ClimateMaster Tranquility® Rooftop TRT Series3 – 6 Tons (10.6 kW – 21.1 kW) Owner's manual

Type
Owner's manual
Rooftop (TRT) Series
Commercial Rooftop
Water-Source Heat Pumps
Installation, Operation
& Maintenance
LC1084
Rev.: April 23, 2020
Table of Contents
Model Nomenclature 3
General Information 4
TRE036 - 072 Dimensional Data 5
Standard Roof Curb 6
Standard Curb with Vibration Isolation 7
Side Discharge Supply & Return Roof Curb 8
Installation 9
Piping Installation 10
Water Quality Standards 11
Electrical Wiring 12
Electrical Low Voltage Wiring 13-14
Electrical Low Voltage Wiring non-vFlow 15
Electrical Thermostat Wiring 16
TWD - 036 to 072 17-18
TWD - Units with MPC DDC Auxiliary Diagram 19
TRT Sound Data 20
TRT Electrical Data Standard 21
TRT Electrical Data Climadry
®
II 22
BLower Motor VFD Controls 23-24
TRT Wiring Diagram Matrix 25
TRT Series Nomenclature 26
General Information 27-28
ClimaDry
®
II Sequence of Operation 29-30
TRT Blower Performance Data -
Units with ClimaDry
®
31
Flushing/Purging Units with ClimaDry
®
32
Unit Commissioning & Operating Conditions 33
Start-Up Preparation 34
Blower Adjustment 35
Tensioning V-Belt Drives 36
Unit System Checkout 37
Unit Start-up 38
Start-up Sheet Log 39
Preventive Maintenance 40
Warranty 41
Revision History 44
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rooftop (TRT) Series
Rev.: April 23, 2020
2
ClimateMaster Water-Source Heat Pumps
This Page Intentionally Left Blank
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Rooftop (TRT) Series
Rev.: April 23, 2020
3
climatemaster.com
Model Nomenclature
Curb (TRT & ERV Unit Nomenclature)
2 5
1
6
4
3 6 7
3
6
8
9
10
6
T R 0 3 6 HD 1C A A A A S
1 2 4 5 6 7 8
9
10 11 12 13 14 15
TRANQUILITY ROOFTOP UNIT
SERIES
UNIT SIZE
REVISION LEVEL
VOLTAGE
CONTROLS
CABINET & FILTER
HEAT EXCHANGER OPTIONS
A = NONE
AIR DAMPER OPTIONS
A = NONE
POWER TERMINATION
B = DISCONNECT
C = DISCONNECT + GFI OUTLET
STANDARD
036
048
060
072
096
120
144
168
C = CXM
BLOWER DRIVE PACKAGE
D = DXM
L = CXM w/LON
M = DXM w/LON
N = CXM w/MPC
P = DXM w/MPC
B = MANUAL ADJUSTABLE FRESH AIR DAMPER
S = STANDARD
240
ETL APPROVED
USA & CANADA
A = STANDARD RPM & STANDARD MOTOR
B = LOW RPM & STANDARD MOTOR
C = HIGH RPM & STANDARD MOTOR
D = STANDARD RPM & LARGE MOTOR
E = HIGH RPM & LARGE MOTOR
D = CIRCUIT BREAKER
E = CIRCUIT BREAKER + GFI OUTLET
C = MOTORIZED FRESH AIR DAMPER
OPTION
RANGE
2”, (50mm) FILTER
MERV 8
4”, (50mm) FILTER
MERV 8
4”, (100mm) FILTER
MERV 13
THROWAWAY FILTER OPTIONS
1
B
C
3
D
E
EXTENDED
RANGE
STANDARD
RANGE
YES NO NO
NO YES NO
NO NO YES
YES NO NO
NO YES NO
NO NO YES
F = MODULATING ENTHALPY ECONOMIZER
A = HOT GAS BYPASS
B-Z = SPECIALS
NON-COATED AIR COILS
COATED AIR COILS
C
T
N
S
A
U
J
W
STANDARD
MOTORIZED VALVE
COPPER (CU)
COAX
CUPRO-NICKEL (CN)
COAX
E P D F
CLIMADRY
H Z G Y
INTERNAL
SECONDARY PUMP
COPPER (CU)
COAX
CUPRO-NICKEL (CN)
COAX
REHEAT COIL
3-WAY MOTORIZED VALVE
PROPORTIONAL CONTROL
CIRCULATING PUMP
PUMP CONTACTOR
HOT GAS BYPASS
CLIMADRY OPTION COMPONENTS
E = SINGLE STAGE COMPRESSOR(S)
COMPRESSOR TYPE
T = DUAL STAGE COMPRESSOR
TRE ONLY
F = VFD, VARIABLE FREQUENCY DRIVE
E
3
{
{
{
EFFECTIVE
DATE “TBD”
1 2 3 4
MODULATING VALVE
N = 575/60/3
D= CURRENT ALL SIZES
(EFFECTIVE 5/12/15)
F = 460/60/3
H = 208-230/60/3 (FACTORY WIRED 208)
G = 280-230/60/1
A C U R B A A A A
1 2 3 4 5
9 10 11 12
Model Type
TRE 036 - 072 Standard Curb = AAA
CURB TYPE and/or Cabinet Size
Curb Constructions
B = Standard 24” High - TRE, ERD, ERS
D = 14” High Curb for ERO Stand Alone ERV
E = 24” High Curb for ERO Stand Alone ERV
C = Horizontal Discharge/RH & LH (TRE Only)
Field Changeable - Supply and Return
TRE 168 - 240 Standard Curb =
Stand Alone 300 - 1000 cfm B =
Stand Alone 1200 - 2800 cfm D =
Stand Alone 1200 - 2000 cfm C =
Stand Alone 2000 - 3600 cfm E =
Stand Alone 3000 - 4600 cfm F =
Stand Alone 4600 - 6200 cfm G =
Stand Alone 6000 - 8000 cfm H =
Stand Alone 8000 - 1200 cfm J =
AAC
