MasterCool ANALOG VACUUM GAUGE Operating instructions

Type
Operating instructions

MasterCool ANALOG VACUUM GAUGE is a high-quality measuring instrument for accurate vacuum readings. The large 80mm gauge makes it easier to read than smaller gauges, and the indicator needle to mark pressure for testing provides a backup in case you forget to write the pressure down. The barometric pressure compensation lets you know if you are at maximum vacuum even at altitudes above sea level and the local weather conditions. This gauge is perfect for checking system vacuum level, reading absolute zero, and leak testing.

MasterCool ANALOG VACUUM GAUGE is a high-quality measuring instrument for accurate vacuum readings. The large 80mm gauge makes it easier to read than smaller gauges, and the indicator needle to mark pressure for testing provides a backup in case you forget to write the pressure down. The barometric pressure compensation lets you know if you are at maximum vacuum even at altitudes above sea level and the local weather conditions. This gauge is perfect for checking system vacuum level, reading absolute zero, and leak testing.

1www.mastercool.com
ANALOG VACUUM GAUGE
Mastercool’s hand-held analog vacuum, class 1.0, gauge is designed
with the highest quality to provide accurate readings every time.
SPECIFICATIONS
• Gauge size: 80 mm
• Units: inhg 30-0 and mbar 0-1000
• Atmospheric pressure compensation: 1065-655 mbar
• Accuracy: EU Class 1, ASME Grade 1A
FEATURES
Large, 80mm gauge makes it easier and more accurate to read than smaller gauges
Indicator needle to mark pressure for testing provides a backup in case you forget to write the pres-
sure down. You can see if the pressure has changed with a quick glance
Barometric pressure compensation lets you know if you are at maximum vacuum even at altitudes
above sea level and the local weather conditions
WARNING
THIS GAUGE IS ONLY FOR VACUUM. Positive pressure will immediately damage the gauge. If you damage the
gauge with positive pressure, Mastercool will not replace the gauge under warranty.
INSTRUCTIONS
1. Checking system vacuum level:
For best system vacuum reading, connect gauge directly to the system, close to an access port. Using
this gauge, you will be able to read how deep of a vacuum is being achieved.
Once the pressure on the gauge stops decreasing, the system is under the most vacuum that can be
achieved with the system and your setup. If the vacuum does not come close to absolute zero (see
#2), there could be a leak or some refrigerant left in the system.
NOTE: How long the vacuum pump needs to be run depends on the size of the system under vacuum
and your vacuum pump.
2. Reading absolute zero:
a. Obtain the local barometric pressure. This
can be found on various weather websites. A
local airport will have the barometric pressure.
An approximation can be done by looking at a
chart that has the decrease in pressure due to
altitude, assuming you know your altitude.
b. Find the barometric pressure on the small
outer scale (fig 1). That will be absolute zero
- the lowest vacuum reading that can be
achieved.
A
T
M
O
S
P
H
E
R
I
C
P
R
E
S
S
U
R
E
C
O
M
P
E
N
S
A
T
I
O
N
200
100
300
400
500
600
700
800
900
1000
0
w
w
w
.
m
a
s
t
e
r
c
o
o
l
.
c
o
m
1000
900
800
700
655
1065
98065
class 1.0
inHg
mbar
30
25
15
20
10
5
0
mbar
FIGURE 1
A
T
M
O
S
P
H
E
R
I
C
P
R
E
S
S
U
R
E
C
O
M
P
E
N
S
A
T
I
O
N
200
100
300
400
500
600
700
800
900
1000
0
w
w
w
.
m
a
s
t
e
r
c
o
o
l
.
c
o
m
1000
900
800
700
655
1065
98065
class 1.0
inHg
mbar
30
25
15
20
10
5
0
mbar
2 www.mastercool.com
3. Leak testing procedure:
a. Connect directly to system through an access port with a T fitting and ball valve as (fig 2).
b. Run vacuum pump until desired vacuum level is reached.
c. Mark the vacuum level using the red indicator needle, by turning the knob in the center of the
gauge. It would be best practice to write the pressure down as well.
d. Close the ball valve. For best results, remove the hoses and place a cap on the ball valve.
e. Allow for a minimum of 5 minutes for system to stabilize. If the pressure increases during the five
minutes, there is a leak in the system or fittings, and/or the system still has some refrigerant left
in it. Reattach the hoses and run the vacuum pump for a long period of time. Then repeat, closing
the ball valve and waiting five minutes. If the vacuum increases slower than before, there is still
some refrigerant or water in the system. If it goes up at the same rate, there is a leak. Be sure to
check the gaskets on the vacuum gauge, tee and ball valve to make sure they are clean and in good
shape.
f. After the allotted vacuum test time (we recommend at least 15 minutes) view the gauge to check
for a leak. If the red leak test indicator is still directly in line with the black needle on the vacuum
gauge you should not have a leak in the system. If you notice that the needle on the gauge has
drifted higher and is not aligned with the leak test indicator, it can be a sign of a leak in your system.
AIR CONDITIONING
or
REFRIGERATION SYSTEM
FIGURE 2
A
T
M
O
S
P
H
E
R
I
C
P
R
E
S
S
U
R
E
C
O
M
P
E
N
S
A
T
I
O
N
200
100
300
400
500
600
700
800
900
1000
0
w
w
w
.
m
a
s
t
e
r
c
o
o
l
.
c
o
m
1000
900
800
700
655
1065
98065
class 1.0
inHg
mbar
30
25
15
20
10
5
0
mbar
98065-INST
  • Page 1 1
  • Page 2 2

MasterCool ANALOG VACUUM GAUGE Operating instructions

Type
Operating instructions

MasterCool ANALOG VACUUM GAUGE is a high-quality measuring instrument for accurate vacuum readings. The large 80mm gauge makes it easier to read than smaller gauges, and the indicator needle to mark pressure for testing provides a backup in case you forget to write the pressure down. The barometric pressure compensation lets you know if you are at maximum vacuum even at altitudes above sea level and the local weather conditions. This gauge is perfect for checking system vacuum level, reading absolute zero, and leak testing.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI