34-975XL2

Zurn-Wilkins 34-975XL2, 2-975XL2S, 2-975XL2SEU Specification

  • Hello! I am an AI chatbot trained to assist you with the Zurn-Wilkins 34-975XL2 Specification. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
  • What is the maximum pressure capacity of the Zurn-Wilkins 34-975XL2?
    What temperature range can the Zurn-Wilkins 34-975XL2 operate in?
    What materials are used in the construction of the Zurn-Wilkins 34-975XL2?
    How many ball valves are included with the Zurn-Wilkins 34-975XL2?
    What sizes are available for the Zurn-Wilkins 34-975XL2?
    What is the operating principle of the Zurn-Wilkins 34-975XL2?
    Can the Zurn-Wilkins 34-975XL2 be used for reclaimed water systems?
    Does the Zurn-Wilkins 34-975XL2 come with union ball valves?
    Is the Zurn-Wilkins 34-975XL2 pre-assembled?
    Can the Zurn-Wilkins 34-975XL2 be installed underground?
e 975XL is the simplest and
best backow preventer available to
the irrigation market. Fewer parts
means simple, reliable performance, and
lower cost, just ask any tester. Irrigation
systems present unique requirements, and
the Wilkins 975XL responds with ease of
access to the rst check, which is the usual
location for debris to lodge and foul. You
can get in, clean out and reassemble in
record time, saving you time and money.
To help you save even more time
and money, Wilkins pre-assembled
backow assembly includes all of
the components you need
to manage your sys-
tem, including
backow,
pressure regulation
and strainers.
Reduced Pressure Principal Assembly
Customer Service Representatives available Monday through Friday 5:30 am to 5:00 pm PST.
Call: 877-222-5356 or 805-226-6297, [email protected] or visit us online at www.zurn.com
WK-AD975XL 0408
FEATURES 975XL
Sizes 3/4”, 1”, 1 1/4”, 1 1/2”, 2”
Reduced pressure principle backflow
preventer consisting of a pressure
differential relief valve located between two
independently operated spring-loaded center
guided check valves, “Y” pattern body
Complete with two full port resilient seated
ball valves for shut-off and four resilient
seated ball valve test cocks
Nickel-plated ball valve handles offer
superior corrosion resistance
Bronze body construction
Noryl
®
replaceable seats and silicone
rubber check discs
Entire unit serviceable in line
Temperature range 33°F-180°F
Maximum pressure 175 psi
Available with BSP (optional)
Available with stainless steel ball valve
handles (optional)
Pre-plumbed backflow station. Assembly
can be of the reduced pressure principle or
of the double check type
3/4" & 1" includes a Model 975XLV or
950XLV backflow preventer and either a
“Y” strainer, in-line check valve or pressure
reducing valve in any combination
1 1/4" - 2" includes a Model 975XLSE or
950XLSE backflow preventer with union
ball valves and either a “Y” strainer, in-line
check valve or pressure reducing valve in
any combination
Nickel-plated ball valve handles offer
superior corrosion resistance
Available with stainless steel handles
(optional)
Available with integral 45° flare SAE test
fittings and dust covers (optional)
Backflow preventer is approved by ASSE
®
Listed 1013 (975XLV and 975XLSE),
ASSE
®
Listed 1015 (950XLV), IAPMO
®
listed
Approved by the Foundation for Cross-
Connection Control and Hydraulic
Research at the University of Southern
California (Model 975XLV and 975XLSE)
Model BR4 regulator is ASSE
®
Listed 1003,
IAPMO
®
Listed, CSA
®
Certified, City of Los
Angeles Approved
FEATURES PRE-SET
(Suffixes can be combined)
- with full port QT ball valves (standard)
L - less ball valves
U - with union ball valves
MS - with integral relief valve monitor switch
P - for reclaimed water systems
S - with bronze “Y” type strainer
BMS - with battery operated monitor switch
FDC - with fire hydrant connection; 2” only
TCU - with test cocks up
V - with union swivel elbows
SE - with street elbows
RV - with test cocks supplied on the opposite side
FT - withintegralmale45°areSAEtesttting
OPTIONS 975xl
Finally, a complete, pre-assembled backow assembly
that includes all of the components you need to manage
your system, including backow, pressure regulation
and strainers. Save material costs and installation time
by installing the Pre-Set.
975XL Reduced Pressure Principal Assembly
/