EVB
EVD
EVE
EVF
EVG
EVH
EVJ
EVC
TRE 096 -144 Standard Curb = AAB
G
8
Revision Level
G = Current Revision
A = Standard 14” High - TRE, ERD, ERS
R T
6 7
ACURB = Curb
Series Type
RT =
EV =
TRE Series
Stand alone ERV Series
A
13
Curb Options
B = Welded
C = Welded Vibration Isolation (TRE only)
A = Knocked Down
S = Standard
N
14
Not Used
S
15
Standard
Note: Horizontal curb adapter for TRE only.
End return RH or LH supply, field changable.
Fits on top of digit 12 option A or B.
Digit 13 can be option A or C.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rooftop (TRT) Series
Rev.: April 23, 2020
4
ClimateMaster Water-Source Heat Pumps
WARNING! To avoid equipment damage, do not use these
units as a source of heat during the construction process.
The mechanical components and lters used in these units
will quickly become clogged with construction dirt and debris
which may cause system damage.
WARNING! Some units may be charged with refrigerants
other than 410A and are so labeled. Use appropriate
refrigerant handling techniques. Mixing refrigerants in units
is dangerous and can cause equipment damage. To avoid
the release of refrigerant into the atmosphere, the refrigerant
circuit of this unit must only be serviced by technicians who
meet local, state and federal prociency requirements.
Inspection - Upon receipt of shipment at the job site,
carefully check the shipment against the bill of lading.
Make sure all units have been received. Inspect the carton
or crating housing of each Rooftop Unit and inspect each
unit for damage. Assure that the carrier makes proper
notation of any shortages or damage on all copies of the
freight bill and that he completes a Carrier Inspection Re-
port. Concealed damage not discovered during unloading
must be reported to the carrier within 15 days of receipt
of shipment. NOTE: It is the responsibility of the pur-
chaser to le all necessary claims with the carrier.
Storage - Upon the arrival of equipment at the job site,
immediately store units in a clean, dry area. Store units
in an upright position at all times. Stack unit model
numbers TRT-036 through TRT-120 no more than 2
units high. Do not stack units larger than model number
TRT-120. Do not remove equipment from pallets until
equipment is required for installation
Unit Protection - Cover rooftop units on the job site. Cap
the open ends of pipes. In areas where painting, plaster-
ing, roong, or the spraying of reproof material has not
been completed, all due precautions must be taken to
avoid physical damage to the units and contamination by
foreign material. Physical damage and contamination
may prevent proper start-up and may result in costly
equipment cleanup.
Pre-Installation - Installation, operation and maintenance
instructions are provided with each unit. Before unit start-
up, read all manuals and become familiar with the unit
and its operation. Thoroughly check out the system before
operation.
Prepare rooftop units for installation as follows:
1. Compare the electrical data on the unit nameplate with
ordering and shipping information to verify that the
correct unit has been shipped.
2. Select an installation site on the roof which allows
adequate clearance for maintenance and servicing
of the unit. A minimum of two feet of clearance is
required on all service access and drain connection
sides of the unit.
3. Verify that refrigerant tubing is free of kinks or dents,
and that it has not been damaged during shipping.
4. Examine all pipes, ttings, valves and components
before installing the system. Remove any dirt found
on or in these components and assure that all
components are securely tted.
5. Verify curb is proper size for unit. Install curb according
to manufacturer's instructions prior to installing unit.
6. Properly size supply and return duct work.
Mount
supply air duct to curb before installing unit.
General Information
WARNING!
WARNING!
CAUTION!
CAUTION! Supply air duct is inaccessible from inside unit
once unit is installed.
WARNING! The installation of water-source heat pumps and
all associated components, parts, and accessories which
make up the installation shall be in accordance with the
regulations of ALL authorities having jurisdiction and MUST
conform to all applicable codes. It is the responsibility of
the installing contractor to determine and comply with ALL
applicable codes and regulations.
WARNING!
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Rooftop (TRT) Series
Rev.: April 23, 2020
5
climatemaster.com
Top View
of Base
Optional
Rain
Hood
Se
rvice Ac
c
es
s
3
.5
(
1
.
1
me
ters)
Ser
v
i
c
e Acce
s
s
3
.
5
(1
.1
mete
r
s
)
Size
Outdoor Air Opening
Water In/Out (IPT)
TRT36 12.57" X 30" 3/4"
TRT48 12.57" X 30" 3/4"
TRT60 12.57" X 30" 1"
TRT72 12.57" X 30" 1 1/4"
Condensate
1"
1”
1”
1”
Optional
Rain
Hood
Pipe
Chase
TRT036 - 072 Dimensional Data
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rooftop (TRT) Series
Rev.: April 23, 2020
6
ClimateMaster Water-Source Heat Pumps
Standard Roof Curb
Model A B C D E F*
TRT036/48/60/72
72.25” 18” 35.25”
72.25” 35.25” 14” or 24”
* “F” dimension can be 14” or 24”
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Rooftop (TRT) Series
Rev.: April 23, 2020
7
climatemaster.com
Standard Curb with Vibration Isolation
Model A B C D E F*
TRT036/48/60/72
72.25” 18” 35.25”
72.25” 35.25” 14” or 24”
* “F” dimension can be 14” or 24”
Note: Finish height is 12.5" taller than the base curb height.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rooftop (TRT) Series
Rev.: April 23, 2020
8
ClimateMaster Water-Source Heat Pumps
Side Discharge Supply & Return Roof Curb
Model A B C
TRT036/48/60/72
72.25” 18” 35.25”
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Rooftop (TRT) Series
Rev.: April 23, 2020
9
climatemaster.com
The installation of rooftop water-source heat pump units
and all associated components, parts and accessories
that make up the installation shall be in accordance with
the regulations of ALL authorities having jurisdiction
and MUST conform to all applicable codes. It is the
responsibility of the Installing Contractor to determine and
comply with ALL applicable codes and regulations.
Installation
Location, Access and Curb Installation -
Install curbs
with adequate clearance to allow unit maintenance and
servicing. Conform to the following guidelines when se-
lecting curb location.
1. Provide adequate clearance for lter replacement
and drain pan removal. Do not block lter access with
piping, conduit or other materials.
2. Provide access for fan and fan motor maintenance and
for servicing the compressor and coils without removal
of the unit.
3. Provide an unobstructed path to the unit to enable
removal of the unit if necessary.
4. Provide access to water valves and ttings, and
adequate access to the unit side panels and all
electrical connections.
Follow these guidelines when installing the curb.
1. Set unit on curb.
2. Align unit so that return air and supply air in the unit
match return and supply air opening in the curb frame.
3. Run supply and return loop piping and electrical
supply lines through the pipe chase provided in
the curb.
Note: Refer to previous pages for actual unit dimensions.
Figure 1: TRT Curb Installation
Gasket
Curb
TRT Series
Unit
Flashing
Roof
CAUTION!
CAUTION! All refrigerant discharged from this unit must
be recovered without exception. Technicians must follow
industry accepted guidelines and all local, state and federal
statutes for the recovery and disposal of refrigerants.
When a compressor is removed from this unit, system
refrigerant circuit oil will remain in the compressor. To
avoid leakage of compressor oil, the refrigerant lines of the
compressor must be sealed after it is removed.
Mineral oil or equipment exposed to mineral oil (manifold
gauges, vacuum pumps or hoses) cannot be used to service
units charged with 410A refrigerant and P.O.E. oil. HFC-410A
and P.O.E. oil are extremely hygroscopic (they absorb water
from air). Only P.O.E. oil that has been veried as moisture
free can be added to the system. Consult factory for more
information.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rooftop (TRT) Series
Rev.: April 23, 2020
10
ClimateMaster Water-Source Heat Pumps
2”
1.5”
1.5”
* Some units include a painted drain connection.
Using a threaded pipe or similar device to clear
any excess paint accumulated inside this fitting
may ease final drain line installation.
1/8” Per
Foot
Condensate Piping -
Install a condensate trap at each
unit with the top of the trap positioned below the unit
condensate drain connection.
Design the length of the trap (water-seal) based upon
the amount of positive or negative pressure on the drain
pan. As a general rule, 1" of trap is required for each 1”
of negative pressure on the unit with a 1.5” (38 mm)
minimum. Each unit must be installed with a dedicated
trap for that unit.
Note that condensate may be allowed to drain onto the
roof.
Supply and Return Piping
-
Follow these piping guidelines.
1. Install a drain valve at the base of each supply and
return riser to facilitate system ushing.
2. Install shut-off/balancing valves and unions at each
unit to permit unit removal of unit, if required.
3. Place strainers at the inlet of each system circulating
pump. To ensure a clean system.
Always insulate where the piping runs through unheated
areas or outside the building. If loop temperature is
maintained between 60°F and 90°F, piping will not sweat
nor lose heat under normal ambient conditions. Otherwise,
insulation is required on loop water piping.
All loop piping above grade must be insulated on any unit
connected to an open or closed GeoThermal loop (GLHP,
GWHP).
Pipe joint compound is not necessary when Teon
®
threaded tape is pre-applied to hose assemblies or when
ared-end connections are used. If pipe joint compound
is preferred, use compound only in small amounts on the
male pipe threads of the tting adapters. Prevent sealant
from reaching the ared surfaces of the joint.
Maximum allowable torque for brass ttings is 30 foot-
pounds. If a torque wrench is not available, tighten
nger-tight plus one quarter turn. Tighten steel ttings as
necessary.
Figure 2: Condensate Drain
WARNING!
WARNING! Piping must comply with all applicable Codes.
CAUTION!
CAUTION! Corrosive system water requires corrosion-
resistant ttings and hoses and may require water treatment.
Piping Installation
Note: The manufacturer strongly recommends all
piping connections, both internal and external to the
unit, be pressure tested by an appropriate method
prior to any nishing of the interior space or before
access to all connections is limited. Test pressure may
not exceed the maximum allowable pressure for the
unit and all components within the water system.
The manufacturer will not be responsible or liable
for damages from water leaks due to inadequate or
lack of a pressurized leak test, or damages caused
by exceeding the maximum pressure rating during
installation.
WARNING! Polyolester Oil, commonly known as POE oil, is
a synthetic oil used in many refrigeration systems including
those with HFC-410A refrigerant. POE oil, if it ever comes
in contact with PVC or CPVC piping, may cause failure of
the PVC/CPVC. PVC/CPVC piping should never be used
as supply or return water piping with water source heat
pump products containing HFC-410A as system failures and
property damage may result.
WARNING!
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Rooftop (TRT) Series
Rev.: April 23, 2020
11
climatemaster.com
Table 1: Water Quality Standards
Water Quality Standards
Water Quality
Parameter
HX
Material
Closed
Recirculating
Open Loop and Recirculating Well
Scaling Potential - Primary Measurement
pH/Calcium Hardness
All
-
pH < 7.5 and Ca Hardness <100ppm
Method
Index Limits for Probable Scaling Situations -
(Operation outside these limits is not recommended)
Ryznar
All
- 6.0 - 7.5
Stability Index If >7.5 minimize steel pipe use.
Langelier
All
-
-0.5 to +0.5
Saturation Index
If <-0.5 minimize steel pipe use. Based upon 66°C HWG and
Direct well, 29°C Indirect Well HX
Iron Fouling
Iron Fe
2+
(Ferrous)
All
-
<0.2 ppm (Ferrous)
(Bacterial Iron potential)
If Fe
2+
(ferrous)>0.2 ppm with pH 6 - 8, O2<5 ppm check for iron bacteria.
Iron Fouling
All
-
<0.5 ppm of Oxygen
Above this level deposition will occur .
Corrosion Prevention
pH
All
6 - 8.5
6 - 8.5
Monitor/treat as
needed
Minimize steel pipe below 7 and no open tanks with pH <8
Hydrogen Sulfide (H
2
S)
All
- <0.5 ppm
At H
2
S>0.2 ppm, avoid use of copper and copper nickel piping or HX's.
Rotten egg smell appears at 0.5 ppm level.
Copper alloy (bronze or brass) cast components are OK to <0.5 ppm.
Ammonia ion as hydroxide, chloride,
nitrate and sulfate compounds
All
-
<0.5 ppm
Maximum
Maximum Allowable at maximum water temperature.
Chloride Levels
10°C 24°C 38
C
Copper
Cupronickel
- <20ppm NR NR
- <150 ppm NR NR
304 S
S - <400 ppm <250 ppm <150 ppm
316 S
S - <1000 ppm <550 ppm < 375 ppm
Titanium - >1000 ppm >550 ppm >375 ppm
Erosion and Clogging
Particulate Size and
Erosion
All
<10 ppm of particles
and a maximum
velocity of 1.8 m/s
Filtered for maximum
841 micron [0.84 mm,
20 mesh] size.
<10 ppm (<1 ppm "sandfree” for reinjection) of particles and a maximum
velocity of 1.8 m/s. Filtered for maximum 841 micron 0.84 mm,
20 mesh] size. Any particulate that is not removed can potentially
clog components.
Notes:
• NR - Application not recommended.
• "-" No design Maximum.
• Closed Recirculating system is identified by a
closed pressurized piping system.
• Recirculating open wells should observe the open recirculating design considerations.
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below
Scaling indexes should be calculated at 66°C for direct use and HWG applications, and at 32°C for indirect HX use.
A monitoring plan should be implemented.
The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. The water should be evaluated by an
independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to
isolate the heat pump heat exchanger from the unsuitable water. Failure to do so will void the warranty for the coaxial heat exchanger and any other components
damaged by a leak.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rooftop (TRT) Series
Rev.: April 23, 2020
12
ClimateMaster Water-Source Heat Pumps
General Line Voltage Wiring
- Be sure the available
power is the same voltage and phase as that shown on
the unit serial plate. Line and low voltage wiring must
be done in accordance with local codes or the National
Electric Code, whichever is applicable.
TRT Power Connection
- Line voltage connection is
made by connecting the incoming line voltage wires to
the power block. Line voltage conduit should be routed
through curb and unit pipe chase. Terminate conduit at
control/compressor deck.
208 Volt Operation
- All 208-240 Volt units are factory
wired for 208 Volt. The transformers may be switched to
240V operation as illustrated on the wiring diagram by
switching the Red (240V) and the Orange (208V) wires
on the transformer primary side. Unused wire terminal will
be “hot” and must be insulated and secured to prevent an
electric short.
Optional GFI Outlet requires dedicated 115V - 20 AMP
circuit provided by installer
WARNING!
WARNING! Disconnect electrical power source to prevent
injury or death from electrical shock.
CAUTION!
CAUTION! Use only copper conductors for eld installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Figure 2 illustrates a typical trap used with TRT Heat Pumps.
Multiple units within the same zone should be operated
from a common temperature control.
Thermostat Wiring -
All wiring must comply with all
applicable electrical codes including NEC and local codes.
Complete all wiring before units are installed. Use multi
conductor, color-coded, low-voltage cable for all wiring.
Refer to unit wiring diagram for required thermostat
connections.
Table 2: Recommended Thermostat Wire Sizes
* Length = physical length of wire from thermostat to unit.
CAUTION!
CAUTION! Maintain zone integrity to assure accurate and
efcient operational control of units or groups of units.
Without adequate zone control, adjacent units may operate in
heating and cooling mode simultaneously.
Electrical Wiring
WIRE SIZE MAX. WIRE LENGTH*
22 - Gauge 30 feet [9.14m]
20 - Gauge 50 feet [15.24m]
18 - Gauge 75 feet [22.86m]
16 - Gauge 125 feet [38.1m]
14 - Gauge 200 feet [60.96m]
Refer to Table 2 for wire sizes and lengths. Do not allow
the total resistance of all low-voltage wires used to exceed
1 ohm. Resistance in excess of 1 ohm may cause high
voltage drop which may result in control malfunction.
Refer to the thermostat installation and operation manual
to determine recommended heat anticipator settings.
When using a DDC building management system (BMS),
communication grade wire may be required. Verify
required communication and sensor wiring type with the
manufacturer of the BMS system components.
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Rooftop (TRT) Series
Rev.: April 23, 2020
13
climatemaster.com
Electrical - Low Voltage Wiring
Thermostat Connections - The thermostat will be wired
to the DXM2 board located within the unit control box.
Refer to the unit wiring diagram for specic details.
Low Water Temperature Cutout Selection - The DXM2
control allows the eld selection of low water (or water-
antifreeze solution) temperature limit by clipping jumper
JW3, which changes the sensing temperature associated
with thermistor LT1. Note that the LT1 thermistor is
located on the refrigerant line between the coaxial heat
exchanger and expansion device (TXV). Therefore, LT1 is
sensing refrigerant temperature, not water temperature,
which is a better indication of how water ow rate/
temperature is affecting the refrigeration circuit.
The factory setting for LT1 is for systems using water
(30°F [-1.1°C] refrigerant temperature). In low water
temperature (extended range) applications with
antifreeze (most ground loops), jumper JW3 should be
clipped as shown in Figure 17 to change the setting to
10°F [-12.2°C] refrigerant temperature, a more suitable
temperature when using an antifreeze solution. All
ClimateMaster units operating with entering water
temperatures below 60°F [15.6°C] must include the
optional water/refrigerant circuit insulation package to
prevent internal condensation.
Figure 17: LT1 Limit Setting
P1
Alarm
Relay
Comp
Relay
O
Y1
Y2
W
G
C
R
AL1
24Vdc
EH1
EH2
P6
R
C
Off On
JW3
A
OVR
ESD
C
R
NSB
AL2
JW1
Acc1
Relay
Acc2
Relay
H
COM
NC1
NO1
COM
NC2
NO2
P3
CO
RV
RV
LT1
LT1
LT2
LT2
LP
LP
HP
HP
P7
Status
Fault
R
R
CC
CCG
CO
S1
S2
1
12
1
4
Factory Use
(240Vac)
Com
N.O.
Fan Enable
5 1/2"
7"
6 1/2"
5"
Use 4 mounting screws
#6 sheet metal screw 1” long
1.5
3/8” standoff
Factory low
voltage Molex
connection for
unit harness
Factory low
voltage Molex
connection for
electric heat
harness
Micro
U1
Off On
P2
COH
COM
AO2
P11
Gnd
T1
P10
T2 T2 T3 T3 T4 T4
T5
P9
T5
T6 T6
A0-1 A0-2
Off On
S3
RV
Relay
CCH
Relay
Test
P5
B-
Gnd
P4
A+ 24V
(240Vac)
Fan Speed
N.O.
N.C.
12V
OUT
Gnd
P8
IN
NC
P12
Note: There is only
one T1 connection
1 2 3 4
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
AO1
Gnd
1
DXM2 PCB
JW3-LT1 jumper should be clipped for low temperature
(antifreeze) operation
Accessory Connections - A terminal paralleling the
compressor contactor coil has been provided on the DXM2
control. Terminal “A” is designed to control accessory
devices. Note: This terminal should be used only with 24
Volt signals and not line voltage. Terminal “A” is energized
with the compressor contactor.
The DXM2 controller includes two accessory relays ACC1
and ACC2. Each relay includes a normally open (NO) and
a normally closed (NC) contact. Accessory relays may be
congured to operate as shown in the tables below.
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rooftop (TRT) Series
Rev.: April 23, 2020
14
ClimateMaster Water-Source Heat Pumps
Electrical - Low Voltage Wiring
Figure 18: Accessory Wiring
P2 Terminal Strip
Typical
Water
Valve
Accessory Relay 2 Conguration
Accessory Relay 1 Conguration
DIP 2.1 DIP 2.2 DIP 2.3 ACC1 Relay Option
ON ON ON Cycle with fan
OFF ON ON N/A for Residential Applications
ON OFF ON Water valve – Slow opening
ON ON OFF Outside air damper
OFF ON OFF ClimaDry option – Dehumidistat
OFF OFF OFF ClimaDry option – Humidistat
OFF OFF ON N/A for Residential Applications
ON OFF OFF N/A for Residential Applications
All other DIP combinations are invalid
DIP 2.4 DIP 2.5 DIP 2.6 ACC2 Relay Option
ON ON ON
Cycle with compressor
OFF ON ON
N/A for Residential Applications
ON OFF ON
Water valve – Slow opening
OFF OFF ON
Humidier
ON ON OFF
Outside air damper
All other DIP combinations are invalid
A slow closing valve may be required to help reduce
water hammer. Figure 13 shows typical wiring for a
24VAC external solenoid valve. Figures 14 and 15
illustrate typical slow closing water control valve wiring for
Taco 500 series (ClimateMaster P/N AVM) and Taco SBV
series valves. Slow closing valves take approximately
60 seconds to open (very little water will ow before
45 seconds). Once fully open, an end switch allows the
compressor to be energized. Only relay or triac based
electronic thermostats should be used with slow closing
valves. When wired as shown, the slow closing valve will
operate properly with the following notations:
1. The valve will remain open during a unit lockout.
2. The valve will draw approximately 25-35 VA through
the “Y” signal of the thermostat.
Note: This valve can overheat the anticipator of an
electromechanical thermostat. Therefore, only relay or
triac based thermostats should be used.
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Rooftop (TRT) Series
Rev.: April 23, 2020
15
climatemaster.com
Electrical - Low Voltage Wiring for non-vFlow
®
Units Using External Motorized Water Valve
Figure 19: AVM Valve Wiring Figure 20: Taco SBV Valve Wiring
From Water Source
IN
OUT
NOTE: Shut-off valves, strainers and
other required components not shown.
Solenoid
Valve
Flow
Regulator
To Discharge
Stage 1
Stage 2
Figure 21: Two-Stage Piping
C
C
Termostato
Y
1
2
3
Y
AVM
Taco Válvula
Calentador Interruptor
Unidad Empacada
C
C
Aquastat
Y1
1
2
3
Y1
AVM
Taco Valve
Heater Switch
DXM2
Water Valve Wiring
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rooftop (TRT) Series
Rev.: April 23, 2020
16
ClimateMaster Water-Source Heat Pumps
Thermostat Installation - The thermostat should be
located on an interior wall in a larger room, away from
supply duct drafts. DO NOT locate the thermostat in areas
subject to sunlight, drafts or on external walls. The wire
access hole behind the thermostat may in certain cases
need to be sealed to prevent erroneous temperature
measurement. Position the thermostat back plate against
the wall so that it appears level and so the thermostat
wires protrude through the middle of the back plate. Mark
the position of the back plate mounting holes and drill
holes with a 3/16” (5mm) bit. Install supplied anchors
and secure plate to the wall. Thermostat wire must be 18
AWG wire. Representative thermostat wiring is shown in
Figures 22a-b however, actual wiring connections should
be determined from the thermostat IOM and or unit wiring
diagram. Practically any heat pump thermostat will work
with ClimateMaster units, provided it has the correct
number of heating and cooling stages.
Electrical - Thermostat Wiring
Field Wiring
Factory Wiring
Figure 22a: Conventional 3 Heat / 2 Cool Thermostat
Connection to DXM2 Control
Thermostat
Connection to DXM2 Control
Compressor
Compressor Stage 2
Reversing Valve
Fan
24Vac Hot
24Vac Common
Fault LED
DXM2
Board
Y1
Y2
W
H
O
G
R
C
AL1
Y1
Y2
W
DH
O
G
R
C
L
iGate
®
Thermostat
ATC
32U03C
Figure 24a: Communicating Thermostat
24Vac Hot
DXM2
24V
Dehumidification
Notes:
Auxiliary Heat
1) ECM automatic dehumidification mode operates with dehumidification airflows
in the cooling mode when the dehumidification output from thermostat is active.
Normal heating and cooling airflows are not affected.
2) DXM2 board DIP switch S2-7 must be in the auto dehumidification mode for
automatic dehumidification.
3) DH connection not possible with units with internal variable speed pump. Use ATC32U03C.
4) Only use ATC Communicating Thermostat when using Humidifier (H Input) in
units with internal variable speed pump.
Figure 24b: Conventional 3 Heat / 2 Cool Thermostat
Connection to DXM2 Control
Comm +
A+
Comm -
B-
B-
OD
ID
GND
Outdoor
Sensor
(Optional)
Remote Indoor
Sensor
(Optional)
24Vac Common
Gnd
R
C
A+
Figure 22b: Communicating Thermostat Connection to
DXM2 Control
Thermostat
Connection to DXM2 Control
Compressor
Compressor Stage 2
Reversing Valve
Fan
24Vac Hot
24Vac Common
Fault LED
DXM2
Board
Y1
Y2
W
H
O
G
R
C
AL1
Y1
Y2
W
DH
O
G
R
C
L
iGate
®
Thermostat
ATC
32U03C
Figure 24a: Communicating Thermostat
24Vac Hot
DXM2
24V
Dehumidification
Notes:
Auxiliary Heat
1) ECM automatic dehumidification mode operates with dehumidification airflows
in the cooling mode when the dehumidification output from thermostat is active.
Normal heating and cooling airflows are not affected.
2) DXM2 board DIP switch S2-7 must be in the auto dehumidification mode for
automatic dehumidification.
3) DH connection not possible with units with internal variable speed pump. Use ATC32U03C.
4) Only use ATC Communicating Thermostat when using Humidifier (H Input) in
units with internal variable speed pump.
Figure 24b: Conventional 3 Heat / 2 Cool Thermostat
Connection to DXM2 Control
Comm +
A+
Comm -
B-
B-
OD
ID
GND
Outdoor
Sensor
(Optional)
Remote Indoor
Sensor
(Optional)
24Vac Common
Gnd
R
C
A+
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Rooftop (TRT) Series
Rev.: April 23, 2020
17
climatemaster.com
Typical Wiring Diagram – Sizes 036 to 072,
DXM2 with Voltage G
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rooftop (TRT) Series
Rev.: April 23, 2020
18
ClimateMaster Water-Source Heat Pumps
Typical Wiring Diagram – Sizes 036 to 072,
DXM2 with Voltage F, H
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Rooftop (TRT) Series
Rev.: April 23, 2020
19
climatemaster.com
Typical Wiring Diagram - Units with MPC DDC Option, Auxiliary Diagram




























MPC
ClimateMaster







 
POLARITY SENSITIVE
DDC COMM NETWORK








MPC2. Refer to MPC installation, application, and operation manual for
control wiring to the unit.













































TITLE:

PCN

DATE:

DRAWING NO.
REV
2. All wiring to the unit must comply with NEC and local codes
low voltage wiring shall be Class 2 or equivalent.
NOTES:
Multi Splice Connector
Low Pressure Switch
Relay contacts - N.O.
Relay contacts - N.C.
Optional Block
Capacitor
Field Low voltage Wiring
Field Line voltage Wiring
Printed Circuit Trace
Optional Wiring
Factory Low voltage Wiring
Factory Line Voltage Wiring

Mate-N-Lock
Optional
LED
G
Thermistor
Wire Nut
Temperature Switch
Relay / Contactor Coil
High Pressure Switch
Ground
Circuit Breaker
Condensate Pan
Splice Cap
Solenoid Coil

MPC1. Factory cut JW1 (CXM) or JW4 (DXM) jumper. Dry Contact will be available
between AL1 and Al2.
Blower Motor Capacitor
Alarm Relay Contacts
Blower Motor
Blower Relay
Capacitor
Circuit Breaker
Compressor Relay
AL
BM
BR
CB
CAP
CR
BMC
HP High Pressure Switch
Multi Splice Connector
Jumper Wire
Leaving Air Temperature
Loss of Charge Pressure Switch
High Pressure Water Switch
Power Terminal Block
HPWS
LOC
MSC
PB
JW
LAT
Fan Speed SwitchFSS
Sensor, low te
mp protection, air coil
Sensor, low temp protection, water coil
End Switch
Damper Motor
Condensate Overflow Sensor
Common Terminal Block
CO
DM
CTB
FP1
FP2
ES
Field Wiring Terminal Block
Transformer
Modulating Water Valve
Start Assist Capacitor
Unit Mounted Thermostat
Return Air Sensor
P1
TRANS
MOD
SAC
UMT
RAS
Reversing Valve Solenoid
RVS
Compressor Contractor CC
Discharge Temperature SwitchDTS
Motorized Water Valve
MWV
Manual StarterMS
Lock Out Relay
LOR
Domestic Hot WaterDHW
Heati
ng RelayHR
Potentiometer
POT
Terminal BlockTB
Power Distribution Block
PDB
Terminal StripTS
Current Sensor
CS
Entering Water Temp SensorEWTS
Leaving Water Temp SensorLWTS



CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Rooftop (TRT) Series
Rev.: April 23, 2020
20
ClimateMaster Water-Source Heat Pumps
TRT Sound Data
Model Mode
Ducted Discharge Octave Band Frequency, Hz.
Free Air Inlet Combined With Casing (Cabinet)
Radiated Octave Band
Frequency, Hz.
125 250 500 1000 2000 4000 8000 125 250 500 1000 2000 4000 8000
TRT036
Fan Only 55 50 37 33 34 36 34 64 51 48 48 41 47 40
Cooling: Full Load 61 52 47 47 45 42 38 75 64 58 54 54 54 45
Heating: Full Load 61 52 47 47 45 40 37 75 63 58 55 52 50 47
Cooling: Part Load 53 49 34 34 37 38 36 69 65 55 58 57 54 43
Heating: Part Load 53 46 36 32 30 33 35 69 65 56 53 48 46 44
TRT048
Fan Only 49 41 35 31 28 33 36 61 52 49 45 42 48 42
Cooling: Full Load 59 54 50 47 48 47 42 72 65 62 59 55 56 49
Heating: Full Load 59 53 49 47 46 44 40 72 63 60 56 53 55 48
Cooling: Part Load 52 43 37 33 31 33 35 67 64 57 54 50 49 43
Heating: Part Load 54 44 37 32 28 32 36 67 59 54 46 43 48 41
TRT060
Fan Only 51 40 33 32 31 34 35 60 53 50 53 46 46 40
Cooling: Full Load 60 52 46 40 40 43 38 69 62 58 57 54 54 46
Heating: Full Load 60 51 44 41 40 42 37 69 63 62 57 54 52 45
Cooling: Part Load 52 43 34 33 33 35 35 63 59 53 52 46 47 42
Heating: Part Load 53 44 32 31 30 33 35 63 61 55 52 45 46 42
TRT072
Fan Only 52 40 36 31 30 34 36 62 54 51 50 44 48 42
Cooling: Full Load 64 54 52 46 47 49 49 72 65 68 60 58 61 53
Heating: Full Load 64 54 50 46 46 48 41 72 64 64 60 57 60 51
Cooling: Part Load 53 42 37 31 31 35 35 65 60 56 56 49 53 50
Heating: Part Load 53 40 37 31 30 34 36 65 64 55 56 49 52 49
Tested in accordance with ARI 260
TRT comes standard w/mute construction
TRT Series Octave Band Sound Power Level
(dB re 1PW)
Standard 60 Hz Construction – Belt Drive Blower Motor + VFD
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

ClimateMaster Tranquility® Rooftop TRT Series3 – 6 Tons (10.6 kW – 21.1 kW) Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI