American Power Conversion Bypass Static User manual

Category
Network switches
Type
User manual
Symmetra MW UPS
w/ Internal
Bypass Static Switch
User
Guide
Contents
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001 i
Safety ......................................................................1
IMPORTANT SAFETY INSTRUCTIONS
- SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Symbols used in this guide . . . . . . . . . . . . . . . . . . . . . . . . . 1
User Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
UPS Display..............................................................3
Display Symbols and Buttons. . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Navigation symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Screen symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
UPS Summary Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Input Summary Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Output Summary Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Bypass Summary Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Battery Summary Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operation Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
UPS Start-Up Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
UPS Shutdown screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Online to Static Bypass Screen. . . . . . . . . . . . . . . . . . . . . . . . . 13
Static Bypass to Online Screen. . . . . . . . . . . . . . . . . . . . . . . . . 14
Network Configuration Screens . . . . . . . . . . . . . . . . . . . . . . . . 15
Network Settings screen . . . . . . . . . . . . . . . . . . . . . . . . . . 15
E-mail Settings screen . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SNMP Settings screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Remote Monitoring Service Settings screen . . . . . . . . . . . . . 18
APC ISX Manager Settings screen . . . . . . . . . . . . . . . . . . . . 19
ii Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
User Configuration Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Touch-Screen Settings screen . . . . . . . . . . . . . . . . . . . . . . 20
Password Settings screen . . . . . . . . . . . . . . . . . . . . . . . . . 21
Modbus Settings screen . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Regional Settings screen . . . . . . . . . . . . . . . . . . . . . . . . . 22
Battery Test screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Event Log Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Predictive Maintenance Screens . . . . . . . . . . . . . . . . . . . . . . . . 25
Inverter DC Capacitors screen . . . . . . . . . . . . . . . . . . . . . . 25
Inverter AC Capacitors screen . . . . . . . . . . . . . . . . . . . . . . 26
Top Fans screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Inverter Fans screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Main Static Switch Fans screen . . . . . . . . . . . . . . . . . . . . . 29
Operation Modes................................................... 31
On-line Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Battery Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Bypass Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Manual Bypass Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
System Start-Up from Manual Bypass Operation . . . . . . . . . . . . 35
System Start-Up from Manual Bypass to Online Operation of
single mains/utility system - Step-by-Step . . . . . . . . . . . . . . 36
System Start-Up from Manual Bypass to Online Operation of
dual mains/utility system - Step-by-Step . . . . . . . . . . . . . . . . 36
System Shutdown from Online to Manual Bypass Operation . . 37
System Shutdown from Online to Manual Bypass Operation of
single mains/utility systems - Step-by-Step . . . . . . . . . . . . . . 38
System Shutdown from Online to Manual Bypass Operation of
dual mains/utility systems - Step-by-Step . . . . . . . . . . . . . . . 38
Transfer from Online to Static Bypass Operation . . . . . . . . . . . 39
Transfer from Static Bypass to Online Operation . . . . . . . . . . . 40
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001 iii
Alarms/Troubleshooting .........................................41
Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Severe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
View active alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
APC Symmetra MW Remote Display........................43
Starting web-based remote session . . . . . . . . . . . . . . . . . . . 44
Warranty ...............................................................45
Factory Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Life Support Policy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Appendix A............................................................47
Air Filter Exchange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001 1
Safety
IMPORTANT SAFETY INSTRUCTIONS
- SAVE THESE INSTRUCTIONS
This guide contains important instructions that should be followed when handling the UPS, Battery
Enclosures, and Batteries.
Symbols used in this guide
WARNING!
Indicates an electrical hazard, which, if not avoided, could result in injury or death.
CAUTION!
Indicates a hazard, which, if not avoided, could result in injury or death.
Note
Indicates important information.
Indicates that more information is available on this subject in a different section of this
manual.
See also
Indicates that more information is available on the same subject in a different manual.
Safety: IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS
2 Symmetr MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
User Safety
WARNING!
User functions: For safety reasons the user may only
- Remove the finishing panels for air filter exchange
- Operate the UPS display.
WARNING!
The UPS can be powered from more than one source.
CAUTION!
The system is equipped with an optional auto-start function, enabling the system to start
without any warning when power is applied.
Note
Typically, the UPS installation will be connected to an EPO (Emergency Power Off)
button located on a wall near the entrance to the room. If activated, the EPO switches off
power to the UPS, disconnects the UPS output, and switches off power to the entire
room. This action will disconnect support to the load if the UPS is online.
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001 3
UPS Display
Display Symbols and Buttons
Navigation symbols
Screen symbols
Home: Press to go to the UPS Summary screen.
Back: Press to go to previous screen.
Help: Press to access further details on current screen.
Page Up: Press to go to previous screen on same subject (only visible when there are
more screens on the same subject).
Page Down: Press to go to next screen on same subject (only visible when there are
more screens on the same subject).
Password logout: Press to log out from password protected screens.
Delta Inverter
Main Inverter
~
~
UPS Display: Display Symbols and Buttons
4 Symmetr MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
Buttons
Press this button to switch ON the module.
Press this button to switch OFF the module.
EMO (Emergency Module OFF) button:
Use in emergency situations to shut down the UPS. When the EMO button is engaged on
the UPS, AC and DC input and output are disabled.
OFF
EMO
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001 5
UPS Summary Screen
The LCD touch-screen UPS display is the user interface. It is used to configure the UPS, monitor the
system, and change the settings. The display also provides the user with audible and visual alarms.
The UPS display is organized hierarchically and the UPS Summary screen is the apex of the
hierarchy. To navigate to the UPS Summary screen, touch the house icon in the upper right corner of
the screen. The UPS Summary screen gives access to additional screens as shown below.
Normal Normal
NormalNormal
Normal
~~
Normal
UPS Summary
Normal
Operation/Configuration
Bypass
Summary
Operation/
Configuration
Battery
Summary
Input
Summary
Output
Summary
Note
The screens on the following pages are examples only. All values are not shown.
6 Symmetr MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
Input Summary Screens
The three Input Summary screens provide input-specific status of voltage, power, current, frequency,
etc.
Normal
~~
Q7 Q8
Normal
0:00 AM
Q2
UPS Summary
Output
Current
Current high
THD
THD high
THD low
Crest factor
Crest factor high
Active power
Active power high
Apparent power
Apparent power high
Power factor
Total active power
Total apparent power
Frequency
Frequency high
Frequency low
Tolerance
Mains SSW
Mains SSW high
Page 2 of 3
Voltage
Voltage high
Voltage low
THD
THD high
Voltage tolerance
Waveform tolerance
Tolerance conditions
Temperature
22.6
90.2
4.0
1.0
2.24
2.17
410
700
320
700
1.0
410
700
320
700
1.0
402
701
312
702
1.0
700
518
47.9
54.1
45.9
2.0
242.5
260.2
199.8
3.1
3.0
0.0
247.7
265.1
206.3
4.0
3.9
0.0
252.7
270.1
211.5
5.0
4.9
0.0
10
10
17.4
77.8
4.9
1.0
2.27
2.2
12.4
72.4
6.1
5.9
1.0
2.37
2.3
Normal
0:00 AM
Normal
Normal
Input Summary
5.40 PM
A
A
%
%
%
V
V
V
%
%
%
%
%
kW
kW
kVA
kVA
kW
kVA
Hz
Hz
Hz
%
129
127
o
F
o
F
Normal
Normal
Input Summary
5.40 PM
Page 1 of 3
587
522
456
391
326
262
196
130
65
L1 L2 L3
0
13 13
13
Current
A
495
440
365
330
275
220
165
110
55
0
450 453
Total Power
kW kVA
607
540
472
405
337
270
202
135
67
L1-2 L2-3 L3-1
0
Voltage
V
259 264 263
55.0
54.0
53.0
52.0
51.0
50.0
49.0
48.0
47.0
45.0
46.0
Frequency
Hz
259
Voltage
200.0
-200.0
0.0
Time (ms)
Current
Voltage
200.0
-200.0
0.0
0.0 5.0 10.0
Time (ms)
15.0
Current
Normal
Normal
Input Summary
5.40 PM
Page 3 of 3
Refresh Data
The black bars represent real-time
data. Yellow triangles represent the
maximum values recorded to date
and blue triangles represent the
minimum values recorded to date.
These values will be reset when the
input statistics are reset
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001 7
Output Summary Screens
The three Output Summary screens provide output-specific status of voltage, power, current,
frequency, etc.
Normal
~~
Q7 Q8
Normal
0:00 AM
Q2
UPS Summary
Normal
Normal
Output Summary
5.40 PM
Page 1 of 3
587
522
456
391
326
262
196
130
65
L1 L2 L3
0
13 13
13
Current
A
495
440
365
330
275
220
165
110
55
0
450 453
Total Power
kW kVA
607
540
472
405
337
270
202
135
67
L1-2 L2-3 L3-1
0
Voltage
V
259 264 263
55.0
54.0
53.0
52.0
51.0
50.0
49.0
48.0
47.0
45.0
46.0
Frequency
Hz
259
L1 L2 L3
L1 L2 L3
L1-2 L2-3 L3-1
Current
Current high
Peak current
Peak current high
THD
THD high
Crest factor
Crest factor high
Active power
Active power high
Apparent power
Apparent power high
Power factor
Total active power
Total apparent power
Frequency
Frequency high
Frequency low
Tolerance
Load
Load high
Total load
Total load high
Page 2 of 3
Voltage
Voltage high
Voltage low
THD
THD high
Voltage tolerance
Waveform tolerance
Tolerance conditions
Load
57.0
60.0
20.0
59.4
3.9
3.8
2.1
2.03
380
700
700
690
0.92
381
701
692
682
0.81
382
702
694
684
0.82
200
150
51.4
54.2
45.8
2.0
220.5
260.0
200.0
2.7
221.0
261.0
201.0
3.6
222.0
262.0
202.0
4.8
4.6
5
6
29
59.0
63.0
19.5
59.9
4.8
4.7
2.13
2.06
62.0
66.0
20.0
60.4
5.8
5.7
2.23
2.16
Normal
0:00 AM
Normal
Normal
Output Summary
5.40 PM
A
A
A
A
%
%
V
V
V
%
%
%
%
kW
kW
kVA
kVA
kW
kVA
Hz
Hz
Hz
%
60.0
58.0
68.0
66.0
78.0
76.0
142.0
250.0
%
%
%
%
Voltage
200.0
-200.0
0.0
Time (ms)
Current
Voltage
200.0
-200.0
0.0
0.0 5.0 10.0
Time (ms)
15.0
Current
Normal
Normal
Output Summary
5.40 PM
Page 3 of 3
Refresh Data
The black bars represent real-time
data. Yellow triangles represent the
maximum values recorded to date
and blue triangles represent the
minimum values recorded to date.
These values will be reset when the
output statistics are reset
8 Symmetr MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
Bypass Summary Screens
The two Bypass Summary screens provide status of voltage, power, current, frequency, etc.
Normal
~~
Q7 Q8
Normal
0:00 AM
Q2
Bypass Summary
Normal
Normal
Bypass Summary
5.40 PM
Page 1 of 2
110
88
86
73
61
49
37
24
12
L1 L2 L3
0
59 61
63
Current
A
127
112
108
84
70
56
42
20
14
0
83 118
Total Power
kW kVA
336
236
207
177
140
110
90
59
30
L1-2 L2-3 L3-1
0
Voltage
V
200 203 205
80.0
57.8
55.6
53.3
51.0
40.9
46.7
44.4
42.2
40.0
Frequency
Hz
51,8
The black bars represent real-time
data. Yellow triangles represent the
maximum values recorded to date
and blue triangles represent the
minimum values recorded to date.
These values will be reset when
the bypass statistics are reset
L1 L2 L3
Output
Current
Current high
Peak Current
Peak Current high
Crest factor
Crest factor high
Power factor
Active power
Active power high
Apparent power
Apparent power high
Total active power
Total active power high
Total apparent power
Total apparent power high
Frequency
Frequency high
Frequency low
Load
Load high
Total load
Total load high
Page 2 of 2
Voltage
Voltage high
Voltage low
THD
Load
200.0
500.0
200.0
300.0
0.0
0.0
0.5
100
200
200
200
0.5
100
200
200
200
0.5
100
200
200
200
200
200
200
0
60.0
61.0
59.0
xxx.0
490.0
470.0
5.0
xxx.0
490.0
470.0
5.0
xxx.0
490.0
470.0
5.0
200.0
500.0
200.0
300.0
0.0
0.0
200.0
500.0
200.0
300.0
0.0
0.0
Normal
0:00 AM
Normal
Ready
Bypass Summary
2.07 PM
A
A
A
A
V
V
V
%
kW
kW
kW
kW
kW
kW
kW
kW
kW
Hz
Hz
Hz
Mains SSW
Mains SSW High
68
68
¡ F
¡ F
10.0
99.0
10.0
99.0
10.0
99.0
0.0
0.0
%
%
%
%
Temperature
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001 9
Battery Summary Screens
The three Battery Summary screens provide battery-specific status of voltage, current, run-time
remaining, temperature, power, etc.
Normal
~~
Q7 Q8
Normal
0:00 AM
Q2
UPS Summary
Normal
Normal
Battery Summary
5.40 PM
Page 1 of 3
200
20
-160
-340
-520
-700
-880
-1060
-1240
Batt 1 Batt 2 Batt 1 Batt 2
-1420
32
37
Current
A
495
440
385
330
275
220
165
110
55
0
Voltage
V
435 435
Runtime remaining
12 m 0 s
-1600
Output
Battery 1
Voltage
Voltage high
Voltage low
Current
Current high discharge
Battery 2
Voltage
Voltage high
Voltage low
Current
Current high discharge
Settings
Min. voltage: warning
Min. voltage: shutdown
Max voltage: warning
Max voltage: shutdown
Boost charge
Auto boost charge
Nominal charge
Boost charge
Estimated charge time
Estimated charge %
Batt 1 charge current high
Batt 2 charge current high
Battery
Max battery
Battery high
Battery low
Battery charge
Time on battery
Runtime remaining
Total time on battery
Total # of times on battery
Page 2 of 3
Statistics
Charge
Temperature
Voltage and Current
false
false
420
450
65
100
-90.0
-90.0
100
86
104
86
440.0
450.0
420.0
57.2
119.5
451.0
460.0
420.0
51.5
120.0
370
320
460
475
Normal
0:00 AM
Normal
Normal
2.08 PM
V
V
V
A
A
V
V
V
A
A
V
V
V
V
V
V
m
%
A
A
o
F
o
F
o
F
o
F
Battery power
Battery power high discharge
Battery power high charge
Power
0
0
0
kW
kW
kW
Floating
0
300 m 0
0
0
s
s
m
Battery Summary
100.0
0.0
50.0
0.0 50.0 100.0
Time (hours)
Temperature
Normal
Normal
Normal
Battery Summary
5.40 PM
Page 3 of 3
Refresh Data
The curve shows the battery
The black bars represent real-time
data. Yellow triangles represent the
maximum values recorded to date
and blue triangles represent the
minimum values recorded to date.
These values will be reset when the
battery statistics are reset
10 Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
Operation Screen
The Operation screen permits system operation and monitoring, and provides the ability to change
display settings (as illustrated in the following menus).
Push the Operation/Configuration button to open the Operation screen.
The Operation screen leads to the following screens:
UPS Start-Up screen
UPS Shutdown screen
Online to Static Bypass screen
Static Bypass to Online screen
Network Configuration screens
User Configuration screens
View Event Log screen
Predictive Maintenance screens
Normal
~~
Q7 Q8
Normal
0:00 AM
Q2
UPS Summary
Normal
5.40 PM
Startup
Shutdown
Network Configuration
User Configuration
View Event Log
Predictive Maintenance
Static Bypass Online
Online Static Bypass
Transfer from manual bypass to online
Transfer from online to manual bypass
Transfer from online to static bypass
Transfer from static bypass to online
Operation
Normal
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001 11
UPS Start-Up Screen
From the UPS Start-Up screen, the power flow can be transferred from Manual Bypass to Online
Operation.
The UPS Start-Up screen shows a list of actions, which need to be completed in order to start up the
UPS from Manual Bypass Operation. The actions are initially indicated in red to show that they have
not yet been completed. A yellow bar will highlight the actions in the order in which they need to be
completed. As actions are completed they will change to green.
The Start-Up procedure is described in “System Start-Up from Manual Bypass
Operation” .
Normal
Manual bypass/Off
UPS Startup
5.40 PM
Close Q1
Close breaker Q5
Charge DC Capacitors
Close battery breakers Q7 and Q8
Close breaker Q2
Initiate transfer to static bypass
Open breaker Q3
Push UPS "ON" button
Display will be off until Q1 closed
SSW input
Initiate Charge
Connect battery
UPS output
Initiate transfer
Manual bypass
UPS will power up
12 Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
UPS Shutdown screen
The UPS Shutdown screen shows a list of actions, which need to be completed in order to shut down
the UPS. The actions are initially indicated in red to show that they have not yet been completed. A
yellow bar will highlight the actions in the order in which they need to be completed. As actions are
completed they will change to green.
The Start-Up procedure is described in “System Shutdown from Online to Manual
Bypass Operation” .
Normal
Normal
UPS Shutdown
5.40 PM
Initiate transfer to static bypass
Close breaker Q3
Open breaker Q5
Push UPS "OFF" button
Open breaker Q2
Open battery breakers Q7 and Q8
Open breaker Q1
Initiate transfer
Load will be on manual bypass
SSW input
UPS power down
UPS output
Isolate UPS from battery
UPS input
Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001 13
Online to Static Bypass Screen
From the Online to Static Bypass screen, the power flow can be transferred from Online to Static
Bypass Operation.
Initiate transfer to static bypass
In static bypass the load is powered directly by utility power.
There will be no UPS backup.
Normal
Normal
0:00 AM
Online to Static Bypass
Initiate transfer
14 Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001
Static Bypass to Online Screen
From the Static Bypass to Online screen, the power flow can be transferred from Static Bypass to
Online Operation.
Normal
Initiate transfer to online
Static Bypass to Online
0:00 AM
Initiate transfer
Static Bypass
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56