CLA-VAL 136-03 Quick Manual

Type
Quick Manual

This manual is also suitable for

CLA-VAL 136-03 is an automatic solenoid control valve designed to either close drip tight or open fully by a Three-Way Solenoid Control. It is a hydraulically operated, diaphragm type globe or angle valve. The valve is suitable for use in a variety of applications, including water, oil, gas, and chemical. The 136-03 is available in sizes from 1/2" to 8" and can be used with pressures up to 200 psi. The valve is also available with a variety of optional features, including flow clean strainers, isolation valves, check valves, and pressure gauges.

CLA-VAL 136-03 is an automatic solenoid control valve designed to either close drip tight or open fully by a Three-Way Solenoid Control. It is a hydraulically operated, diaphragm type globe or angle valve. The valve is suitable for use in a variety of applications, including water, oil, gas, and chemical. The 136-03 is available in sizes from 1/2" to 8" and can be used with pressures up to 200 psi. The valve is also available with a variety of optional features, including flow clean strainers, isolation valves, check valves, and pressure gauges.

4. Check that solenoid (2) is set to close main valve. Slowly open
the gate or block valve upstream of the valve.
5. Carefully loosen tube fittings at highest points and bleed air
from system. Carefully loosen the plug at top of main valve cover.
If X101 Valve Position Indicator is installed, carefully open the
bleed valve at top of Indicator. Bleed air from cover and tighten
plug or bleed screw. Tighten tube fittings.
6. Slowly open downstream gate or block valve. Check the oper-
ation of the valve by energizing and de-energizing the solenoid.
The valve should open fully and close drip tight.
Need minimum 5 psi differential under flowing coditions.
MAINTENANCE
1. Cla-Val Valves and Controls require no lubrication or packing
and a minimum of maintenance. However, a periodic inspection
schedule should be established to determine how the fluid han-
dled is affecting the efficiency of the valve assembly. Minimum of
once per year.
2. Repair and adjustment procedures of the Cla-Val Hytrol main
valve and control components are included in a more detailed
IOM manual. It can be downloaded from our web site (www.cla-
val.com) or by contacting a Cla-Val Regional Sales Office.
3. When ordering parts always refer to the catalog number
and stock number on the valve nameplate.
Solenoid Control Valve
136-03/636-03
MODEL
INSTALLATION / OPERATION / MAINTENANCE
INTRODUCTION
The Cla-Val Model 136-03/636-03 Solenoid Control Valve is an
automatic valve designed to either close drip tight or open fully by
means of a Three-Way Solenoid Control. It is a hydraulically oper-
ated, solenoid controlled, diaphragm type globe or angle valve.
INSTALLATION
1. Allow sufficient room around the valve assembly to make
adjustments and for disassembly.
Note: Before the valve is installed, the pipeline should be
flushed to remove all chips, scale and foreign matter.
2. It is recommended that gate or line block valves be installed
upstream and downstream of the Model136-03/636-03 to facilitate
isolating the valve for preventive maintenance.
3. Place the valve in the line with flow in the direction of flow
arrows or by the inlet nameplate. Check all fittings and hardware
for proper makeup and that no apparent damage is evident. Be
sure main valve cover nuts/bolts are tight. Pressure in some appli-
cations can be very high so be thorough in checking and inspect-
ing for proper installation and makeup.
4. Cla-Val Valves operate with maximum efficiency when mounted
in horizontal piping with the cover UP; however, other positions are
acceptable. Due to size and weight of cover and internal compo-
nents of six inch valves and larger, installation with the cover up is
advisable. This makes periodic inspection of internal parts readily
accessible.
5. Caution must be taken in the installation of this valve to insure
that galvanic and/or electrolytic action does not take place. The
proper use of dielectric fittings and gaskets are required in all sys-
tems using dissimilar metals.
6. Comply with local and national electrical codes when wiring the
Solenoid Control.
OPERATION AND START-UP
1. Prior to pressurizing the valve assembly make sure the neces-
sary gauges to measure pressure in the system are installed as
required by the system engineer. A Cla-Val Model X101 Valve
Position Indicator can be installed in the center cover port to pro-
vide visual indication of the valve diaphragm assembly position
during start-up.
CAUTION: During start-up and test procedures a large volume of
water may be discharged downstream. Check that the downstream
venting is adequate to prevent damage to personnel and equip-
ment. If the main valve closes too fast it may cause surging in
upstream piping.
2. If isolation valves (B) are installed in pilot system open these
valves. (see schematic).
3. The three-way Solenoid Control applies or relieves pressure in
the 102E three-way valve cover chamber. This, in turn, applies or
relieves pressure in the main valve cover chamber. The following
action takes place:
Note: Solenoids are not reversible because of different internal
construction between Energize to open and De-energize to open
solenoids.
SOLENOID CONTROL(2)
POSITION
ENERGIZED
DE-ENERGIZED
FLOW
1TO2
3TO1
THREE-WAY
VALVE FLOW(3)
COM. TO N.O.
N.C. TO COM.
MAIN
VALVE (1)
OPEN
CLOSED
THREE-WAY
VALVE FLOW(3)
N.C. TO COM.
COM. TO N.O.
MAIN
VALVE 1
CLOSED
OPEN
ENERGIZED TO OPEN
136-03 SERIES
DE-ENERGIZED TO OPEN
136-03 SERIES
SYMPTON PROBABLE CAUSE REMEDY
Main Valve
Fails to Close
No flow condition Inspect downstream piping for
closed valve or obstruction
Too low pressure differential
across valve
Need minimum 5psi differential
under flow coditions
Restrict valve opening with
Cla-Val X102A
limiting assembly
(Contact Cla-Val)
Closed isolation valves in pilot
system, or in main line
Open valves
Lack of cover chamber pressure Check upstream
pressure, tubing needle
valves for restriction
Diaphragm damaged Replac diaphragm
Mechanical obstruction
Object lodged in valve
Worn disc
Remove obstruction
Replace disc
Badly scored seat Replace seat
CNA needle valve closed Open this speed control to
allow pressure to cover
Main Valve
Fails to Open
Closed isolation valves in pilot
system, or in main line
Insufficient line pressure
Diaphragm assembly inoperative
Open valves
Clean & polish stem
Replace and defective or
damaged parts
Main Valve
Vibrates when
Closed
Air in cover Bleed all air from valve
102E
COVER
PIPE PLU
G
COVER BEARING
SPRING
STEM NUT
DIAPHRAGM WASHER
DISC RETAINER
BODY
*
SPACER WASHERS
DISC GUIDE
SEAT
PIPE PLUG
STEM
SEAT O-RING
STUD
8" and Larger
*
DIAPHRAGM
*
DISC
*
Repair Parts
Seat Screw
8" and Larger
(Globe
or
Angle)
PIPE PLUG
HEX NUT
8" and Larger
Cover Bolt
6" and Smaller
FLAT WASH
FLAT WASHER
1
A
OUTLETINLET
CS3
1
32
DRAIN TO
ATMOSPHERE
INDEPENDENT
OPERATING
PRESSURE
1
Note: "D" Feature and "H" feature
cannot be ordered together
H
B
P2
D2
D3
V
P3
B
B
P1
F
Y
D1
32
COM.
N.C.
N.O.
4A
4B
For a more detailed IOM Manual go to www.cla-val.com or contact a Cla-Val Regional Sales Office.
CLA-VAL
Copyright Cla-Val Printed in USA Specifications subject to change without notice.
1701 Placentia Ave Costa Mesa CA 92627 Phone: 949-722-4800 E-mail: info@cla-val.com www.cla-val.com
©
N-136-03/636-03 (R-04/2023)
136-03/636-03 SCHEMATIC
HYTROL MAIN VALVE
OPTIONALFEATURES
A X46A Flow Clean Strainer
B CK2 (Isolation Valve)
D Check Valves with Isolation Valve
F Independent Operating Pressure
H Atmospheric Drain
P X141 Pressure Gauge
S CNA Angle Needle Valve (Opening)
V X101 ValveY X43Y Strainer
BASICCOMPONENTS
1 100-01 Hytrol (Main Valve)
100-20 600 Series Hytrol (Main Valve)
2 CS3 Solenoid Control
3 102E Three-Way Valve
4 CNA Angle Needle Valve (Closing)
Wiring must comply with local and
National Electrical Codes. For valves
equipped with an explosion-proof,
watertight solenoid enclosure, the elec-
trical fittings must be approved for use
in the approved hazardous locations.
Housings for all solenoids have con-
nections for 1/2 inch conduit. The
enclosure may be rotated to facilitate
wiring.
SOLENOID WIRING
CS3
2
CNA
4X46A
A
CK2
B
CV
C
X43
Y
102E
3
CDC-1
D
Manual Operator
(Optional)
*SUGGESTED REPAIR PARTS
Cover
Socket Head
Cap Screw
Lower
Diaphragm
Washer
Body
Lower Disc
Spring
Upper
Diaphragm
Washer
Diaphragm
O-Ring
O-Ring
O-Ring
Fitting
Washer
Hex Nut
Stem
Lower Seat
3
  • Page 1 1
  • Page 2 2

CLA-VAL 136-03 Quick Manual

Type
Quick Manual
This manual is also suitable for

CLA-VAL 136-03 is an automatic solenoid control valve designed to either close drip tight or open fully by a Three-Way Solenoid Control. It is a hydraulically operated, diaphragm type globe or angle valve. The valve is suitable for use in a variety of applications, including water, oil, gas, and chemical. The 136-03 is available in sizes from 1/2" to 8" and can be used with pressures up to 200 psi. The valve is also available with a variety of optional features, including flow clean strainers, isolation valves, check valves, and pressure gauges.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI