pressure inside the tube of the indoor unit.
• Please do not apply extra eort for fear of damaging the expansion orice.
7. Arrangement of the drain hose
To drain the condensate water easily, the drain hose should be xed to a declined position.
The following 5 arrangement methods are incorrect.
• If you nd the drain hose not long enough to connect
with the indoor unit, you can extend it with the hoses
in the accessory box.
• The drain hose through the room must be wrapped
with special adiabatic material.
12
8. Wall sealing and Pipe fastening
• Use putty to seal the wall hole.
• Use a clamp (pipe fastener) to secure the pipe at specied position.
13
Installation of the Outdoor unit
1. Wiring
Wiring For Above 6000W Model (above 21000BTU/h model)
1. Remove the self-tapping screws (2 pcs) on the maintenance board and take out
the maintenance board.
2. Loosen the self-tapping screws (2 pcs) on the xing clip to loosen the xing clip.
3. Loosen the xing screw of the wire terminal board, pass the power wire and
signal wire through the xing clip. Then rmly x the power wire and signal wire
on the terminal board with the xing screw. (Earth wire must be connected
rmly.)
Single Split Model
Dual Split Model
Connecting
cable
Outdoor unit terminal
Connecting
cable
Outdoor unit terminal
Connecting
cable
Outdoor unit terminal
OR
14
The cable wire can be led from the back hole of the piping hole or ejecting hole.
Please utilize outdoor pipe support when the cable wire is led from the backside.
4. Tighten the self-tapping screw on the xing clip.
5. Install the maintenance board. After the pipes and cable wire are installed,
please seal the sponge block as per drawing indication.
15
Connection diagram
NOTE:
• If not include the connect diagram you need, please see the wiring diagram.
• If you nd that the color of connecting cable does not comply with the top
diagram, please take the actual purchased products as your major reference.
However, the terminal of the same sign must be joint with the connecting cable
of the same color.
• The plug housing 1 is to be connected to the matched receptacle housing of the
indoor unit.
• The plug housing 2 is to be connected to the matched receptacle housing of the
outdoor unit.
• If the signal wire has to be bought separately, choose and electric wire above
0.75mm2.
• If the interconnection cord for power supply has to be replaced, please see the
following table for reference.
IMPORTANT:
• Please take the electric circuit diagram attached to the indoor/outdoor units as
major reference while installing.
• The power wire and signal wire between the indoor/outdoor units must be
connected one by one as per corresponding number on the wiring
terminal board.
• The connecting cables must be clipped together.
L
2
N
L
2A 2B
N
Connecting
cable
Indoor unit A terminal
L
2
N
Yellow/Green
Blue
Brown
Black
Black
Indoor unit B terminal
Outdoor
unit terminal
Connecting
cable
Indoor unit terminal
Outdoor unit terminal
Blue
Brown Black
2
L
N
NL
2
Yellow/Green
Dual Split Model
Power
source
L
2
N
2A 2B
N
Connecting
cable
L
2
N
Yellow/Green
Blue
Brown
Black
Outdoor
unit terminal
Power
source
L
N
L
Blue
Brown
Inverter Type Dual Split Inverter Type
Indoor unit A terminal Indoor unit B terminal
Cool only and heat pump type
Heat pump type
Heat pump type
Plug housing 1
Plug housing 2
16
• Special cable must be used to connect indoor unit and outdoor unit. It should
be ensured that the terminals are not inuenced by external force. Poor
connection may cause re.
• The electric box cover must be mounted and secured in position, otherwise re
or electrical shock may occur because of dust or moisture.
• The temperature of refrigerant circuit will be high. Please keep the
interconnection cable away from the connecting tube.
• All the models shall be connected with the mains which have system impedance
limitations. While installing the unit, please see the following table for
impedance information or consult with your supply authority.
(The following information and specications are subject to change without
prior notice due to continuing research.)
2. Installation of the drain joint
Insert the outdoor double-channel drain joint into one of the bottom holes of the
suitable size then connect the drain hose and join together.
17
3. Join the connecting pipe
• Put some seal oil to cover the joint and the are.
• Align the centre of joint in line with that of the are and tighten the nut of the
connecting pipe with a wrench. (Adjust the torque by the same method of
connecting pipe for the indoor unit.)
4. Air exhausting
• Screw down the cap of both gas
shut-o valve and liquid shut-o
valve as well as the nut of service
port.
• Use an Allen key to turn the valve
cork of the liquid side 90˚ counter-
clockwise, and close it after 10
seconds. Use soapy water to check
the gas leakage especially at all
joints. If there is no gas leakage,
please turn the valve cork of the
liquid side at 90˚ counter-clockwise
again.
• Press the cork of service port at
the gas shut-o valve, 10 seconds
later, when you see a foggy gas
discharged, that means inner air has
exhausted out.
• Use an Allen key to turn the valve
cork of both the liquid shut-o valve
and gas shut-o valve counter-
clockwise until they are completely
open, then replace the valve caps
and tighten them.
NOTE:
Do not vent refrigerant into atmosphere: refrigerant is a uorinated greenhouse gas,
covered by Kyoto protocol, with a Global Warming Potential (GWP) =1900(R410A)/16
00(R407C)/1700(R22).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Akai AUS-12H53R130D2 User manual

Category
Split-system air conditioners
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI