  • Hello! I have analyzed the provided specification document for the Cerberus Pyrotronics FM-200 Extinguishing System. This document details the system's components, including cylinders, nozzles, and control equipment. It also provides information about installation, operation, and compliance with various safety standards. I'm ready to answer your questions about the system.
  • What is the pressure in the cylinders?
    What material are the nozzles made of?
    What standards does the system comply with?
6014
CATALOG NUMBER
FM-200TM Extinguishing Systems
Automatic Pre-Engineered Modular Type
ENGINEER AND ARCHITECT SPECIFICATIONS
General Requirements
There shall be furnished a Cerberus Pyrotronics Balanced
Modular Type Extinguishing System for total flooding protection
of the hazard. The protection shall be provided by one or by an
interconnected group of single cylinder systems as necessary to
achieve the specified concentration. Each cylinder shall be
individually piped to the nozzles served by that cylinder. The
system design shall be suitable for the purpose intended and
shall be in accordance with the Factory Mutual approval, the
Underwriters Laboratories, Inc. listing, as identified by ULC File
No. CEX590 and with NFPA Standard No. 2001 Clean Agent Fire
Extinguishing Agent Systems.
The system shall be installed in full compliance with the manu-
facturers installation manual referenced in the UL listing, the FM
approval and with NFPA Standard No. 2001.
Cylinders
The cylinders shall be manufactured, tested and marked in
accordance with D.O.T. Specification 4BW500 or 4BA500. Eight
(8) different sizes of cylinders are available, they are 10 lb.,
20 lb., 40 lb., 70 lb., 125 lb., 200 lb., 350 lb. and 500 lb. capaci-
ties.
The cylinders shall be charged with FM-200TM and shall be
superpressurized with dry nitrogen to a total pressure of 360
psig (24.84 bars) at 70°F (21.1°C) to assure rapid discharge and
reliable operation at temperatures as low as -40°F (-40°C).
Cylinders larger than 70 pounds capacity shall be fitted with
lifting lugs for ease of handling. Cylinders shall be furnished with
bracketing suitable for secure mounting.
Each cylinder shall be furnished with a cylinder pressure
supervisory switch to cause a supervisory signal at the control
panel if the pressure in the cylinder drops to approximately 220
psig. Cylinders with a capacity of 200 pounds or more shall be
fitted with a liquid level indicating device for determining the
weight of the FM-200TM charge in the cylinders. The device shall
consist of a brass diptube with a stainless steel float riding on
the outside of the diptube and a magnetic tape within the
diptube. Both the tape and the float shall be fitted with magnets
capable of coupling so as to suspend the tape with its calibra-
tions easily read at the entry to the diptube, indicating the actual
liquid level in the cylinder.
A graph shall be provided to translate the tape reading to
pounds of FM-200TM at the cylinder temperature.
Cylinder Valves
The cylinder valves shall have a brass body and shall be of a
pressure seated, high flow rate design incorporating a brass
piston with seal, pressure releasing pilot check assembly, safety
disc assembly, pressure actuation outlet port and pressure
gauge. Cylinder valves on electrically actuated master control
cylinders shall have a connection for an electric solenoid valve.
The solenoid valve shall be easily removable from the cylinder
valve to facilitate cylinder removal and servicing.
The cylinder valves shall be provided with an anti-recoil plug
fitted to the valve discharge outlet to prevent rocketing or
spinning of the cylinder in the event of discharge while the
cylinder is not bracketed or not otherwise held securely in place.
Nozzles
The nozzles shall be brass and shall be of a type specified in the
UL listing and FM approval and suitable for the purpose
intended. They shall be marked with the manufacturer’s identify-
ing part number.
The nozzles shall have a standard female pipe thread for
attachment to the discharge piping. Nozzles shall be spaced in
accordance with the instructions in the installation manual and
as required by the UL listing and FM approval.
Pipe and Fittings
Ferrous piping either black or galvanized, conforming to ASTM
A-53 or A-106, or other materials confirming to these strength
requirements shall be used. The thickness of the pipe wall shall
be calculated in accordance with ANSI B-31.1, Power Piping
Code. All fittings used shall be 300 pound or 600 pound class in
accordance with NFPA Standard 2001.
All pipe ends shall be thoroughly reamed after cutting, and all oil
and chips shall be removed. Dry air or nitrogen shall be blown
through the piping to remove chips or other debris prior to
installation of the nozzles.
All piping shall be securely fastened with particular attention
being given to fastening near nozzles to prevent pipe movement
due to the reaction force during discharge.
Control Equipment
The system shall be designed for automatic electric operation
and for manual operation. When the cylinder is not so located as
to be readily accessible at the time of fire, a remote manual
control of either the mechanical type (preferred) or the electrical
type shall be used.
Automatic release shall be by a Cerberus Pyrotronics CP-2ER
Agent Release Panel or System 3 model HC-35 or RM-30U
Control Module connected to a cross-zoned detector circuit or
an MXL Control Panel using its custom software utilizing
detectors of the best type suited for the hazard. The signal from
the control panel shall open the solenoid valves on the control
cylinders, thus causing the cylinder valves to open.
firealarmresources.com
November 1996
Supersedes sheet dated 9/95
11/96
1M
CPY-IG
Printed in U.S.A.
Cerberus Pyrotronics
50 East Pearce Street
Richmond Hill, Ontario
L4B, 1B7 CN
Tel: (905) 764-8384
FAX: (905) 731-9182
Cerberus Pyrotronics
8 Ridgedale Avenue
Cedar Knolls, NJ 07927
Tel: (201) 267-1300
FAX: (201) 397-7008
In multiple cylinder installations, the first cylinder and every fourth
cylinder thereafter shall be a master cylinder. The remaining
cylinders shall be pressure actuated by means of pressure
actuators fitted to their cylinder valves. Each master cylinder shall
have its pressure actuation outlet port utilized for interconnection
with the pressure actuators on the pressure actuated cylinders.
Nitrogen pilot cylinders shall be used to pressure actuate up to
15 cylinders as per the instructions in the installation manual.
Pressure operated switches, operating upon release of the FM-
200TM into the discharge piping, shall be provided to shut down
the electric power for the ventilation system and all electrically
powered equipment within the hazard and to sound an alarm, if
these functions are not performed by the detection system.
Pressure-operated trips, operating upon release of the FM-
200TM into the discharge piping, shall be provided for release of
door and damper closing hardware, if these functions are not
performed by the detection system.
System Checkout
Upon completion of system installation, a final checkout
inspection shall be made by a qualified inspector trained by the
manufacturer.
Warranty
All materials furnished by the manufacturer are to be warranted
against defects in material or workmanship for a period of two
years from the date of manufacture.