Danfoss CF-RP Public (Tamperproof) Room Thermostat Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss CF-RP Public (Tamperproof) Room Thermostat Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
088U0211
Instruction CF-RP Public (Tamperproof) Room Thermostat
Instruktion CF-RP Ö entlicher Raumthermostat (gegen Eingri e gesichert)
Vejledning CF-RP Rumthermostat - Institutionsmodel
Instruction CF-RP Thermostat collectivité (réglage masqué)
Bruksanvisning till CF-RP rumstermostat - institutionsmodell
SE
1VI.UH.P3.80
Produced by Danfoss Floor Heating Hydronics 01.2006
Instruction CF-RP Public (Tamperproof) Room Thermostat
Instruction . . . . . . . . . . . . . . . . . . . . . . . 3
Instruktion . . . . . . . . . . . . . . . . . . . . . . 10
Vejledning . . . . . . . . . . . . . . . . . . . . . . . 18
Instruction . . . . . . . . . . . . . . . . . . . . . . 25
SE
Bruksanvisning . . . . . . . . . . . . . . . . . . 33
2
VI.UH.P3.80
Produced by Danfoss Floor Heating Hydronics 01.2006
Instruction CF-RP Public (Tamperproof) Room Thermostat
3VI.UH.P3.80
Produced by Danfoss Floor Heating Hydronics 01.2006
Instruction CF-RP Public (Tamperproof) Room Thermostat
1. Functional Overview . . . . . . . . . . . . . . . . . . . 4
2. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3. Transmission Test . . . . . . . . . . . . . . . . . . . . . . 7
4. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5. Uninstallation . . . . . . . . . . . . . . . . . . . . . . . . . 9
6. Speci cations . . . . . . . . . . . . . . . . . . . . . . . . . 10
7. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 11
8. Figures and illustrations . . . . . . . . . . . A1-A2-A3
Index
4
VI.UH.P3.80
Produced by Danfoss Floor Heating Hydronics 01.2006
Instruction CF-RP Public (Tamperproof) Room Thermostat
Front -  g. 1
Front cover
Red LED (behind the cover)
Turning knob & push button (room tempera-
ture setting & installation/transmission test)
LED modes
• Permanent light ON
• No light OFF
• Slow  ashing Flashes
• Fast  ashing Flickers
Back -  g. 2
Back plate
Front cover release
Back plate lock/unlock (turn 90°)
Screw hole for wall mounting
Battery placement
Screw and wall plug
Note: To activate batteries please remove enclosed
strips from batteries
1. Functional Overview
5VI.UH.P3.80
Produced by Danfoss Floor Heating Hydronics 01.2006
Instruction CF-RP Public (Tamperproof) Room Thermostat
Front Cover -  g. 3
Front Cover release
2. Installation
Note:
To activate batteries in the Room Thermostat
please remove enclosed strips from the batteries
The assignment of the Room Thermostats to the
Master Controller should be within 1½m distance
Activate Install mode on
Master Controller -  g. 1
Use the menu selection button to select the
Install mode. Install LED ashes
Activate Install mode by pressing OK . Install
LED goes ON
Activate Install mode on
Room Thermostat
Press the push button . LED and icker
during communication
6
VI.UH.P3.80
Produced by Danfoss Floor Heating Hydronics 01.2006
Instruction CF-RP Public (Tamperproof) Room Thermostat
Select output on Master Controller
All available output LEDs on Master Controller
light up, and the  rst of them  ashes
Press output selection button , select desired
output ( ashes) and accept with OK
All output LEDs go OFF. Selected output
stays ON shortly
Room Thermostat installation status
Satisfactory - LED goes OFF
Not satisfactory - LED ashes 5 times
Note: A Room Thermostat can be assigned to sev-
eral outputs if needed
7VI.UH.P3.80
Produced by Danfoss Floor Heating Hydronics 01.2006
Instruction CF-RP Public (Tamperproof) Room Thermostat
3. Transmission Test
Initiate transmission test on Room
Thermostat -  g. 1
• Press the push button
• LED goes ON
Link test is satisfactory
• LED goes OFF
Link test is unsatisfactory
• LED ashes 5 times
No Link connection to Room
Thermostat
Try to relocate Room Thermostat in the room
Or install Repeater Unit (CF-RU) and locate be-
tween Master Controller and Room Thermostat
Note: Master Controller output LED(s) connected
to the room thermostat,  ash(es) during Link test
8
VI.UH.P3.80
Produced by Danfoss Floor Heating Hydronics 01.2006
Instruction CF-RP Public (Tamperproof) Room Thermostat
4. Mounting
Placing the Room Thermostat -  g. 4
! Wherever possible, the room thermostat should be
installed at a place where the e ect of sunlight,
draught, other heaters (eg. TVs), etc. is avoided.
Mounting with screws -  g. 2
5. Uninstallation
Activate Uninstall mode on Master
Controller -  g. 1
Use the Menu selection button to choose the
Uninstall menu. Uninstall LED ashes
Activate Uninstall mode by pressing OK .
Uninstall LED goes ON
Deselect output on Master Controller
Select output to be removed by output selec-
tion button
Remove  ashing output with OK
9VI.UH.P3.80
Produced by Danfoss Floor Heating Hydronics 01.2006
Instruction CF-RP Public (Tamperproof) Room Thermostat
6. Speci cations
7. Troubleshooting
Temperature setting range 5-35°C
Transmission frequency 868.42MHz
Transmission range in
normal buildings (up to)
30m
Transmission power < 1mW
Battery Alkaline 2xAA, 1.5V
Battery lifetime (up to) 3-4 years
Ambient temperature 0-50°C
IP class 21
Error Indication Possible Cause
The LED  ashes every 5th
minute
Low battery
The LED  ashes Critical low battery
The LED  ashes 5 times Installation/Link Test is
unsatisfactory
Instruktion CF-RP Rumthermostat - Institutionsmodel
18
VI.UH.P3.80
Fremstillet af Danfoss Floor Heating Hydronics 01.2006
1. Funktionsoversigt. . . . . . . . . . . . . . . . . . . . . . 19
2. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3. Transmissionstest . . . . . . . . . . . . . . . . . . . . . 21
4. Montering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5. A nstallation . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6. Speci kationer . . . . . . . . . . . . . . . . . . . . . . . . 24
7. Fejl nding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8. Figurer og illustrationer . . . . . . . . . . A1-A2-A3
Indhold
/