CET LBP62 Owner's manual

Type
Owner's manual

CET LBP62 is a programmable bidirectional counter with two programmable thresholds. It can be used to visualize and control a bidirectional count through two programmable thresholds. The device has a front push-button panel made of polycarbonate (anti-scratch, oil and acid resistant) and a protection grade of IP 65. It has removable terminal connections and a DIN 48 x 96 execution.

The CET LBP62 has several programmable parameters, including:

  • Time Reset
  • Impulse Multiplication factor
  • Count (Up / Down)
  • Decimal Point
  • Reset key function
  • Restart input

The device also has two thresholds, two relays with a capacity of 5A - 250 Vac or 2 NPN transistors 35 Vdc - 100 mA, and a static (without battery) programmed data memory.

CET LBP62 is a programmable bidirectional counter with two programmable thresholds. It can be used to visualize and control a bidirectional count through two programmable thresholds. The device has a front push-button panel made of polycarbonate (anti-scratch, oil and acid resistant) and a protection grade of IP 65. It has removable terminal connections and a DIN 48 x 96 execution.

The CET LBP62 has several programmable parameters, including:

  • Time Reset
  • Impulse Multiplication factor
  • Count (Up / Down)
  • Decimal Point
  • Reset key function
  • Restart input

The device also has two thresholds, two relays with a capacity of 5A - 250 Vac or 2 NPN transistors 35 Vdc - 100 mA, and a static (without battery) programmed data memory.

• Front push-bUtton panel made of polycarbonate
( antiscratch, oil and acid resistant )
• Protection grade IP 65
• Acces to parameters with software key: Time
Reset / Impuls Multiplier / Count / Decimal Point
/ Restart / Autolearning / Count mode / Keys lock
/ Reset key function / Restart input /
• Removable terminal connections
• DIN 48 x 96 execution
• Recessed assembly
• Special retaining brackets
• Two thresholdS
• Time Reset
• Inpuls multiplicatIon factor
• Count ( Up / Down )
• Overcount
• Autolearning
• Restart register
• Decimal point
• Reset key function
• Keys lock
• Restart input
• POWER SUPPLY
• SUPPLY TOLERANCE
• ABSORPTION
• OPERATION TEMPERATURE
• CLIMATIC CONDITIONS
• VISUALIZATION
• MULTIPLICATION FACTOR INPUT IMPULSES
• TYPE OF INPUTS
• COUNT FREQUENCY
• IMPULS COUNT
• AUXILIARY INPUT SUPPLY
• CONTROL INPUTS
• OUTPUTS
• RESET RELAY
• PROGRAMMED DATA MEMORY
THE LBP62 COUNTER CAN BE
ASSEMBLED WHERE NECESSARY TO
VISUALIZE AND CONTROL, THROUGH
TWO PROGRAMMABLE THRESHOLD,
A BIDIRECTIONAL COUNT.
MAIN FEATURES PROGRAMMABLE PARAMETERS
TECHNICAL FEATURES
: 24 - 110 - 220 Vac ( 50 / 60 Hz )
: + 10 % - 15 %
: 4 VA
: - 5 ł˚ C + 55 ˚ C
: U.R. 95 % at 40 ˚ C ( without condensate )
: 6 figures plus sign
: from 0,00001 to 9,99999
: suitable for NPN bidirectional encoder ( PNP by request )
: up to 20 KHz
: on 4 fronts : x4 ( Standard )
: on 1 front : x1 ( by request )
: 12 Vdc - 100 mA available on terminal
: reset counter - count restart - autolearning
: 2 relays - capacity of 5A - 250 Vac or 2 NPN transistors
35 Vdc - 100 mA
: manual or automatic with excitation time from 0,1 to 99,9
sec.
: static ( without battery )
PAGE 1
LBP62
LBP electronic counter
L1 L2
ENT
RES
PROG
CET s.r.l.
PROGRAMMABLE
BIDIRECTIONAL COUNTER
WITH TWO THRESHOLDS
Type:
LBP62
PRESS PUSH - BUTTON FOR ABOUT 2 SECS. THE DISPLAY VISUALIZE :
PRESS PUSH - BUTTON THE DISPLAY VISUALIZE :
OUTSIDE PROGRAMMING FOR NEW VALUE ENTERING ACCESS
FOR THRESHOLD PROGRAMMING ACCESS PROCEED AS FOLLOWS:
PROG
S1 THRESHOLD SETTING - PROGRAMMABLE FROM 000001 TO 999999 .
- if the data set results to be = 0 the device acts as totalizer, automatically
excluding the Reset Time and the Overcount ( SUP )
PROG
QUIT PROGRAMMING
ENT
WITH THE KEYS INSERT THE NEW VALUES AND CONFIRM WITH
ENT
THE PROGRAMMABLE PARAMETERS ARE DIVIDED INTO TWO GROUPS PROTECTED BY A 4 FIGURE CODE.
IN ORDER TO OBTAIN ACCESS TO PROGRAMMING, PROCEED AS FOLLOWS :
PROG
GROUP 1:
COUNT PROGRAMMING :
- UP = UP : the count increases ( from 0 to S1 )
- dn. = DOWN : count decreases ( from S1 to 0 )
S2 THRESHOLD SETTING - PROGRAMMABLE FORM 0001 TO 9999
- if the data set results = 0 the S2 threshold is excluded from the working .
- if the data set results equal or higher than S1, automatically become S2 = S1- 1
S2 is in OFFSET respect S1, that is the real S2 = S1 - S2. For example: S1 = 100
AUTOMATIC TIME RESET SETTING - PROGRAMMABLE FROM 0,1 TO 99,9 sec.
- if programmed = 0 the RESET is MANUAL
- if programmed with a value, the RESET is AUTOMATIC and the OVERCOUNT
( SUP ) is automatically excluded .
QUIT PROGRAMMING
ENT
ENT
ENT
ENT
ENTPROG
ENTER CODE 2357
- if programmed = 0 it automatically reprogrammes = 1. If a count value is to be
- S2 is in OFFSET respect S1; if S1 is equal or lower than S2, automatically
become S2 = S1 - 1.
MULTIPLIER OF THE IMPULSES is programmable from 0,00001 to 9,99999
PRESS PUSH - BUTTON RES
S2 = 20. The real value of S2 is = 100 - 20 = 80
divided, set a number lower than 1 on the multiplier. For example, to divided by 5
set 0,2 ( 1 : 5 = 0,2 ); to divided by 8 set 0,125 ( 1 : 8 = 0,125 )
FRONT PUSH-BUTTON PANEL
THRESHOLD PROGRAMMING
FUNCTIONING PARAMETERS PROGRAMMING
PAGE 2 LBP62
PROG
RED
BLUE
YELLOW
YELLOW During programming mode cursor moves to the left.
During normal mode allows temporary visualization of the programmed data
During programming mode increases the flashing figures.
During normal mode visualizes the previously set data on totalizer.
Access and quit from the programming mode .
During programming mode confirms the data and passes to the next ( ENT ).
During normal mode resets the device ( RES ).
RES
ENT
CET s.r.l.
ENT
PROG.
PRESS PUSH - BUTTON FOR ABOUT 2 SECS. THE DISPLAY VISUALIZES :
GROUP 2 : ENTER CODE 2413
OVERCOUNT PROGRAMMING : in this working mode when the count
- n .= OVERCOUNT off
- Y. = OVERCOUNT on
- Y. = AUTOLEARNING active
- n. = AUTOLEARNING excluded
RESTART REGISTER :value programmable from 0 to 999999
ENT
ENT
ENT
ENT
pass the S1 value set on the OUTPUT 1 and proceed on the visualizatio:n
if the count return under S1 or S2 the OUTPUTS turn off.
AUTOLEARNING : if it is Y. yes, the two leds on the front blinking and when
It can be inserted with the frontal RES key ( if programmed ) or with the
back command in impulsive or direct mode )
It is possible to programm a DECIMAL POINT on the last three digits
- 1 -> 999999 - 2 -> 99999.9
- 3 -> 9999.99 - 4 -> 999.999
if it is on it automatically exclued the Time reset
the input command is close the device memorize as S1 the value on the
display. It can not memorize negative values.
OUTSIDE PROGRAMMING FOR NEW VALUE ENTERING ACCESS
QUIT PROGRAMMING
ENTPROG
ENT
ENT
It’s possible to select the working mode of the frontal ENT / RES key:
- 1 - INHIBIT RESET. It is possible to reset the device only from the input
- 2 - ACTIVE RESET . It is possible to reset the device from the front key
- 3 - IMPULSIVE RESTART the key working as impulsive Restart
KEY LOCK: inhibit the possibility to modify the S1 with the key
- Y : LOCK access to S1
- n : FREE access to S1
Selection of the RESTART INPUT MODE:
- I. INPULSIVE RESTART ; il RESTART
- C. CONTINUOUS RESTART ; when the input command is close the
display shows the Restart value up to the input command is on
PRESS PUSH - BUTTON RES
command
and from the input command
FUNCTIONING PARAMETERS PROGRAMMING
PAGE 3LBP62CET s.r.l.
In DOWN programmation the S1 programmed
value is the count Start value and the OUTPUT 1 is
on when the count is = 0; the OUTPUT 2 is on
when the count is equal or lower than S2.
The RESTART Register value is between 0 and
999999. Every time the RESTART input is close the
RESTART value is loaded on display visualization
WORKING DIAGRAMS
PAGE 4 LBP62 CET s.r.l.
OUTPUT1
S1
S2
COUNT
OUTPUT1
S1
S2
COUNT
COUNT
OUTPUT1
S1
S2
t.r. t.r. t.r.
RESET
OUTPUT2
OUTPUT2
RESET
OUTPUT2
RESET
In MANUAL working the OUTPUT 1 is on
when the count is equal or higher than S1
and it’s stay on up to a RESET command.
The OUTPUT 2 is on when the count is
higher or equal than S2 and it’s stay on up
to a RESET command.
WORKING IN MANUAL
AUTOMATIC RESET WORKING
OVERCOUNT WORKING
The AUTOMATIC RESET working is the
same of the MANUAL one but when the S1
value is over, the count and the OUTPUT2
are automatically resetted and the
OUTPUT 1 is on all time long setted in " t.r."
The count restart the same working.
In OVERCOUNT ( SUP.) working the
OUTPUTS 1 - 2 are on every time the
count is equal or higher than the S1 and
S2 values. The S1 and S2 OUTPUTS are
off every time the count is lower than S1
and S2 values. With a RESET command
the OUTPUTS turn off and the count
restart the same working.
In the AUTOMATIC RESET working the "t.r." time
reset must be lower than the time used from the
count to arrive at the S1 value. Otherwise the
OUTPUTS 1 - 2 wil be alwayas on.
If the learned threshold value with
AUTOLEARNED ( APP ) input is lower than the
current count, the OUTPUTS go on. In the
contrary way, if the OUTPUTS are already on,
they turn off.
PAGE 5LBP62
COUNT DIAGRAMS
CET s.r.l.
AC POWER
14
1 2 3 4 5 6 7 8 9 10 11 12 13
12 Vdc
100mA
CNT2
CNT 1
R e s t a r t
R e s e t
A u t o l e a r n i n g
0 24 110 220
19 18 17 16 15
G
N
D
G
N
D
O
U
T
1
O
U
T
2
OUTPUT 1 OUTPUT 2
x 4
x 1
x 4
x 1
PHASE 1
PHASE 2
PHASE 2
PHASE 1
PHASE 2
PHASE 1
PHASE 2
PHASE 1
UP COUNTING
DOWN COUNTING
LBP62S
TRANSISTOR OUTPUTS
WIRING CONNECTIONS OUTPUT CHARACTERISTICS
RELAY :
The RL1 - RL2 outputs have 5A -
250 VAC contacts
STATIC :
The OUT 1 and OUT 2 outputs are
NPN in direct voltage with GND in
common together.
The maximun voltage applied to its
outputs is 35 Vdc and its maximum
current is 100mA.
WIRING CONNECTIONS
PAGE 6 LBP62
ENT
RES
LBP electronic counter
FRONT 10 Max.
SIDE
RETAINING
BRACKETS
REMOVABLE
TERMINAL
158
130 19 9
44 X 92
L1 L2
96
48
PROG
DRILL TEMPLATEBACK
93
45
48
96
19 18 17 16 15 14
1 83 5 7
469 10 11 12 132
OVERALL DIMENSIONS ( mm )
AC POWER
14
1234567 8910 11 12 13
12 Vdc
100mA
R L 1R L 2
CNT2
CNT 1
R e s t a r t
R e s e t
A u t o l e a r n i n g
0 24 110 220
19 18 17 16 15
OUTPUT 1 OUTPUT 2
INPUT SIGNALS
CET s.r.l.
CET Control System S.a.s.
SS 211 Km 53,550
28071 Borgolavezzaro - No - ITALY
Tel : ++39 321-885180/885301/885807
Fax : ++39 321-885560
Agent :
LBP62
RELAY OUTPUTS
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6

CET LBP62 Owner's manual

Type
Owner's manual

CET LBP62 is a programmable bidirectional counter with two programmable thresholds. It can be used to visualize and control a bidirectional count through two programmable thresholds. The device has a front push-button panel made of polycarbonate (anti-scratch, oil and acid resistant) and a protection grade of IP 65. It has removable terminal connections and a DIN 48 x 96 execution.

The CET LBP62 has several programmable parameters, including:

  • Time Reset
  • Impulse Multiplication factor
  • Count (Up / Down)
  • Decimal Point
  • Reset key function
  • Restart input

The device also has two thresholds, two relays with a capacity of 5A - 250 Vac or 2 NPN transistors 35 Vdc - 100 mA, and a static (without battery) programmed data memory.