Fujitsu ARGA36FMTA-Q Installation guide

Type
Installation guide
PART No. 9381386024-02
AIR CONDITIONER
INDOOR UNIT ( Duct Type )
INSTALLATION MANUAL
For authorized service personnel only.
English
MADE IN THAILAND
9381386024-02_IM_EN.indd 1 5/16/2019 3:11:27 PM
En-1
1. SAFETYPRECAUTIONS
• Be sure to read this manual thoroughly before installation.
• The warnings and precautions indicated in this Manual contain important information
pertaining to your safety. Be sure to observe them.
• Hand this Manual, together with the operating manual, to the customer. Request the
customer to keep them on hand for future use, such as for relocating or repairing the unit.
WARNING
Indicates a potentially or imminently hazardous situation which,
if not avoided, could result in death or serious injury.
Installation of this product must be done by experienced service technicians or profes-
sional installers only in accordance with this manual. Installation by nonprofessional or
improper installation of the product may cause serious accidents such as injury, water
leakage, electric shock, or re. If the product is installed in disregard of the instructions
in this manual, it will void the manufacturer’s warranty.
Do not turn on the power until all work has been completed. Turning on the power
before the work is completed can cause serious accidents such as electric shock or
re.
If refrigerant leaks when you are working, ventilate the area. If the leaking refrigerant
is exposed to a direct ame it may produce a toxic gas.
Do not use this equipment with air or any other unspecied refrigerant in the refriger-
ant lines. Excess pressure can cause a rupture.
Installation must be performed in accordance with regulations, codes, or standards for
electrical wiring and equipment in each country, region, or the installation place.
Do not touch the ns of the heat exchanger. Touching the heat exchanger ns could
result in damage to the ns or personal injury such as skin rupture.
CAUTION
Indicates a potentially hazardous situation that may result in
minor or moderate injury or damage to property.
Read carefully all safety information written in this manual before you install or use the
air conditioner.
Install the product by following local codes and regulations in force at the place of instal-
lation, and the instructions provided by the manufacturer.
This product is part of a set constituting an air conditioner. The product must not be
installed alone or be installed with non-authorized device by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all
wires with a distance between contact of 3 mm for this product.
To protect the persons, earth (ground) the product correctly, and use the power cable
combined with an Earth Leakage Circuit Breaker (ELCB).
The product is not explosion proof, and therefore should not be installed in explosive
atmosphere.
To avoid getting an electric shock, never touch the electrical components soon after the
power supply has been turned off. After turning off the power, always wait 5 minutes or
more before you touch the electrical components.
This product contains no user-serviceable parts. Always consult experienced service
technicians for repairing.
When moving or relocating the air conditioner, consult experienced service technicians
for disconnection and reinstallation of the product.
Do not place any other electrical products or household belongings under the product.
Condensation dripping from the product might get them wet, and may cause damage or
malfunction of the property.
This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children should be supervised to ensure that they do
not play with the appliance.
2. ABOUTTHISPRODUCT
2.1.PrecautionsforusingR410Arefrigerant
WARNING
Do not introduce any substance other than the prescribed refrigerant into the refrigera-
tion cycle. If air enters the refrigeration cycle, the pressure in the refrigeration cycle
will become abnormally high and cause the piping to rupture.
If there is a refrigerant leak, make sure that it does not exceed the concentration limit.
If a refrigerant leak exceeds the concentration limit, it can lead to accidents such as
oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other
area. Touching the refrigerant directly can cause frostbite.
If a refrigerant leak occurs during operation, immediately vacate the premises and
thoroughly ventilate the area. If the refrigerant comes in contact with a ame, it pro-
duces a toxic gas.
2.2.SpecialtoolsforR410Arefrigerant
WARNING
To install a unit that uses R410A refrigerant, use dedicated tools and piping materi-
als that have been manufactured specically for R410A use. Because the pressure
of R410A refrigerant is approximately 1.6 times higher than the R22, failure to use
dedicated piping material or improper installation can cause rupture or injury.
Furthermore, it can cause serious accidents such as water leakage, electric shock, or re.
Toolname Changes
Gaugemanifold
The pressure in the refrigerant system is extremely high
and cannot be measured with a conventional gauge.
To prevent erroneous mixing of other refrigerants,
the diameter of each port has been changed. It is
recommended to use a gauge manifold with a high
pressure display range of –0.1 to 5.3 MPa and a low
pressure display range of –0.1 to 3.8 MPa.
Charginghose
To increase pressure resistance, the hose material and
base size were changed.
(The charging port thread diameter for R410A is 1/2-20
UNF.)
Vacuumpump
A conventional vacuum pump can be used by installing a
vacuum pump adapter.
Be sure that the pump oil does not backow into the
system. Use one capable for vacuum suction of
–100.7 kPa (5 Torr, –755 mmHg).
Gasleakagedetector Special gas leakage detector for R410A refrigerant.
1. SAFETY PRECAUTIONS ……………………………………………………………… 1
2. ABOUT THIS PRODUCT ………………………………………………………………… 1
2.1. Precautions for using R410A refrigerant ………………………………………… 1
2.2. Special tools for R410A refrigerant ……………………………………………… 1
2.3. Accessories ………………………………………………………………………… 2
2.4. Optional parts ……………………………………………………………………… 2
3. GENERAL SPECIFICATION …………………………………………………………… 2
3.1. Selecting the pipe material ………………………………………………………… 2
3.2. Pipe requirement …………………………………………………………………… 2
3.3. Electrical requirement ……………………………………………………………… 2
4. INSTALLATION WORK ………………………………………………………………… 3
4.1. Selecting an installation location ………………………………………………… 3
4.2. Installation dimension ……………………………………………………………… 3
4.3. Installing the unit …………………………………………………………………… 4
4.4. Installing the drain hose …………………………………………………………… 4
4.5. Intake duct connection …………………………………………………………… 5
4.6. Fresh air intake ……………………………………………………………………… 5
5. PIPE INSTALLATION …………………………………………………………………… 6
5.1. Pipe connection …………………………………………………………………… 6
5.2. Installing heat insulation …………………………………………………………… 6
6. ELECTRICAL WIRING …………………………………………………………………… 7
6.1. Wiring method ……………………………………………………………………… 7
7. REMOTE CONTROLLER SETTING …………………………………………………… 8
7.1. Installing the remote controller …………………………………………………… 8
7.2. Setting the DIP switches …………………………………………………………… 9
8. FUNCTION SETTING …………………………………………………………………… 9
8.1. Turning on the power ……………………………………………………………… 9
8.2. Setting method ……………………………………………………………………… 9
8.3. Setting the room temperature detection location ……………………………… 9
8.4. Function Details ………………………………………………………………… 10
8.5. Jumper wire setting ……………………………………………………………… 11
9. SPECIAL INSTALLATION METHODS ……………………………………………… 11
9.1. Group control system …………………………………………………………… 11
9.2. Fan delay setting ………………………………………………………………… 11
10. OPTIONAL PARTS …………………………………………………………………… 12
11. CHECK LIST …………………………………………………………………………… 12
12. TEST RUN ……………………………………………………………………………… 12
13. CUSTOMER GUIDANCE ……………………………………………………………… 12
14. ERROR CODES ……………………………………………………………………… 13
AIR CONDITIONER
INSTALLATIONMANUAL
PART No. 9381386024-02
Indoor Unit (Duct Type)
Contents
Note: This manual describes how to install the air conditioner described above. Handling
and installation shall only be done by professionals as outlined in this manual.
9381386024-02_IM_EN.indd 1 5/16/2019 3:11:27 PM
En-2
2.3.Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit falling,
water leakage, electric shock, or re.
• The following installation parts are furnished. Use them as required.
• Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
NameandShape Q’ty Description
Operating Manual
1
Installation Manual
2
Specication Manual
1
Special nut A
(large ange)
4
For suspending the indoor unit
from ceiling
Special nut B
(small ange)
4
Washer
8
Coupler heat insulation (large)
1
For indoor side pipe joint
(gas pipe)
Coupler heat insulation (small)
1
For indoor side pipe joint
(liquid pipe)
Cable tie (large)
4 For xing the heat insulation
Cable tie (medium)
1
For xing the remote controller
cable
Cable tie (small)
1
For xing the remote controller
cable
Remote controller
(WAE type)
1 For air conditioner operation
Tapping screw
(ush heads)
2
For installing the remote
controller
Remote controller cable
1
For connecting the remote
controller
Drain hose insulation
1
Insulates the drain hose and
vinyl hose
Drain hose
1
For installing drain pipe
VP25 (O.D.32, I.D.25)
Hose Band
1 For installing drain hose
2.4.Optionalparts
Partsname ModelNo. Summary
Remote sensor UTY-XSZX
New amenity space can
be offered by installing the
Remote sensor
External control set UTD-ECS5A
Use to connect various
peripheral devices and air
conditioner PC board
3. GENERALSPECIFICATION
3.1.Selectingthepipematerial
CAUTION
Do not use existing pipes.
Use pipes that have clean external and internal sides without any contamination which
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion (es-
pecially on the interior surface). Otherwise, the expansion valve or capillary tube may
become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using R410A in-
curs pressure higher than when using conventional refrigerant, it is necessary to choose
adequate materials.
• Thicknesses of copper pipes used with R410A are as shown in the table.
• Never use copper pipes thinner than those indicated in the table even if they are available
on the market.
Pipeoutsidediameter[mm(in.)] Thickness[mm]
6.35 (1/4) 0.8
9.52 (3/8) 0.8
12.70 (1/2) 0.8
15.88 (5/8) 1.0
19.05 (3/4) 1.2
3.2.Piperequirement
CAUTION
Refer to the Installation Manual of the outdoor unit for description of the length of con-
necting pipe or for difference of its elevation.
Diameter[mm(in.)]
Liquid
9.52 (3/8)
Gas
19.05 (3/4)
• Use pipe with water-resistant heat insulation.
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may
cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70 %, install heat insulation around the refrigerant piping.
If the expected humidity level is 70-80 %, use heat insulation that is 15 mm or thicker
and if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or
thicker. If heat insulation is used that is not as thick as specied, condensation may
form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
3.3.Electricalrequirement
Cable Cablesize(mm
2
) Type Remarks
Connection cable 1.5 (MIN.) Type 60245 IEC57 3Cable+Earth (Ground),
220 - 240V
Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage
drop is 2% or more.
• Perform all electrical work according to the standard.
• Install circuit breakers, which have the terminal spacing of more than 3 mm, in a place of
near the indoor unit and outdoor unit.
CAUTION
Be sure to execute the electrical work according to the Laws of each country and the
Installation Instructions. In addition, be sure to set as exclusive line and use the rated
voltage and circuit breaker.
9381386024-02_IM_EN.indd 2 5/16/2019 3:11:29 PM
En-3
4.2.Installationdimension
Unit:mm
150 or
more
300 or more
2500 or more
(When no ceiling)
20 or more
20 or more
Provide a service access for maintenance purposes.
(Bottomside) Unit:mm
AIR
Control box
300 or more
500 or more
500 or more
Service access
* The service access necessary for fan units and lter maintenance.
(Bottomside) Unit:mm
AIR
Service access
Fan unit side
300 or more
500 or more
1800 or more
100
4. INSTALLATIONWORK
WARNING
Do not turn on the power until all installation work is complete.
Carrying and installation of the unit should be performed by a sufcient number of
people and with sufcient equipment that is adequate for the weight of the unit.
Performing such work with an insufcient number of people or with inadequate equip-
ment could result in dropping of the unit or personal injury.
CAUTION
For installation details, refer to the technical data.
4.1.Selectinganinstallationlocation
Decide the mounting position together with the customer as follows.
WARNING
Select installation locations that can properly support the weight of the indoor unit
and which will not amplify sound or vibration. If the installation location is not strong
enough, the indoor unit may fall and cause injuries.
Install the units securely so that they do not topple or fall.
CAUTION
Do not install the indoor unit in the following areas:
• Area with high salt content, such as at the seaside.
It will deteriorate metal parts, causing the parts to fall or the unit to leak water.
• Area lled with mineral oil or containing a large amount of splashed oil or steam,
such as a kitchen.
It will deteriorate plastic parts, causing the parts to fall or the unit to leak water.
• Area that generates substances that adversely affect the equipment, such as sulfuric
gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to
corrode, which can cause refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon bers or
ammable dust, or volatile inammables such as paint thinner or gasoline. If gas
leaks and settles around the unit, it can cause a re.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects. It can degrade the quality of the
preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or ammable gas.
Install the unit where drainage does not cause any trouble.
Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote
control cable at least 1 m away from a television or radio receivers. The purpose of this
is to prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still receive noise under
some signal conditions.)
Install the unit where ambient temperature does not reach 60°C or more.
Take a measure such as ventilation for an environment in which heat is retained.
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
(1) Install the indoor unit in a place which can withstand a load of at least 5 times the
weight of the unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) Install the unit where connection to the outdoor unit is easy.
(5) Install the unit where the connection pipe can be easily installed.
(6) Install the unit where the drain pipe can be easily installed.
(7) Install the unit where noise and vibrations are not amplied.
(8) Take servicing, etc., into consideration and leave the spaces. Also install the unit where
the lter can be removed.
(9) Do not install the unit where it will be exposed to direct sunlight.
Correct initial installation location is important because it is difcult to move unit after it is
installed.
9381386024-02_IM_EN.indd 3 5/16/2019 3:11:30 PM
En-4
4.3.Installingtheunit
WARNING
Carrying and installation of the unit should be performed by a sufcient number of
people and with sufcient equipment that is adequate for the weight of the unit. Per-
forming such work with an insufcient number of people or with inadequate equipment
could result in dropping of the unit or personal injury.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
When fastening the hangers, make the bolt positions uniform.
CAUTION
Conrm the directions of the air intake and outlet before installing the unit.
Hanging bolt installation diagram.
Unit:mm
(Rightside)
57
22
218
256
222
25
22
(Topside)
750
700
630
1400
1440
1500
Hanging bolt M10
(Locally procured)
Special nut A (Accessory)
Washer
(Accessory)
Special nut B
(Accessory)
Hanger
BoltStrength 9.81 to 14.71 N·m (100 to 150 kgf·cm)
WARNING
Fasten the unit securely with special nuts A and B so that the unit does not fall.
Leveling
Base vertical direction leveling on the unit (right and left).
(Rightside)
Level
AIR
AIR
Base horizontal direction leveling on top of the unit.
Drain hose
0 – 5 mm
Level
Give a slight tilt to the side to which the drain hose is connected. The tilt should be in the
range of 0 mm to 5 mm.
4.4.Installingthedrainhose
CAUTION
Install the drain hose in accordance with the instructions in this installation instruction
sheet and keep the area warm enough to prevent condensation. Problems with the
piping may lead to water leaks.
Install the drain hose according to the measurements given in the following gure.
Unit:mm
280
40
300
65
145
29
Drain pipe
Ø32 mm (O.D.)
(Rightside)
How to install the drain hose
(1) Install the drain hose (accessory) to the drain port of the indoor unit. Attach the hose
band around the hose within the dimension shown. Secure rmly with the hose band.
(2) Attach the drain pipe (locally procured). Use general hard polyvinyl chloride pipe (VP25)
[outside diameter 38 mm] and connect it with adhesive (polyvinyl chloride) so that there
is no leakage.
(3) Check the drainage.
(4) Wrap the drain hose insulation around the drain hose connection.
Drain hose
(Accessory)
5~10 mm
4 mm or less
20 mm
Hose band (Accessory)
Soft PVC side
Joint pipe
(Locally procured)
Drain pipe (VP25)
(Locally procured)
Area to
apply
adhesive
15 mm
Indoor unit
Indoor unit
Drain hose
100 mm
Drain hose insulation
(Accessory)
Hose band (Accessory)
Overlap the heat insulation.
Drain hose insulation
(Accessory)
9381386024-02_IM_EN.indd 4 5/16/2019 3:11:31 PM
En-5
NOTE:
• Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises or
traps in the pipe.
Drain
pipe
Outlet
airow
Arrange the drain pipe
lower than this portion
OK
Rise
PROHIBITED
Trap
• When the pipe is long, install supporters.
Supporter
1.5 to 2 m
• Do not perform air bleeding.
Air bleeding
4.5.Intakeductconnection
Follow the procedure in the following gure.
(Back side)
1400 mm
300 mm
The air inlet duct can be changed by replacing the intake grille and service panel.
For the bottom air intake, position (1) the intake grille, and (2) the service panel, as shown
in the following gure. (The factory setting is back air intake.)
(2)
(1)
CAUTION
To prevent people from touching the parts inside the unit, be sure to install grilles on
the inlet and outlet ports. The grilles must be designed in such a way that cannot be
removed without tools.
When air is taken in from the bottom side, the operating sound of the product will
easily enter the room.
Install the product and intake grilles where the affect of the operating sound is small.
To prevent people from touching the parts inside the unit, be sure to install grilles on
the inlet and outlet ports. The grilles must be designed in such a way that cannot be
removed without tools.
Recommended range of static pressure is 30 Pa to 120 Pa.
If an intake duct is installed, take care not to damage the temperature sensor (the
temperature sensor is attached to the intake port ange).
Be sure to install the air inlet grille and the air outlet grille for air circulation. The
correct temperature cannot be detected.
Unit
(Room)
Air Outlet Grille Air Inlet Grille
When connecting the duct, perform duct-insulation appropriate for the installing
environment.
Inappropriate insulation work may cause condensation on the surface of the insulating
material, and may lead to condensation dripping.
Be sure to install the air lter in the air inlet. If the air lter is not installed, the heat
exchanger may be clogged and its performance may decrease.
4.6.Freshairintake
(Processingbeforeuse)
(1) When taking in fresh air, cut out the slit of the cabinet on the left side of the outer case
with nippers.
Cut
Cut
Square hole
Cabinet (iron plate)
CAUTION
When removing the cabinet (iron plate), be careful not to damage the indoor unit
internal parts and surrounding area (outer case).
When processing the cabinet (iron plate), be careful not to injure yourself with burrs,
etc.
(2) Install the round ange to the fresh air intake.
Round ange (Locally procured)
(3) Connect the duct to the round ange.
(4) Seal with a band and vinyl tape, etc. so that air does not leak from the connection.
Duct
9381386024-02_IM_EN.indd 5 5/16/2019 3:11:32 PM
En-6
5. PIPEINSTALLATION
WARNING
During installation, make sure that the refrigerant pipe is attached rmly before you
run the compressor.
Do not operate the compressor under the condition of refrigerant piping not attached
properly with 2-way or 3-way valve open. This may cause abnormal pressure in the
refrigeration cycle that leads to breakage and even injury.
During the pump-down operation, make sure that the compressor is turned off before
you remove the refrigerant piping.
Do not remove the connection pipe while the compressor is in operation with 2-way or
3-way valve open. This may cause abnormal pressure in the refrigeration cycle that
leads to breakage and even injury.
When installing and relocating the air conditioner, do not mix gases other than the
specied refrigerant (R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to
an abnormally high value and cause breakage, injury, etc.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a ame, it produces a toxic gas.
CAUTION
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant R410A models. Also, when storing the piping, securely seal the openings
by pinching, taping, etc.
While welding the pipes, be sure to blow dry nitrogen gas through them.
5.1.Pipeconnection
5.1.1. Flaring
• Use special pipe cutter and are tool exclusive for R410A.
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert the are nut (always use the are nut attached to the indoor and outdoor units
respectively) onto the pipe and perform the are processing with a are tool. Use the
special R410A are tool, or the conventional are tool. Leakage of refrigerant may
result if other are nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
Check if [L] is ared uniformly
and is not cracked or scratched.
Pipe
Die
B
A
L
Pipeoutside
diameter
[mm(in.)]
DimensionA[mm]
DimensionB
-
0
0.4
[mm]
FlaretoolforR410A,
clutchtype
6.35 (1/4)
0 to 0.5
9.1
9.52 (3/8) 13.2
12.70 (1/2) 16.6
15.88 (5/8) 19.7
19.05 (3/4) 24.0
When using conventional are tools to are R410A pipes, the dimension A should be
approximately 0.5 mm more than indicated in the table (for aring with R410A are tools) to
achieve the specied aring. Use a thickness gauge to measure the dimension A.
Width across
ats
Pipeoutside
diameter[mm(in.)]
Widthacrossats
ofFlarenut[mm]
6.35 (1/4) 17
9.52 (3/8) 22
12.70 (1/2) 26
15.88 (5/8) 29
19.05 (3/4) 36
5.1.2. Bendingpipes
• If pipes are shaped by hand, be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it difcult
to bend or stretch them any more.
• Do not bend or stretch the pipes more than 3 times.
CAUTION
To prevent breaking of the pipe, avoid sharp bends. Bend the pipe with a radius of
curvature of 150 mm or over.
If the pipe is bent repeatedly at the same place, it will break.
5.1.3. Connectingpipes
CAUTION
Be sure to apply the pipe against the port on the indoor unit correctly. If the centering
is improper, the are nut cannot be tightened smoothly. If the are nut is forced to turn,
the threads will be damaged.
Do not remove the are nut from the indoor unit pipe until immediately before connect-
ing the connection pipe.
Do not use mineral oil on ared part. Prevent mineral oil from getting into the system
as this would reduce the lifetime of the units.
(1) Detach the caps and plugs from the pipes.
(2) Centering the pipe against port on the indoor unit, turn the are nut with your hand.
(3) When the are nut is tightened properly by your hand, use a torque wrench to nally
tighten it.
Holding
spanner
Torque
wrench
Indoor unit pipe
(Body side)
Flare nut
Connection pipe
CAUTION
Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order to
tighten the are nut correctly.
Tighten the are nuts with a torque wrench using the specied tightening method. Oth-
erwise, the are nuts could break after a prolonged period, causing refrigerant to leak
and generate a hazardous gas if the refrigerant comes into contact with a ame.
Flarenut[mm(in.)] Tighteningtorque[N·m(kgf·cm)]
6.35 (1/4) dia. 16 to 18 (160 to 180)
9.52 (3/8) dia. 32 to 42 (320 to 420)
12.70 (1/2) dia. 49 to 61 (490 to 610)
15.88 (5/8) dia. 63 to 75 (630 to 750)
19.05 (3/4) dia. 90 to 110 (900 to 1,100)
5.2.Installingheatinsulation
Install the heat insulation material after performing a refrigerant leak check (see the
Installation Manual for the outdoor unit for details).
5.2.1. COUPLERHEATINSULATION
No gaps
Indoor unit side
Cable ties (large)
(Accessory)
Pipes
(Gas and liquid pipes)
Coupler heat insulation
(Accessory)
Be sure to overlap
the insulation.
CAUTION
There should be no gaps between the insulation and the product.
CAUTION
After connecting the piping, check the all joints for gas leakage with gas leak detector.
When inspecting gas leakage, always use the vacuum pump for pressure. Do not use
nitrogen gas.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to
do so may cause water leaks.
9381386024-02_IM_EN.indd 6 5/16/2019 3:11:33 PM
En-7
6. ELECTRICALWIRING
WARNING
Electrical work must be performed in accordance with this Manual by a person certi-
ed under the national or regional regulations. Be sure to use a dedicated circuit for
the unit.
An insufcient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or re.
Before starting work, check that power is not being supplied to the indoor unit and
outdoor unit.
Use the included connection cables and power cables or ones specied by the manu-
facturer. Improper connections, insufcient insulation, or exceeding the allowable
current can cause electric shock or re.
For wiring, use the prescribed type of cables, connect them securely, making sure that
there are no external forces of the cables applied to the terminal connections. Improp-
erly connected or secured cables can cause serious accidents such as overheating
the terminals, electric shock, or re.
Do not modify the power cables, use extension cables, or use any branches in the wir-
ing. Improper connections, insufcient insulation, or exceeding the allowable current
can cause electric shock or re.
Match the terminal board numbers and connection cable colors with those of the
outdoor unit. Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends of
the wiring, can cause a malfunction, electric shock, or re.
Always fasten the outside covering of the connection cable with the cable clamp. (If
the insulator is chafed, electric leakage may occur.)
Securely install the electrical box cover on the unit. An improperly installed electrical
box cover can cause serious accidents such as electric shock or re through exposure
to dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
Install a ground leakage breaker. In addition, install the ground leakage breaker so
that the entire AC main power supply is cut off at the same time. Otherwise, electric
shock or re could result.
Install a ground leakage breaker.
If a ground leakage breaker is not installed, it may cause electric shock or re.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Connect the connection cable rmly to the terminal board. Imperfect installation may
cause a re.
CAUTION
Ground the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
Do not connect power supply cables to the transmission or remote controller termi-
nals, as this will damage the product.
Never bundle the power supply cable and transmission cable together. Bundling these
cables together will cause miss operation.
When handling PCB, static electricity charged in the body may cause malfunction of
the PCB. Follow the cautions below:
• Establish a ground for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor and outdoor units for more than 10 seconds to
discharge static electricity charged in the body.
• Do not touch terminals of parts and patterns implemented on PCB.
6.1.Wiringmethod
6.1.1. Connectiondiagrams
Connectioncabletooutdoorunit
Earth (ground) line
Power line
Control line
Wiredremotecontrollercable
Red
White
Black
Indoor
unit side
6.1.2. Connectioncablepreparation
Keep the earth (ground) wire longer than the other wires.
Power supply cable
or connection cable
Earth (ground)
wire
30 mm
70 mm or more
Use a 4-core wire cable.
Howtoconnectwiringtotheterminals.
(1) Use ring terminals with insulating sleeves as shown in the gure below to connect to
the terminal block.
(2) Securely crimp the ring terminals to the wires using an appropriate tool so that the
wires do not come loose.
Strip 10 mm
Ring terminal
Sleeve
(3) Use the specied wires, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table below for the terminal screw tightening torques.
WARNING
Use ring terminals and tighten the terminal screws to the specied torques, otherwise,
abnormal overheating may be produced and possibly cause serious damage inside
the unit.
Tighteningtorque[N·m(kgf·cm)]
M4 screw 1.2 to 1.8 (12 to 18)
M5 screw 2.0 to 3.0 (20 to 30)
Screw with
special washer
Ring terminal
Terminal blocks
Wire
Wire
Screw with
special
washer
Ring terminal
9381386024-02_IM_EN.indd 7 5/16/2019 3:11:33 PM
En-8
6.1.3. Connectionwiring
CAUTION
Use care not to mistake the power supply cable and connection wires when installing.
Install so that the wires for the remote controller will not come in contact with other
connection wires.
(1) Remove the control box cover and install each connection wire.
Control box cover
Loosen the screws.(3 locations)
Control line
Connection cable
Power line
Outdoor unit
Earth (ground)
Black
White
Red
Remote
controller
*Ground the remote controller if it has a earth (ground) wire.
(2) After wiring is complete, secure the remote controller cable, connection cable, and
power supply cable with the cable clamps.
Connection cable
(to outdoor unit)
Remote controller
cable
Cable tie (medium)
(Accessory)
Control box
(3) Seal the cable outlet or other gaps with putty to prevent dew condensation or insect
from entering the electric control box.
(4) Install the control box cover.
CAUTION
Do not bundle the remote controller cable, or wire the remote controller cable in paral-
lel, with the indoor unit connection wire (to the outdoor unit) and the power supply
cable. It may cause erroneous operation.
7. REMOTECONTROLLERSETTING
CAUTION
When detecting the room temperature using the remote
controller, please set up the remote controller according to
the following conditions.
If the remote controller is not well set, the correct room
temperature will not be detected, and thus the abnormal
conditions like “not cooled” or “not heated” will occur even if
the air-conditioner is running normally.
Temperature sensor
• A location with an average temperature for the room being air-conditioned.
• Not directly exposed to the outlet air from the air-conditioner.
• Out of direct sunlight.
• Away from the inuence of other heat sources.
When installing the remote controller and cable near a source of electromagnetic
waves, separate the remote controller from the source of the electromagnetic waves
and use shielded cable.
Do not touch the remote controller PC board and PC board parts directly with your
hands.
Hole
Hole 2
Hole 3
Unit : mm
33.5
4.5
4.5
4.5
12.5
45.3
63.5
83.5
15.3
30
23
8
6
17120
120
7.1.Installingtheremotecontroller
(1) Open the operation panel on the front of the remote controller, remove the two
screws indicated in the following gure, and then remove the front case of the remote
controller.
Connector
Front case
(back side)
Rear case
Screws
When installing the remote controller, remove the connector from the front case.
The wires may break if the connector is not removed and the front case hangs down.
When installing the front case, connect the connector to the front case.
(2) Install the rear case to the wall, etc. with the two tapping screws. Refer to the following
information to install the remote controller wires.
(Example)
Rear case
Connector
Front case
Remote controller
wires
Install the remote controller wires so as not to be direct touched with your hand.
Routingtheremotecontrollerwires
(1) Install the remote controller wires to the terminals on the top of the rear case as
shown in the following gure.
(2) Fasten the wires with the cable tie.
Cable tie
(small)
(Accessory)
1. Red
2. White
3. Black
CAUTION
When connecting the remote
controller wires, do not overtighten
the screws.
9381386024-02_IM_EN.indd 8 5/16/2019 3:11:34 PM
En-9
7.2.SettingtheDIPswitches
Whenusingabattery(memorybackup)
DIP Switch
OFF ON
ON
Front case (back side)
Change the DIP switch setting to use batteries. (The DIP switch is not set to use batteries
at the factory.)
Change DIP switch No. 6 from OFF to ON.
If batteries are not used, all of the settings stored in memory will be deleted if there is a
power failure.
CAUTION
Conrm whether the wiring work for outdoor unit has been nished.
Conrm whether the cover for electric control box on the outdoor unit is close.
8. FUNCTIONSETTING
8.1. Turningonthepower
(1) Check the remote controller wiring and DIP switch settings.
(2) Install the front case. When installing the front case, connect the connector to the front
case.
(3) Check the indoor and outdoor unit wiring and circuit board switch settings, and then
turn on the indoor and outdoor units. After “9C” has ashed on the set temperature
display for several seconds, the clock display will appear in the centre of the remote
controller display.
The clock display will appear in the centre of the remote controller display.
SU
MO
TU
WE
TH FR
SA
8.2. Settingmethod
• This procedure is for changing the function settings used to control the indoor unit
according to the installation conditions.
• Incorrect settings can cause the indoor unit malfunction.
• After the power is turned on, perform the “FUNCTION SETTING” according to the
installation conditions using the remote controller.
• The settings may be selected between the following two:
• Function Number and Setting Value.
• Settings will not be changed if invalid numbers or setting values are selected.
(1) Press the SET TEMP. buttons (
) ( ) and FAN button simultaneously for more than
5 seconds to enter the function setting mode.
SU
MO
TU
WE
TH FR
SA
Press the SET BACK button to select the indoor R.C. address.
SET BACK
SU
MO
TU
WE
TH FR
SA
R.C. address of INDOOR UNIT
(2) Press the Set time buttons (
) ( ) to select the function number.
SU
MO
TU
WE
TH FR
SA
Function number
(3) Press the SET TEMP. buttons (
) ( ) to select the setting value.
The display ashes as shown to the right during setting value selection.
(4) Press the TIMER SET button to conrm the setting. Press the TIMER SET button for a
few seconds until the setting value stops ashing.
If the setting value display changes or if “- -” is displayed when the ashing stops,
the setting value has not been set correctly. (An invalid setting value may have been
selected for the indoor unit.)
SU
MO
TU
WE
TH FR
SA
Setting value
(5) Repeat steps 2 to 4 to perform additional settings. Press the SET TEMP. (
) ( )
buttons and FAN button simultaneously again for more than 5 seconds to cancel the
function setting mode. In addition, the function setting mode will be automatically
cancelled after 1 minute if no operation is performed.
(6) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
CAUTION
After turning off the power, wait 30 seconds or more before turning on it again. The
FUNCTION SETTING doesn’t become effective if it doesn’t do so.
8.3.Settingtheroomtemperaturedetectionlocation
The detection location of the room temperature can be selected from the following two
examples. Choose the detection location that is best for the installation location.
A.Indoorunitsetting(factorysetting)
The room temperature is detected by the indoor unit temperature sensor.
(1) When the THERMO SENSOR button is pressed, the lock display ashes because the
function is locked at the factory.
A
Indoor unit
B.Remotecontrollersetting
The room temperature is detected by the remote controller temperature sensor.
(1) Enable the room temperature sensor selection by changing the room temperature
sensor switching in “8.4. Function details” to “Both”.
(2) Press the THERMO SENSOR button for 5 seconds or more to select the temperature
sensor of the indoor unit or the remote controller.
B
Indoor unit
CAUTION
When selecting the “Remote controller setting”, if the detected
temperature value between the temperature sensor of the indoor unit
and the temperature sensor of the remote controller varies
signicantly, it is likely to return to the control status of temperature
sensor of the indoor unit temporarily.
As the temperature sensor of remote controller detects the temperature near the wall,
when there is a certain difference between the room temperature and the wall tempera-
ture, the sensor will not detect the room temperature correctly sometimes.
Especially when the outer side of the wall on which the sensor is positioned is exposed to
the open air, it is recommended to use the temperature sensor of the indoor unit to detect
the room temperature when the indoor and outdoor temperature difference is signicant.
The temperature sensor of the remote controller is not only used when there is a problem
in the detection of the temperature sensor of the indoor unit.
NOTE:
If the function to change the temperature sensor is used as shown in examples A (other than
example B), be sure to lock the detection location. If the function is locked, the lock display
will ash when the THERMO SENSOR button is pressed.
9381386024-02_IM_EN.indd 9 5/16/2019 3:11:35 PM
En-10
8.4.FunctionDetails
Filtersign
Select appropriate intervals for displaying the lter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
(♦... Factory setting)
Function
Number
Setting
Value
SettingDescription
11
00 Standard (2500 hours)
01 Long interval (4400 hours)
02 Short interval (1250 hours)
03 No indication
Staticpressure
Select the appropriate static pressure according to the installation conditions.
(♦... Factory setting)
Function
Number
Setting
Value
SettingDescription
21
00 Normal (60 Pa)
01 Low static pressure (30 Pa)
02 High static pressure 1 (90 Pa)
03 High static pressure 2 (120 Pa)
Roomtemperaturecontrolforcooling
Depending on the installed environment, correction of the room temperature sensor may
be required.
Select the appropriate control setting according to the installed environment.
(♦... Factory setting)
Function
Number
Setting
Value
SettingDescription
30
00 Standard
01 Lower control
02 Slightly higher control
03 Higher control
Roomtemperaturecontrolforheating
Depending on the installed environment, correction of the room temperature sensor may
be required.
Select the appropriate control setting according to the installed environment.
(♦... Factory setting)
Function
Number
Setting
Value
SettingDescription
31
00 Standard
01 Lower control
02 Slightly lower control
03 Higher control
Autorestart
Enable or disable automatic restart after a power interruption.
(♦... Factory setting)
Function
Number
Setting
Value
SettingDescription
40
00 Enable
01 Disable
* Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or
external device.
Roomtemperaturesensorswitching
* This setting is to disable the cold air prevention function during heating operation. When
disabled, the fan setting will always follow the setting on the remote controller. (Excluding
defrost mode)
(♦... Factory setting)
Function
Number
Setting
Value
SettingDescription
42
00 Indoor unit
01 Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
*
Remote controller sensor must be turned on by using the remote controller
Coldairprevention
(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
(♦... Factory setting)
Function
Number
Setting
Value
SettingDescription
43
00 Enable
01 Disable
Externalinputcontrol
"Operation/Stop" mode or "Forced stop" mode can be selected.
(♦... Factory setting)
Function
Number
Setting
Value
SettingDescription
46
00 Operation/Stop mode
01 (Setting prohibited)
02 Forced stop mode
Roomtemperaturesensorswitching(Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
"Wired remote controller" (01). This function will only work if the function setting 42 is set
at "Both" (01)
(♦... Factory setting)
Function
Number
Setting
Value
SettingDescription
48
00 Both
01 Wired remote controller
Settingrecord
Record any changes to the settings in the following table.
Setting SettingValue
Filter sign
Static pressure
Room temperature control for cooling
Room temperature control for heating
Auto restart
Room temperature sensor switching
Cold air prevention
External input control
Room temperature sensor switching (Aux.)
After completing the Function Setting, be sure to turn off the power and turn it on again.
9381386024-02_IM_EN.indd 10 5/16/2019 3:11:35 PM
En-11
8.5.Jumperwiresetting
Change the following settings by using the jumpers.
This setting is made by cutting the jumper wires on the circuit board of the indoor unit.
JM3
JM2
JM1
Jumper wires
Jumperwire
JMstate
Details
Connect Disconnect
JM1
-
Cannot be used
(Do not change)
JM2
JM3 Disable Enable Fan delay setting
9. SPECIALINSTALLATIONMETHODS
CAUTION
Be sure to turn off the electrical breaker before making settings.
When setting the rotary switch and DIP switches, do not touch any other parts on the
circuit board directly with your bare hands.
9.1.Groupcontrolsystem
CAUTION
Group control is only possible between units with remote controllers of the same type.
To conrm the type of remote controller, see the back of the remote controller or
“2.3. Accessories”.
A number of indoor units can be operated at the same time using a single remote controller
.
(1) Wiring method (indoor unit to remote controller)
Indoor
unit
1
Bus wire
Remote
controller cable
Remote controller
When ground wire is necessary
Indoor
unit 2
Indoor
unit
3
Indoor
unit 4
(2) DIP switch setting (Indoor unit)
Set the unit number of each indoor unit using the DIP switches on the indoor unit
circuit board. (See the following table and gure.)
The DIP switches are normally set to make the unit number 00.
Indoorunit Unitnumber DIPSWITCHNo.
1 2 3 4
1
00 OFF OFF OFF OFF
2
01 ON OFF OFF OFF
3
02 OFF ON OFF OFF
4
03 ON ON OFF OFF
5
04 OFF OFF ON OFF
6
05 ON OFF ON OFF
7
06 OFF ON ON OFF
8
07 ON ON ON OFF
9
08 OFF OFF OFF ON
0
09 ON OFF OFF ON
A
10 OFF ON OFF ON
B
11 ON ON OFF ON
C
12 OFF OFF ON ON
D
13 ON OFF ON ON
E
14 OFF ON ON ON
F
15 ON ON ON ON
ON
Example :
Unit number 02
DIP switches
Circuit board in the control box of indoor unit.
NOTE:
Be sure to set the unit numbers sequentially.
When different indoor unit models are connected using the group control system, some
functions may no longer be available.
• It should not be connected to any other Gr that is not of the same series.
9.2.Fandelaysetting
This setting can be used when the auxiliary heater is mounted.
When the operation is stopped when the indoor unit is operating with an auxiliary heater,
the operation continues 1 minutes.
Refer to “8.5. Jumper wire setting” to change the settings.
9381386024-02_IM_EN.indd 11 5/16/2019 3:11:36 PM
En-12
10.OPTIONALPARTS
WARNING
Regulation of cable differs from each locality, refer in accordance with local rules.
This air conditioner can be connected with the following optional kits.
Optiontype ConnectorNo.
UTY-XSZX (Remote sensor unit) CN8
UTD-ECS5A (External input) CN102
UTD-ECS5A (External output) CN103
CN8
CN103
CN102
Remotesensor
• Remove the existing connector and replace it with the remote sensor connector (ensure
that the correct connector is used).
• The original connector should be insulated to ensure that it does not come into contact
with other electrical circuitry.
Setting for room temperature correction
When a remote sensor is connected, set the function setting of indoor unit as indicated
below.
• Set Function Number “30” (Room temperature control for cooling) to “01”
• Set Function Number “31” (Room temperature control for heating) to “01”
11.CHECKLIST
Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
Checkitems Checkbox
Has the indoor unit been installed correctly?
Has there been a check for gas leaks (refrigerant pipes)?
Has heat insulation work been completed?
Does water drain easily from the indoor units?
Is the voltage of the power source the same as that indicated on the
label on the indoor unit?
Are the wires and pipes all connected completely?
Is the indoor unit grounded?
Is the connection cable the specied thickness?
Are the inlets and outlets free of any obstacles?
After installation is completed, has the proper operation and handling
been explained to the user?
Operate the unit according to the operating manual provided, and
check that it is operating normally.
12.TESTRUN
CAUTION
Supply power to the crankcase heater for at least 12 hours before the start of
operation in winter.
(1) Stop the air conditioner operation.
(2) Press the MODE button and the FAN button simultaneously for 2 seconds or more to
start the test run.
Test run display
(3) Press the START/STOP button to stop the test run.
13.CUSTOMERGUIDANCE
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, air
ow switching, and other remote controller operations.
(2) Cleaning and maintenance of the product, and other items such as air lters and air
louvers if applicable.
(3) Give the operating and installation manuals to the customer.
9381386024-02_IM_EN.indd 12 5/16/2019 3:11:36 PM
En-13
14.ERRORCODES
[SELF-DIAGNOSIS]
If an error occurs, the following display will be shown. (“Er” will appear in the set room
temperature display.)
Unit number
of indoor unit
Error code
EX. Self-diagnosis
If you use a wired type remote controller, error codes will appear on the remote controller
display. If you use a wireless remote controller, the lamps on the IR receiver unit will output
error codes by way of blinking patterns. See the lamp blinking patterns and error codes in
the table below. An error display is displayed only during operation.
Errordisplay
Wired
remote
controller
Errorcode
Description
OPERATION
lamp(green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
(1)
(1)
Serial communication error
(1)
(2)
Wired remote controller
communication error
(1)
(5)
Check run unnished
(1)
(6)
Peripheral unit transmission PCB
connection error
(2)
(1)
Unit number or Refrigerant circuit
address setting error
[Simultaneous Multi]
(2)
(2)
Indoor unit capacity error
(2)
(3)
Combination error
(2)
(4)
• Connection unit number
error (indoor secondary unit)
[Simultaneous Multi]
• Connection unit number error
(indoor unit or branch unit)
[Flexible Multi]
(2)
(7)
Primary unit, secondary unit setup
error [Simultaneous Multi]
(3)
(1)
Power supply interruption error
(3)
(2)
Indoor unit PCB model
information error
(3)
(5)
Manual auto switch error
(4)
(1)
Room temp. sensor error
(4)
(2)
Indoor unit Heat Ex. Middle temp.
sensor error
(5)
(1)
Indoor unit fan motor error
(5)
(3)
Drain pump error
(5)
(7)
Damper error
(5)
(15)
Indoor unit error
(6)
(1)
Outdoor unit reverse/missing
phase and wiring error
(6)
(2)
Outdoor unit main PCB
model information error or
communication error
(6)
(3)
Inverter error
(6)
(4)
Active lter error, PFC circuit error
(6)
(5)
Trip terminal L error
(6)
(10)
Display PCB microcomputers
communication error
(7)
(1)
Discharge temp. sensor error
Errordisplay
Wired
remote
controller
Errorcode
Description
OPERATION
lamp(green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
(7)
(2)
Compressor temp. sensor error
(7)
(3)
Outdoor unit Heat Ex. liquid temp.
sensor error
(7)
(4)
Outdoor temp. sensor error
(7)
(5)
Suction Gas temp. sensor error
(7)
(6)
• 2-way valve temp. sensor error
• 3-way valve temp. sensor error
(7)
(7)
Heat sink temp. sensor error
(8)
(2)
• Sub-cool Heat Ex. gas inlet
temp. sensor error
• Sub-cool Heat Ex. gas outlet
temp. sensor error
(8)
(3)
Liquid pipe temp. sensor error
(8)
(4)
Current sensor error
(8)
(6)
• Discharge pressure sensor error
• Suction pressure sensor error
• High pressure switch error
(9)
(4)
Trip detection
(9)
(5)
Compressor rotor position
detection error (permanent stop)
(9)
(7)
Outdoor unit fan motor 1 error
(9)
(8)
Outdoor unit fan motor 2 error
(9)
(9)
4-way valve error
(9)
(10)
Coil (expansion valve) error
(10)
(1)
Discharge temp. error
(10)
(3)
Compressor temp. error
(10)
(4)
High pressure error
(10)
(5)
Low pressure error
(13)
(2)
Branch boxes error
[Flexible Multi]
Display mode
: 0.5s ON / 0.5s OFF
: 0.1s ON / 0.1s OFF
( ) : Number of ashing
9381386024-02_IM_EN.indd 13 5/16/2019 3:11:42 PM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Fujitsu ARGA36FMTA-Q Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI