AGSTECH 100L User manual

Type
User manual

AGSTECH 100L is a 100W, 1U rack mountable DC output UPS with a wide range of features for reliable power backup and monitoring. It provides continuous, uninterrupted power to critical loads during power outages or fluctuations. With its advanced design, the AGSTECH 100L offers protection against overloads, short circuits, overvoltage, and overtemperature, ensuring the safety of your connected equipment.

AGSTECH 100L is a 100W, 1U rack mountable DC output UPS with a wide range of features for reliable power backup and monitoring. It provides continuous, uninterrupted power to critical loads during power outages or fluctuations. With its advanced design, the AGSTECH 100L offers protection against overloads, short circuits, overvoltage, and overtemperature, ensuring the safety of your connected equipment.

Page 1 of 7 VER.: 1.1
ON LINE DC OUTPUT UPS
100W-300W
Rack Mount 19” 1U
Users Manual
(DC12V/24V/48V with 2~6 channels)
Models: 100L / 150L / 200L / 300L
Page 2 of 7 VER.: 1.1
TABLE OF CONTENTS
1. Functional Description
Page 3
2. Installation Instructions
Page 4
3. Communication Interface
Page 5
4. Block Diagram
Page 5
5. LED Indications
Page 6
6. Specification
Page 7
Page 3 of 7 VER.: 1.1
1. Functional Description
In the normal mode, the charger will charge the battery and supply constant power
for O/P. The charging current will reduce when loading current increases.
Sometimes if the peak load current is over the level that charger can supply, the
battery will supply the load current at the same time. When battery is fully charged,
the charger will maintain the trickle charging and the O/P current. In case of power
failure, the charger will stop providing current, and the battery will take over to
maintain the output voltage.
Charging & Power Device design
Zero interruption
On-line structure design to provide the constant power without interruption.
backup mode (battery mode)
Soft start design to protect SPS
When AC is connect, SPS will turn on by soft start, then SPS in stable state,
It means if connect battery, there will be an inrush current to cause SPS, soft
start design will protect SPS.
Short circuit protection on outputs
The quick response short circuit protection limits the maximum output
current and prevents the fuse from burning.
Wide range input 130~280Vac, 50/60Hz
The UPS is able to provide stable DC output at 130~280Vac input voltage.
2~6 channels protection outputs
The multi-channel outputs use independent fuses for protection.
Condition monitoring USB, RS232 & optional SNMP
The smart interface for monitor conditions of battery, utility power & load status.
Deep discharge protection
Battery hot-swappable (External battery type)
Page 4 of 7 VER.: 1.1
2. Installation Instructions
The DC UPS may only be installed by trained personnel or qualified engineers.
Connect DC UPS to the batteries with correct polarity.
Check all connections for correct polarity!
Upon starting up the DC UPS with system monitoring, an automatic self-test is
carried out. The function monitoring for the battery circuit is not active until the
first test cycle is done, approx. 1 minute after startup. A test cycle then takes
place every 32 minute.
Page 5 of 7 VER.: 1.1
3. Communication Interface
Dry contact signal:
The definition and setup for RS-232 is as following:
Baud Rate
: 2400 bps
Data Length
: 8 bits
Stop Bit
: 1 bit
Parity
: None
Pin #6
: RS-232 data Tx out.
Pin #7
: Common of Pin #6 and Pin #9
Pin #9
: RS-232 data Rx In
4. Block Diagram
DC Output and
Backup
emergency power
Output Protection
OVP, OLP & SCP
System
Monitoring
Input Filter
Charging
Rectifier
Battery
AC Input
5 4 3 2 1
9 8 7 6
Page 6 of 7 VER.: 1.1
5. LED Indications
The system monitoring provides 8 LEDs to indicate the status of the DC UPS.
Front Panel Display
LED SIGNAL
LED#
COLOR
Operating Status
I/PWR
(Input Power)
Green
AC Normal
Yellow
Power Failure
O/PWR
(Output Power)
Green
DC Normal
Yellow
Overload or Short Circuit
CHG
(Charging)
Green
Fully Charged
Yellow
Charging or with loading
BAT
(Battery)
Red
Battery Replacement
Yellow
Battery Low
Functional Description of System Monitoring
The I/PWR green LED lights up when AC I/P is good and charger can provide
current to the battery. In case of blackout or burning of I/P fuse, the I/PWR
yellow LED lights up, the Green LED goes out and the error will be reported
via the dry contact signal.
The O/PWR green LED lights up when the O/P power is normal, the O/PWR
yellow LED lights up when the O/P power is abnormal, or short circuit, or the
O/P is overload.
The CHG green LED lights up when the charging voltage on battery reach full
level, the CHG yellow LED lights up when the charger is full ON for providing
current to the load or battery. It is normal when CHG yellow LED lights up all the
time when the load level is over 60% of full load.
The BAT red LED lights up when the battery is not well connected or when any
one of the battery is fail, the BAT yellow LED lights up when the battery voltage
is low and the error will be reported via the dry contact signal.
Page 7 of 7 VER.: 1.1
6. Specification
Model
AGS-100L
AGS-150L
AGS-200L
AGS-300L
Power Rating
100W
150W
200W
300W
Input Voltage
135 ~ 285VAC
Input Current @220VAC
Approx.1A
Approx.1.5A
Approx.2A
Approx.3A
Frequency
50/60Hz
Output Voltage
44Vdc ~ 56 Vdc (48Vdc)
Charge Close Voltage at
20
°
C
55.20VDC, with temperature compensation
Max. Charging Current (No Consumer Current)
2.2A
3.3A
4.4A
6.6A
Max. Allowable Constant Consumer Current
2A
3A
4A
6A
Environmental temperature range
0 ~ 40
°
C
Emergency power batteries
48V, 120Ah (max. charging current @6.6A)*
Battery Connections
12V: connected 4 pieces in series
24V: connected 2 pieces in series
Battery Low Signal
At approx. 44VDC Total
Cooling
Natural cooling (Fanless)
Protection
Overload / Short Circuit Protection
Over Voltage Protection
Over Temperature Protection
Battery Low Cut off
Fuse for Positive Polarity negative polarity
wrong connection
UPS Net Weight
3.4kg
3.5kg
3.9kg
4.1kg
Dimensions:
1u x 25cm
Battery Input
Anderson type* 1
I/O Switch
Power ON / OFF * 1
AC Input
IEC socket * 1
DC Output
Multiple screw terminals block * 2
Safety Standards
EN60950
Indicator
As following table
Package
1 piece / CTN using cushion to fixed device
Accessory (not included, except specified)
1. Power Cable IEC to any Type * 1
2. Mounting bracket * 2, Screw * 6 (included)
3. Battery charger cable
Anderson to #250 Terminal
* PS. Recommended battery size is 60Ah for charging current 6.6A and 20Ah for 2.2A.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7

AGSTECH 100L User manual

Type
User manual

AGSTECH 100L is a 100W, 1U rack mountable DC output UPS with a wide range of features for reliable power backup and monitoring. It provides continuous, uninterrupted power to critical loads during power outages or fluctuations. With its advanced design, the AGSTECH 100L offers protection against overloads, short circuits, overvoltage, and overtemperature, ensuring the safety of your connected equipment.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI