Danfoss scroll compressors H series - GB - US User guide

Type
User guide
Danfoss scrolls, H-Series
Residential and light commercial
50 - 60 Hz - R407C - R22 - R410A
Application guidelines
http://danfoss.us.com/
Application Guidelines
3FRCC.PC.012.A6.22
Content
Scroll compression principle ....................................................................5
Scroll compressor components ................................................................................................................................. 5
The scroll compression process .................................................................................................................................6
H-series color ....................................................................................................................................................................6
Compressor model designation ...............................................................7
Nomenclature ..................................................................................................................................................................7
Label .................................................................................................................................................................................... 7
Technical specications ............................................................................8
60-Hz data * ...................................................................................................................................................................... 8
50-Hz data * ...................................................................................................................................................................... 9
Dimensions ...............................................................................................10
HRM032-034-038-040-042 / HRP034-038-040-042 / HRH029-031-032-034-036-038 /
HRM-045-047 / HRP-045-047 / HRH039-040 ........................................................................................................ 10
HRM048-051-054-058-060 / HLM068-072-075-078-081 / HRP048-051-054-058-060 /
HLP068-072-075-078-081 / HRH041-044-049-051-054-056 / HLH061-068 / HLJ072-075-083 .........11
HCM/HCP 094-109-120 ................................................................................................................................................12
HCJ090-105-120 ............................................................................................................................................................. 13
HCJ091-106-121 ............................................................................................................................................................. 14
HLH061-HLJ072-HLJ083 ..............................................................................................................................................15
Electrical data, connections and wiring ..................................................16
Motor voltage .................................................................................................................................................................16
Wiring connections ....................................................................................................................................................... 16
IP rating .............................................................................................................................................................................17
LRA (Locked Rotor Amp) .............................................................................................................................................17
MCC (Maximum Continuous Current) .................................................................................................................... 17
Winding resistance ........................................................................................................................................................ 17
Electrical connections .................................................................................................................................................. 17
Nominal capacitor value and relays ........................................................................................................................ 18
Internal motor protection ...........................................................................................................................................18
Phase sequence and reverse rotation protection .............................................................................................. 18
Voltage imbalance ........................................................................................................................................................18
Approvals and certications ....................................................................19
Approvals and certicates ..........................................................................................................................................19
Pressure equipment directive 97/23/EC ................................................................................................................ 19
Low voltage directive 73/23/EC, 93/68/EC ...........................................................................................................19
Internal free volume .....................................................................................................................................................19
Operating conditions ...............................................................................20
Refrigerant and lubricants .......................................................................................................................................... 20
Motor supply ...................................................................................................................................................................21
Compressor ambient temperature ..........................................................................................................................21
Application envelope ................................................................................................................................................... 21
R22, R407C Model variation T ....................................................................................................................................21
R410A Model variation T .............................................................................................................................................22
R22, R410A Model variation U ...................................................................................................................................22
Maximum discharge gas temperature ................................................................................................................... 22
High and low pressure protection ...........................................................................................................................24
On/o cycling (cycle rate limit) .................................................................................................................................24
Application Guidelines
4 FRCC.PC.012.A6.22
System design recommendations ...........................................................25
General ..............................................................................................................................................................................25
Essential piping design considerations .................................................................................................................25
Refrigerant charge limit ..............................................................................................................................................26
Crankcase heater............................................................................................................................................................28
Reversible heat pump systems .................................................................................................................................29
Loss of charge protection ...........................................................................................................................................29
Tandem .............................................................................................................................................................................. 29
Oil level checking and top-up ................................................................................................................................... 29
Minimum sump superheat .........................................................................................................................................29
High pressure ratio ........................................................................................................................................................ 29
Phase sequence and reverse rotation protection .............................................................................................. 29
Internal motor protection ...........................................................................................................................................30
Preventing liquid ood back .....................................................................................................................................30
Testing for excessive liquid ood back ..................................................................................................................30
Split unit cooling mode ............................................................................................................................................... 30
Water utilising systems ................................................................................................................................................30
Sound and vibration management .........................................................31
Starting sound level ...................................................................................................................................................... 31
Running sound level ..................................................................................................................................................... 31
Stopping sound level ...................................................................................................................................................31
Sound generation in a refrigeration system / air conditioning system .....................................................31
Compressor sound radiation ..................................................................................................................................... 31
Mechanical vibrations .................................................................................................................................................. 32
Gas pulsation ...................................................................................................................................................................32
Installation ................................................................................................33
System cleanliness.........................................................................................................................................................33
Compressor handling and storage ..........................................................................................................................33
Compressor mounting .................................................................................................................................................33
Compressor holding charge ......................................................................................................................................33
Tube brazing procedure .............................................................................................................................................. 33
Brazing material .............................................................................................................................................................33
Vacuum evacuation and moisture removal .........................................................................................................34
Liquid line lter driers ..................................................................................................................................................35
Refrigerant charging .....................................................................................................................................................35
Insulation resistance and dielectric strength ......................................................................................................35
Compressor replacement after motor burn out ................................................................................................. 35
Ordering information and packaging .....................................................36
Packaging .........................................................................................................................................................................36
Packaging details ........................................................................................................................................................... 36
R22 Single pack ..............................................................................................................................................................37
R22 Industrial pack ........................................................................................................................................................ 38
R407C Single pack .........................................................................................................................................................39
R407C Industrial pack ...................................................................................................................................................40
R410A Single pack ......................................................................................................................................................... 41
R410A Industrial pack ..................................................................................................................................................42
Spare parts & accessories .........................................................................43
Run capacitors for PSC wiring ...................................................................................................................................43
Start capacitors and starting relay for CSR wiring .............................................................................................43
Rotolock adaptor set ....................................................................................................................................................43
Rotolock adaptor ...........................................................................................................................................................44
Crankcase heater............................................................................................................................................................44
Discharge temperature protection .........................................................................................................................44
Lubricant ........................................................................................................................................................................... 44
Mounting hardware ...................................................................................................................................................... 45
Content
Application Guidelines
5FRCC.PC.012.A6.22
Scroll compression principle
The motor stator is rigidly attached to the shell.
The rotor is shrink-t onto the eccentric shaft. The
shaft is supported by two bearings, one in the
crankcase and the second below the motor.
Scroll compressor
components
Shell
Eccentric shaft
Stator
Rotor
Counterweight
Slider block
Lifting lug
Check valve
Magnet
Discharge tube
Fixed scroll
Orbiting scroll
Terminal cover
Electric terminal
Lower bearing
Application Guidelines
6 FRCC.PC.012.A6.22
Scroll compressor principle
The entire scroll compression process is illustrated
below. The centre of the orbiting scroll traces a
circular path around the centre of the xed scroll.
This movement creates compression pockets
between the two scroll elements.
Low pressure suction gas is trapped within each
crescent-shaped pocket as it forms; continuous
motion of the orbiting scroll serves to seal
the pocket, which decreases in volume as the
pocket moves towards the centre of the scroll
set, with corresponding increase in gas pressure.
Maximum compression is achieved, as the pocket
reaches the discharge port at the centre.
Scroll compression is a continuous process: when
one pocket of gas is being compressed during
the second orbit, another gas quantity enters
a new pocket formed at the periphery, and
simultaneously, another is being discharged.
The scroll
compression process
H-series color The H-series compressors can be black or blue
depending on the production site.
Danfoss scroll compressors are manufactured
using the most advanced machining, assembly,
and process control techniques. In design of
both the compressor and the factory, very high
standards of reliability and process control were
rst priority. The result is a highly ecient product
with the highest reliability obtainable, and a low
sound level.
SUCTION
COMPRESSION
DISCHARGE
Application Guidelines
7FRCC.PC.012.A6.22
Compressor model designation
Label
Nomenclature
Type FeaturesMotorSize
HRH P6U1L
036
Application:
H: high temperature / air conditioning
Family:
C: commercial scroll
R: residential scroll (new platform)
L: light commercial scroll (new platform)
Refrigerant & lubricant:
M: R22, alkylbenzene lubricant
P: R407C, PVE lubricant
H: R410A, PVE lubricant
J: R410A, PVE lubricant
Nominal capacity:
In thousand Btu/h at 60 Hz,
ARI conditions
Model variation
T: design optimized for 45/130°F
U: design optimized for 45/100°F
Motor voltage code
1: 208-230V/1~/60 Hz
2: 200-220V/3~/50Hz & 208-230V/3~/60 Hz
4: 380-415V/3~/50 Hz & 460V/3~/60 Hz
5: 220-240V/1~/50 Hz
7: 500V/3~/50 Hz & 575V/ 3~/60 Hz
9: 380V/3~/60 Hz
Motor protection
L: internal motor protection
Tubing and electrical connections
P: brazed connections, spade terminals
C: brazed connections, screw terminals
Other features
Oil sight
glass
Oil equali-
sation
Oil
drain
LP gauge
port
Gas equa-
li-sation port
None
6
None
None
None
Brazed Brazed
None
None
None
None
None
None
None
None
Threaded
7
8
None Screw NoneSchrader None
T
Version T compressors are built with a threaded oil equalization port to be used with our variable speed compressors range VZH.
Application Guidelines
8 FRCC.PC.012.A6.22
Technical specifications
60-Hz data *
Model
Nominal
Cap. 60 Hz
Nominal cooling capacity Power input A max. Eciency
Swept
volume
Displacement Oil charge Net weight
TR W Btu/h kW A COP W/W EER Btu/h/W cu.in/rev cu.ft/h oz lbs
R22
HRM032U4 2.7 9 320 31 790 2.94 9.5 3.17 10.8 2.66 323 36 71
HRM034U4 2.8 9 810 33 480 3.07 9.5 3.20 10.9 2.82 343 36 71
HRM038U4 3.2 11 130 37 980 3.39 10.0 3.28 11. 2 2.82 343 36 71
HRM040U4 3.3 11 720 39 980 3.57 10.0 3.28 11. 2 3.32 403 36 71
HRM042U4 3.5 12 300 41 980 3.75 11. 0 3.28 11. 2 3.49 424 36 71
HRM045U4 3.8 13 180 44 980 4.01 12.0 3.28 11.2 3.75 456 45 71
HRM047U4 3.9 13 920 47 490 4.22 12.0 3.30 11. 3 3.91 475 45 71
HRM048U4 4.0 13 830 47 180 4.25 12.5 3.25 11.1 3.93 477 53 86
HRM051T4 4.3 15 030 51 270 4.46 13.0 3.37 11. 5 4.20 510 53 86
HRM051U4 4.3 15 030 51 280 4.46 13.0 3.37 11. 5 4.20 510 53 86
HRM054U4 4.5 15 730 53 680 4.62 13.1 3.40 11. 6 4.45 541 53 90
HRM058U4 4.8 16 930 57 780 5.02 15.0 3.37 11. 5 4.77 580 53 90
HRM060T4 5.0 17 490 59 670 5.14 15.0 3.40 11.6 4.94 600 53 90
HRM060U4 5.0 17 490 59 680 5.19 15.0 3.37 11. 5 4.94 600 53 90
HLM068T4 5.7 20 190 68 880 5.94 15.0 3.40 11. 6 5.68 690 53 90
HLM072T4 6.0 21 330 72 770 6.27 15.0 3.40 11.6 6.02 732 53 90
HLM075T4 6.3 22 120 75 480 6.45 16.0 3.43 11. 7 6.27 762 53 90
HLM081T4 6.8 23 880 81 470 6.96 17.0 3.43 11.7 6.77 823 53 90
HCM094T4 7.8 27 690 94 470 8.07 21.0 3.43 11.7 7. 69 934 90 104
HCM109T4 9.1 32 020 109 270 9.33 24.0 3.43 11.7 9.08 110 4 90 104
HCM120T4 10.0 34 950 119 260 10.22 25.0 3.42 11. 7 9.91 1204 90 104
R407C
HRP051T4 4.3 14 380 49080 4.46 13.0 3.23 11. 0 4.20 510 53 86
R410A
HRH029U4 2.4 8 500 29 000 2.84 10.0 2.99 10.2 1.70 206 36 71
HRH031U4 2.6 9 080 30 990 3.04 10.0 2.99 10.2 1.82 221 36 71
HRH032U4 2.7 9 380 31 990 3.10 10.0 3.02 10.3 1.87 227 36 71
HRH034U4 2.8 10 110 34 510 3.38 10.0 2.99 10.2 2.03 245 36 71
HRH036U4 3.0 10 370 35 390 3.47 10.0 2.99 10.2 2.12 258 36 71
HRH038U4 3.2 11 10 0 37 890 3.79 12.0 2.93 10.0 2.23 271 36 86
HRH040U4 3.3 12 160 41 490 4.03 12.0 3.02 10.3 2.42 293 45 86
HRH041U4 3.3 12 100 41 300 4.05 12.5 2.99 10.2 2.40 293 53 86
HRH044U4 3.7 13 010 44 390 4.31 13.5 3.02 10.3 2.60 316 53 86
HRH049U4 4.1
14 360 48 990 4.66 13.5 3.08 10.5 2.89 351 53 86
HRH051U4 4.3 15 180 51 780 4.84 13.0 3.14 10.7 3.01 366 53 90
HRH054U4 4.5 15 970 54 480 5.14 15.0 3.11 10.6 3.18 386 53 90
HRH056U4 4.7 16 670 56 880 5.36 15.0 3.11 10.6 3.30 401 53 90
HLH061T4 5.1 18 050 61 580 5.70 15.0 3.17 10.8 3.53 428 53 90
HLH068T4 5.7 20 130 68 670 6.30 19.0 3.20 10.9 3.93 477 53 90
HLJ072T4 6.0 21 240 72 500 6.65 19.0 3.19 10.9 4.15 504 53 90
HLJ075T4 6.3 22 320 76 190 6.86 18.0 3.25 11.1 4.32 525 53 90
HLJ083T4 6.9 24 340 83 090 7. 55 19.0 3.22 11.0 4.77 579 53 90
HCJ090T4 7.5 26 810 91 500 8.47 19.0 3.16 10.8 5.30 644 90 97
HCJ091T4 7. 5 27 140 92 600 8.37 17.0 3.24 11. 07 5.30 644 83 108
HCJ105T4 8.8 31 170 106 390 9.75 25.0 3.20 10.9 6.20 754 90 97
HCJ106T4 8.8 31 670 108 050 9.67 20.0 3.28 11.18 6.20 754 83 108
HC J120T4 10.0 35 620 121 600 11.15 27.0 3.20 10.9 7.10 863 90 97
HC J121T4 10.0 35 940 122 620 11. 07 21.0 3.25 11.08 7.10 863 83 108
TR = Ton of Refrigeration *: ARI standard rating conditions, Evaporating temperature : 45 °F
COP = Coecient Of Performance 460V / 3ph / 60Hz Condensing temperature: 130 °F
EER = Energy Eciency Ratio Superheat: 20 °F
Sub-cooling: 15 °F
Subject to modication without prior notication
For full data details and capacity tables refer to Online Datasheet Generator : www.danfoss.com/odsg
Application Guidelines
9FRCC.PC.012.A6.22
Technical specications
50-Hz data *
Model
Nominal Cap
60 Hz
Nominal cooling capacity Power input A max. Eciency
Swept
volume
Displacement Oil charge Net weight
TR W Btu/h kW A COP W/W EER Btu/h/W cu.in/rev cu.ft/h oz lbs
R22
HRM032U4 2.7 7 850 26 790 2.55 9.5 3.08 10.5 2.66 268 36 71
HRM034U4 2.8 8 350 28 490 2.66 9.5 3.14 10.7 2.82 284 36 71
HRM038U4 3.2 9 240 31 520 2.94 10.0 3.14 10.7 2.82 284 36 71
HRM040U4 3.3 9 710 33 120 2.98 10.0 3.26 11.1 3.32 334 36 71
HRM042U4 3.5 10 190 34 770 3.13 11.0 3.26 11.1 3.49 351 36 71
HRM045U4 3.8 10 940 37 310 3.45 12.0 3.17 10.8 3.75 378 45 71
HRM047U4 3.9 11 500 39 250 3.57 12.0 3.23 11. 0 3.91 394 45 71
HRM048U4 4.0 11 510 39 270 3.57 12.5 3.23 11.0 3.93 396 53 86
HRM051T4 4.3 12 390 42 280 3.67 13.0 3.37 11. 5 4.20 423 53 86
HRM051U4 4.3 12 800 43 690 3.83 13.0 3.34 11.4 4.20 423 53 86
HRM054U4 4.5 13 390 45 680 3.97 13.1 3.37 11. 5 4.45 448 53 90
HRM058U4 4.8 14 340 48 930 4.25 15.0 3.37 11. 5 4.77 480 53 90
HRM060T4 5.0 14 570 49 720 4.28 15.0 3.40 11.6 4.94 498 53 90
HRM060U4 5.0 14 820 50 580 4.40 15.0 3.37 11. 5 4.94 498 53 90
HLM068T4 5.7 16 880 57 580 5.00 15.0 3.37 11. 5 5.68 572 53 90
HLM072T4 6.0 17 84 0 60 870 5.29 15.0 3.37 11. 5 6.02 607 53 90
HLM075T4 6.3 18 430 62 880 5.37 16.0 3.43 11. 7 6.27 631 53 90
HLM081T4 6.8 19 890 67 880 5.80 17. 0 3.43 11.7 6.77 682 53 90
HCM094T4 7.8 23 060 78 670 6.80 21.0 3.39 11. 6 7.69 774 90 104
HCM109T4 9.1 26 690 91 070 7.7 7 24.0 3.43 11.7 9.08 914 90 104
HCM120T4 10.0 29 130 99 390 8.51 25.0 3.42 11.7 9.91 998 90 104
R407C
HRP034T4 2.8 7 940 27 080 2.68 9.5 2.96 10.1 2.82 283 36 71
HRP038T4 3.2 8 840 30 150 2.82 11.0 3.14 10.7 3.15 317 36 71
HRP040T4 3.3 9 110 31 080 3.14 11. 5 2.90 9.9 3.32 334 36 71
HRP042T4 3.5 9 580 32 680 3.30 10.0 2.90 9.9 3.49 351 36 71
HRP045T4 3.8 10 810 36 890 3.58 12.0 3.02 10.3 3.75 378 45 71
HRP047T4 3.9 11 130 37 980 3.69 12.0 3.02 10.3 3.91 394 45 71
HRP048T4 4.0 11 10 0 37 880 3.35 12.0 3.31 11. 3 3.93 396 53 86
HRP051T4 4.3 12 120 41 370 3.83 13.0 3.17 10.8 4.20 423 53 86
HRP054T4 4.5 12 570 42 880 3.97 12.5 3.17 10.8 4.44 447 53 90
HRP058T4 4.8 13 470 45 970 4.25 14.0 3.17 10.8 4.77 480 53 90
HRP060T4 5.0 13 860
47 280 4.26 15.0 3.25 11.1 4.94 498 53 90
HLP068T4 5.7 15 700 53 560 5.10 15.0 3.08 10.5 5.68 572 53 90
HLP072T4 6.0 16 810 57 350 5.16 15.0 3.26 11.1 6.02 606 53 90
HLP075T4 6.3 18 040 61 550 5.54 16.0 3.26 11.1 6.27 631 53 90
HLP081T4 6.8 18 600 63 470 5.66 17.0 3.28 11. 2 6.77 682 53 90
HCP094T4 7.8 21 590 73 660 6.63 21.0 3.26 11.1 7. 69 774 90 104
HCP109T4 9.1 25 070 85 550 7.77 24.0 3.23 11.0 9.08 914 90 104
HCP120T4 10.0 27 370 93 400 8.47 25.0 3.23 11.0 9.91 998 90 104
R410A
HRH029U4 2.4 7 120 24 310 2.43 10.0 2.93 10.0 1.70 171 36 71
HRH031U4 2.6 7 530 25 710 2.67 10.0 2.82 9.62 1.82 183 36 71
HRH032U4 2.7 7 670 26 170 2.75 10.0 2.79 9.51 1.87 188 36 71
HRH034U4 2.8 8 500 29 000 2.90 10.0 2.93 10.0 2.03 203 36 71
HRH036U4 3.0 8 820 30 110 3.13 10.0 2.82 9.62 2.12 213 36 71
HRH038U4 3.2 9 250 31 560 3.35 12.0 2.76 9.41 2.23 225 36 86
HRH040U4 3.3 10 200 34 810 3.58 12.0 2.85 9.72 2.42 244 45 86
HRH041U4 3.3 10 050 34 300 3.43 12.5 2.93 10.00 2.40 240 53 86
HRH044U4 3.7 10 830 36 940 3.92 13.5 2.76 9.41 2.60 262 53 86
HRH049U4 4.1 12 110 41 320 4.04 13.5 2.99 10.22 2.89 291 53 86
HRH051U4 4.3 12 860 43 890 4.21 13.0 3.05 10.42 3.01 303 53 90
HRH054U4 4.5 13 340 45 510 4.41 15.0 3.02 10.32 3.18 320 53 90
HRH056U4 4.7 13 830 47 200 4.58 15.0 3.02 10.31 3.30 333 53 90
HLH061T4 5.1 15 210 51 880 4.89 15.0 3.11 10.61 3.53 357 53 90
HLH068T4 5.7 16 880 57 610 5.26 19.0 3.21 10.96 3.93 396 53 90
HLJ072T4 6.0 17 840 60 900 5.56 19.0 3.21 11.0 4.15 417 53 90
HLJ075T4 6.3 18 600 63 490 5.77 18.0 3.22 11.0 4.32 435 53 90
HLJ083T4 6.9 20 420 69 690 6.28 19.0 3.25 11.1 4.77 480 53 90
HCJ090T4 7.5 22 320 76 190 7.19 19.0 3.11 10.6 5.30 534 90 97
HCJ091T4 7.5 22 380 76 360 7.03 18.0 3.18 10.87 5.30 534 83 108
HCJ105T4 8.8 26 100 89 090 8.25 25.0 3.16 10.8 6.20 624 90 97
HCJ106T4 8.8 26 050 88 880 8.07 21.0 3.23 11.01 6.20 624 83 108
HCJ120T4 10.0 29 610 101 080 9.53 27.0 3.11 10.6 7.10 715 90 97
HCJ121T4 10.0 29 720 101 400 9.22 22.0 3.22 11.0 7.10 715 83 108
TR = Ton of Refrigeration *: ARI standard rating conditions, Evaporating temperature : 45 °F
COP = Coecient Of Performance 400V / 3ph / 50Hz Condensing temperature: 130 °F
EER = Energy Eciency Ratio Superheat: 20 °F Sub-cooling: 15 °F
Subject to modication without prior notication
For full data details and capacity tables refer to Online Datasheet Generator : www.danfoss.com/odsg
Application Guidelines
10 FRCC.PC.012.A6.22
Dimensions
Mounting grommetTerminal box
Refer to page 43 for overview of shipped mounting
accessories
HRM032-034-038-040-042 / HRP034-038-040-042 / HRH029-031-032-034-036-038 /
HRM-045-047 / HRP-045-047 / HRH039-040
Quick connect spade terminals
P terminal box type
0.067
1.614
Ø 1.614
1.161
5/16” - 18 UNC
self tapping
Recommended torque for mounting bolts:
8 ft.lbs (±1ft.lbs)
Ø 0.433
9.40
4 x Ø 0.75 - 0.78
3.750
5.06
4.38
2.74 - 2.80
34°
31°
45°
14°
4.32
3.750
7.491 - 7.509
9.40
7.491 - 7.509
(1) HRM032-034-038-040-042 / HRP034-038-040-042 / HRH029-031-032-034-036-038
(2) HRM-045-047 / HRP-045-047 / HRH039-040
(1) 15.53
(2) 16.53
Suction line
(1) 0.753 - 0.757
(2) 0.881
6.438 - 6.515
2.84 - 2.95
(1) 14.19
(2) 15.19
(1) 7.76
(2) 8.67
(1) 9.09
(2) 10.09
0.42
0.75
Discharge line
0.502 - 0.506
P6
All dimensions in inch
Application Guidelines
11FRCC.PC.012.A6.22
Dimensions
Terminal boxes
HRM048-051-054-058-060 / HLM068-072-075-078-081 / HRP048-051-054-058-060 /
HLP068-072-075-078-081 / HRH041-044-049-051-054-056 / HLH061-068 / HLJ072-075-083
Ring connect screw terminals
C terminal box type
C
T₁
S
T₂
R
T₃
9.41
7.491 - 7.509
3.750
5.44
(1) 4.76
(2) 4.80
2.74-2.80
7.187 - 7.265
Suction line
0.878 - 0.885
Discharge line
(1) 0.502-0.506
(2) 0.755
2.84 - 2.95
15.85
8.86
10.27
0.43
0.75
17.16
34°
31°
45°
14°
4 x Ø 0.75-0.78
9.41
7.491 - 7.509
4.66
3.750
(1) HRM048-051-054-058-060 / HLM068-072-075 / HRP048-051-054-058-060 /
HLP068-072-075 / HRH041-044-049-051-054-056 / HLH061-068 / HLJ072-075-083
(2) HLM078-081 / HLP078-081
All dimensions in inch
P6
9.41
7.491 - 7.509
3.750
5.26
(1) 4.76
(2) 4.8
3.10 - 3.17
7.187 - 7.265
Suction line
0.878-0.885
Discharge line
(1) 0.502-0.506
(2) 0.755
3.63 - 3.70
15.85
7.97
10.27
0.75
0.43
17.16
34°
31°
45°
14°
4 x Ø 0.75 - 0.78
9.41
7.491 - 7.509
4.69
3.750
(1) HRM048-051-054-058-060 / HLM068-072-075 / HRP048-051-054-058-060 /
HLP068-072-075 / HRH041-044-049-051-054-056 / HLH061-068 / HLJ072-075-083
(2) HLM078-081 / HLP078-081
All dimensions in inch
C6
Quick connect spade terminals
P terminal box type
Mounting grommet
Refer to page 43 for overview of shipped mounting
accessories
0.067
1.614
Ø 1.614
1.161
5/16” - 18 UNC
self tapping
Recommended torque for mounting bolts:
8 ft.lbs (±1ft.lbs)
Ø 0.433
Application Guidelines
12 FRCC.PC.012.A6.22
Dimensions
HCM/HCP 094-109-120
9.13
7.491 - 7.509
3.750
4.84
7.211 - 7.288
3.63 - 3.70
(1) 19.29
(2) 19.67
11.28
0.28
13.79
(1) 20.35
(2) 20.72
(1) HCM/HCP 094
(2) HCM/HCP 109-120
All dimensions in inch
Suction line
1.128-1.135
Discharge line
0.878-0.885
3.10-3.17
34°
31°
45°
14°
4.93
3.750
9.13
7.491 - 7.509
4 x Ø 0.75 - 0.78
5.24
0.75
C6
Mounting grommetTerminal box
Refer to page 43 for overview of shipped mounting
accessories
Ring connect screw terminals
C terminal box type
C
T₁
S
T₂
R
T₃
0.067
1.614
Ø 1.614
1.161
5/16” - 18 UNC
self tapping
Recommended torque for mounting bolts:
8 ft.lbs (±1ft.lbs)
Ø 0.433
Application Guidelines
13FRCC.PC.012.A6.22
Dimensions
HCJ090-105-120
HCJ090-105-120
All dimensions in inch
9.41
9.41
3.750
3.750
5.24
4.84
3.10 - 3.17
19.36
11.59
0.43
14.10
20.41
3.63 - 3.70
4.93
4 x Ø 0.75 - 0.78
7.211 - 7.288
Discharge line
0.878-0.885
Suction line
1.128-1.135
45°
34°
31°
14°
7.491 - 7.509
7.491 - 7.509
0.75
Terminal boxes
Ring connect screw terminals
C terminal box type
C
T₁
S
T₂
R
T₃
Mounting grommet
Refer to page 43 for overview of shipped mounting
accessories
0.067
1.614
Ø 1.614
1.161
5/16” - 18 UNC
self tapping
Recommended torque for mounting bolts:
8 ft.lbs (±1ft.lbs)
Ø 0.433
Application Guidelines
14 FRCC.PC.012.A6.22
Dimensions
HCJ091-106-121
9.41
7.49 - 7.51
3.75
4 x Ø 0.75 - 0.78
5.24
4.84
3.10 - 3.16
34° 31°
45°
14°
4.93
3.75
7.49 - 7.51
9.41
7.21 - 7.28
Suction line
1.128 - 1.135
21.08
14.77
0.43
3.63 - 3.70
12.26
20.01
Discharge line
0.87 - 0.88
HCJ091-106-121
All dimensions in inch
Mounting grommetTerminal box
Refer to page 43 for overview of shipped mounting
accessories
Ring connect screw terminals
C terminal box type
C
T₁
S
T₂
R
T₃
0.067
1.614
Ø 1.614
1.161
5/16” - 18 UNC
self tapping
Recommended torque for mounting bolts:
8 ft.lbs (±1ft.lbs)
Ø 0.433
Application Guidelines
15FRCC.PC.012.A6.22
Dimensions
Mounting grommetTerminal box
Refer to page 43 for overview of shipped mounting
accessories
Ring connect screw terminals
C terminal box type
C
T₁
S
T₂
R
T₃
0.067
1.614
Ø 1.614
1.161
5/16” - 18 UNC
self tapping
Recommended torque for mounting bolts:
8 ft.lbs (±1ft.lbs)
Ø 0.433
HLH061-HLJ072-
HLJ083
9.41
7.49 - 7.50
3.75
4 x Ø 0.75 -0.78
3.75
7.49 - 7.50
9.41
4.69
5.26
4.76
3.10 - 3.17
34°
31°
14°
73°
45°
7.18 - 7.26
Suction line
0.878 - 0.885
Discharge line
0.502 - 0.506
92.0 - 94.0
15.85
10.27
17.16
7.97
0.43
2.23
3.36
All dimensions in inch
Version T compressors are built with a threaded oil equalization port to be used with our variable speed compressors range VZH.
Application Guidelines
16 FRCC.PC.012.A6.22
Electrical data, connections and wiring
Scroll compressors are available in 6 dierent motor voltages.
Motor voltage
Danfoss scroll compressors will only compress gas
while rotating counter-clockwise (when viewed
from the compressor top). Since single-phase
motors will start and run in only one direction,
reverse rotation is not a major consideration.
Three-phase motors, however, will start and
run in either direction, depending on the phase
angles of the supplied power. Care must be taken
during installation to ensure that the compressor
operates in the correct direction (see “Phase
sequence and reverse rotation protection”).
The drawings below show electrical terminal
labelling and should be used as a reference
when wiring the compressor. For three phase
applications, the terminals are labelled T1, T2, and
T3. For single-phase applications the terminals
are labelled C (common), S (start), and R (run).
Prior to energizing, verify that leads and terminal
connectors are in proper working condition.
Warning: For safety reasons, make voltage
measurements at the unit contactor, not at
compressor terminals. Always keep the terminal
cover in place when the compressor is energized.
The terminal cover and gasket should be installed
prior to operation of the compressor. The terminal
cover has two outside tabs, 180 degrees apart,
that engage the terminal fence. When installing
the cover, check that it is not pinching the lead
wires. Both the inside of the terminal cover and
the gasket have labels for the terminal pins: C
(common), R (run), and S (start).
Wiring connections
Terminal cover mounting
Terminal cover removal
Ring connect screw terminals
C terminal box type
C
T₁
S
T₂
R
T₃
Quick connect spade terminals
P terminal box type
push
push
push
Motor voltage
code 1
Motor voltage
code 2
Motor voltage
code 4
Motor voltage
code 5
Motor voltage
code 7
Motor voltage
code 9
Nominal voltage
50 Hz
- 200-220V-3-50 Hz 380-415V-3-50 Hz 220-240V-1-50 Hz 500V-3-50 Hz -
Voltage range
50 Hz
- 180 - 242 342 - 457 198 - 264 450 - 550 -
Nominal voltage
60 Hz
208-230V-1-60 Hz 208-230V-3-60 Hz 460V-3-60 Hz - 575V-3-60 Hz 380V-3-60 Hz
Voltage range
60 Hz
187 - 253 187 - 253 414 - 506 - 517 - 632 342 - 418
Application Guidelines
17FRCC.PC.012.A6.22
Electrical data, connections and wiring
If start assist is required, in case of operating
below the nominal voltage, a CSR starting device
is required.
During start-up, the start winding (C-S) is
energised through an electromagnetic potential
relay and a start capacitor.
A permanent (run) capacitor is wired between the
start winding (C-S) and the run winding (C-R).
CSR wiring
The compressor terminal box IP rating according to CEI 529 is IP22 for all models. IP ratings is only valid
when correctly sized cable glands of the IP rating is applied.
First numeral, level of protection against contact and foreign objects
2 protection against object size over 1/2 inch (ngers of similar)
Second numeral, level of protection against water
2 protection against dripping water when tilted up to 1
IP rating
LRA is the higher average current as measured on
a mechanically blocked compressor tested under
nominal voltage. LRA is printed on the nameplate.
The LRA value can be used as a rough estimation
for the starting current. However in most cases,
the real starting current will be lower. Many
countries have dened limits for the starting
current in domestic use. A soft starter can be
applied to reduce starting current.
The MCC is the current at which the internal
motor protection trips under maximum load and
low voltage conditions.
This MCC value is the maximum at which
the compressor can be operated in transient
conditions and out of the application envelope.
Above this value the overload will switch o to
protect the motor.
MCC (Maximum
Continuous Current)
LRA (Locked Rotor
Amp)
Winding resistance
Danfoss scroll compressors are designed to
operate without any assistance if running within
the dened nominal voltage. PSC wiring is
sucient (see below).
The start winding (C-S) of the motor remains in
circuit through a permanent (run) capacitor.
This permanent (run) capacitor is connected
between the start winding (C-S) and the run
winding (C-R).
Electrical connections
PSC wiring
C
S
R
Line
Run
Capacitor
Start
Capacitor
Potential
Relay
1
2
5
C
S
R
Line
Run
Capacitor
Winding resistance is the resistance between
indicated terminal pins at 77°F (resistance value
±7%).
Winding resistance is generally low and it
requires adapted tools for precise measurement.
Use a digital ohm-meter, a ‘4 wires’ method and
measure under stabilised ambient temperature.
Winding resistance varies strongly with winding
temperature ; If the compressor is stabilised at a
dierent value than 77°F, the measured resistance
must be corrected with following formula:
a + t
amb
R
tamb
= R
77°F
_______
a + t
77°F
t
77°F
: reference temperature = 77°F
t
amb
: temperature during measurement (°F)
R
77°F
: winding resistance at 77°F
R
amb
: winding resistance at t
amb
coecient a= 390
Application Guidelines
18 FRCC.PC.012.A6.22
Electrical data, connections and wiring
Nominal capacitor
value and relays
The compressor will only operate properly in a
single direction. Use a phase meter to establish
the phase orders and connect line phases L1, L2
and L3 to terminals T1, T2 and T3, respectively.
For three-phase compressors, the motor will run
equally well in both directions. Reverse rotation
results in excessive noise; no pressure dierential
between suction and discharge; and suction line
warming rather than immediate cooling. A service
technician should be present at initial start-up to
verify that supply power is properly phased and
that compressor and auxiliaries are rotating in the
correct direction.
DanfossH-series through Hxx075 scroll
compressors are designed to operate for a
maximum of 150 hours in reverse, but as a reverse
rotation situation can go unnoticed for longer
periods, phase monitors are recommended.
For compressors Hxx078 and larger, phase
monitors are required. The selected phase
monitor should lock out the compressor from
operation in reverse.
At brief power interruptions, reverse rotation can
occur with single phase compressors. In this case
the internal protector will stop the compressor.
It will have to cool down and will restart safely
afterwards.
For three-phase applications the voltage
measured at the compressor terminals for each
phase should be within ± 2% of the average for
all phases.
Phase sequence and
reverse rotation
protection
Voltage imbalance
Internal motor
protection
Danfoss scroll compressors are equipped with
an internal line break protector mounted on the
motor windings. The protector is an automatic
reset device, containing a snap action bimetal
switch.
Internal protectors respond to over-current and
overheating. They are designed to interrupt
motor current under a variety of fault conditions,
such as failure to start, running overload, and fan
failure.
If the internal overload protector trips out, it must
cool down to about 140°F to reset. Depending on
ambient temperature, this may take up to several
hours.
Models
PSC wiring
Run capacitor
CSR wiring
Start capacitor
Relay
60 Hz, motor voltage code 1
R22
HRM032-034 45 μF 145-175 μF/370V RVA 2AC3D
HRM038 55 μF 88-108 μF/370V RVA 2AB3D
HRM040-042-045-047 60 μF 88-108 μF/370V RVA 2AB3D
HRM048 60 μF 161-193 μF/370V RVA 2AB3D
HRM051-054 70 μF 161-193 μF/370V RVA 2AB3D
HRM058T1-060T1 55 μF 88-108 μF/370V RVA 4AG3D
HRM058U1-060U1, HLM068-072-075-081 80 μF 189-227 μF/370V RVA 2AB3D
R407C
HRP051 70 μF 161-193 μF/370V RVA 2AB3D
HLP068-072-075-081 80 μF 189-227 μF/370V RVA 2AB3D
R410A
HRH031 45 μF 145-175 μF/370V RVA 2AC3D
HRH032-034 50 μF 88-108 μF/370V RVA 2AB3D
HRH036 55 μF 88-108 μF/370V RVA 2B3D
HRH038-039-040 60 μF 88-108 μF/370V RVA 2AB3D
HRH041-044-048-049-050-051 70 μF 161-193 μF/370V RVA 2AB3D
HRH054-056, HLH068, HLJ072-083 80 μF 189-227 μF/370V RVA 2AB3D
50 Hz, motor voltage code 5
R22
HRM032-034-038-040-042 70 μF 145-175 μF/440V RVA 2B3D
HRM045-047 60 μF 145-175 μF/440V RVA 2B3D
HRM051 50 μF 161-193 μF/440V RVA 3E3D
HRM054 55 μF 161-193 μF/440V RVA 3E3D
HRM058-060 55 μF 88-108 μF/440V RVA 4G3D
HLM068-072-075-081 55 μF 88-108 μF/440V RVA 4G3D
R407C
HRP034-038-040-042 70 μF 145-175 μF/440V RVA 2B3D
HRP045-047 60 μF 145-175 μF/440V RVA 2B3D
HRP051 50 μF 161-193 μF/440V RVA 3E3D
HRP054 55 μF 161-193 μF/440V RVA 3E3D
HRP058-060 55 μF 88-108 μF/440V RVA 4G3D
HLP068-072-075-081 55 μF 88-108 μF/440V RVA 4G3D
R410A
HRH031-032-034-036 70 μF 145-175 μF/440V RVA 2B3D
HRH038-040 60 μF 145-175 μF/440V RVA 2B3D
HRH050-051-054-056-061 55 μF 88-108 μF/440V RVA 4G3D
HLH068, HLJ072-083 55 μF 88-108 μF/440V RVA 4G3D
Application Guidelines
19FRCC.PC.012.A6.22
Approvals and certifications
Danfoss H-series compressors comply with the
following approvals and certicates.
Certicates are listed on the product datasheets:
http://www.danfoss.com/odsg
Approvals and
certicates
Pressure equipment
directive 97/23/EC
Low voltage directive
73/23/EC, 93/68/EC
Internal free volume
CE 0062 or CE 0038
(European Directive)
All models
UL
(Underwriters Laboratories)
All 60 Hz models
Other approvals / certicates Contact Danfoss
Products
Manufacturer's declaration of incorporation
ref. EC Machines Directives 98/392/CE
Contact Danfoss
Products
Refrigerating uids Group 2
Category PED I
Evaluation module no scope
Products
Internal free volume at LP
side without oil (gallon)
Internal free volume at HP
side without oil (gallon)
HRM/P032-034-038-040-042
HRH029-031-032-034-036-038
0.77 0.13
HRM/P045-047
HRH040
0.84 0.18
HRM/P048-051-054-058-060, HLM/P068-072-075-081
HRH044-049-051-054-056, HLH/J061-068-072-075-083
0.90 0.19
HCM/P094-109-120
HCJ090-105-120
1.56 0.13
HCJ091-106-121 1.51 0.13
Application Guidelines
20 FRCC.PC.012.A6.22
Operating conditions
The Danfoss scroll compressor H-Series
application range is inuenced by several
parameters which need to be monitored for a
safe and reliable operation.
These parameters and the main recommendations
for good practice and safety devices are explained
hereunder.
Refrigerant and lubricants
Motor supply
Compressor ambient temperature
Application envelope (evaporating
temperature, condensing temperature, return
gas temperature)
General information
Refrigerant and
lubricants
When choosing a refrigerant, dierent aspects
must be taken into consideration:
• Legislation (now and in the future)
• Safety
Application envelope in relation to expected
running conditions
• Compressor capacity and eciency
Compressor manufacturer recommendations &
guidelines
Additional points could inuence the nal choice:
• Environmental considerations
Standardisation of refrigerants and lubricants
• Refrigerant cost
• Refrigerant availability
Alkylbenzene oil
Oil type
Residual moisture
PVE Polyvinyl ether (PVE) is an innovative refrigeration
lubricant for HFC refrigerant systems. PVE is as
hygroscopic as existing polyolester lubricants
(POE), but PVE doesn’t chemically react with
water; no acids are formed and compressor
evacuation is easier.
The compressor technology applied in Danfoss
H-series scroll compressors in combination with
PVE lubricant provides the best possible result in
terms of reliability and compressor lifetime.
The PVE lubricant is compatible with R22 which
makes the Danfoss H-series scroll compressors a
very versatile multi- refrigerant solution.
Alkylbenzene oil can be applied in systems
using HCFC refrigerants (R22). Compared to
a mineral oil it provides distinct advantages:
excellent miscibility, excellent thermal stability,
compatibility with mineral oils and constant
quality.
Danfoss Scroll H_M series compressors are
charged with Alkylbenzene oil and herewith
oer an economically interesting alternative to
the Danfoss H series in regions where R22 is still
the predominant refrigerant. Note however that
Danfoss H-series scroll compressors can not be
used with HFC refrigerants.
Danfoss scroll compressors are charged with
oil at the factory with the oils indicated, in the
following table.
Eective week 31 of 2009, the HRP/HLP/HCP &
HRH/HLH series of compressors were changed
from POE oil to PVE oil. Compressors produced
prior to this week still had POE, and may be in stock
in the warehouses until supply is exhausted. This
change was made to standardize to the better oil
for reliability. Replacement PVE 320HV is available
for topping up or replacing oil in the eld (see
accessory section). As it is fully miscible with POE,
Danfoss recommends the 320HV regardless of
original oil charge in the compressor.
Prior to shipment from the factory, every
compressor is dehydrated, evacuated, and
charged with dry nitrogen. Maximum residual
moisture levels are 0.0082 oz. for models
capacities up to HRM/HRP047 and HRH040 and
0.0120 oz. for larger compressors.
Compressor range Oil type
HRM / HLM / HCM Alkylbenzene
HRP / HLP / HCP PVE
HRH / HLH PVE
HLJ/HCJ PVE
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48