Oilon RE 140 Operating instructions

Category
Heat pumps
Type
Operating instructions
RE03 1406 EN
Installation and operation manual
Oilon RE 110 - RE 170
Read these instructions carefully before installation, use, or maintenance
RE03 1406 EN 1 (48)
Contents
1. Introduction
1.1. Warnings....................................................................................................... 3
1.2. Transportation and storage.......................................................................... 3
1.3. Delivery content, optional equipment and accessories................................ 4
1.4. Control system.............................................................................................. 4
1.5. Ground source heat pump operating principle............................................. 5
1.6. Ground source heat pump features............................................................. 6
1.7. Coefficient of performance........................................................................... 7
1.8. Ground source heat pump sizing................................................................. 7
1.9. Collecting heat.............................................................................................. 8
2. Installation
2.1. Installation site requirements........................................................................9
2.2. Main components........................................................................................10
2.3. Connections................................................................................................ 11
2.4. Piping diagrams.......................................................................................... 12
2.5. Installing filters............................................................................................ 17
2.6. Connecting to cooling systems...................................................................17
2.7. Electrical connections................................................................................. 18
3. Commissioning
3.1. Fuses and switches.................................................................................... 20
3.2. Prerequisites for commissioning.................................................................20
3.3. Commissioning the system.........................................................................21
3.4. Relay test.................................................................................................... 22
3.5. Adding heating circuits............................................................................... 22
3.6. Configuring heating curve...........................................................................23
3.7. Connecting solar heating............................................................................24
3.8. Configuring alarm output............................................................................ 24
4. Operation
4.1. Control panel...............................................................................................25
4.2. Changing settings....................................................................................... 28
4.3. Changing user level....................................................................................29
4.4. Setting language......................................................................................... 29
4.5. Setting time and date................................................................................. 29
4.6. Configuring domestic hot water settings.................................................... 30
4.7. Operating lines............................................................................................30
5. Maintenance
5.1. Annual maintenance................................................................................... 35
5.2. Cleaning the brine circuit filter....................................................................35
5.3. Troubleshooting...........................................................................................35
2 (48) RE03 1406 EN
5.4. Compressor protection device....................................................................37
6. Technical data
6.1. Technical data.............................................................................................39
6.2. Condenser and evaporator circuit flow and pumps....................................40
6.3. Spare parts................................................................................................. 46
RE03 1406 EN 3 (48)
1. Introduction
1.1. Warnings
Read these instructions carefully before installing, adjusting or maintenance of the
device. Follow the given instructions.
Throughout this manual, the following warnings are used to point out information:
Be careful. The symbol indicates a possible danger of bodily
harm or lethal injury if instructions are not followed.
Pay attention. The symbol indicates a possible danger
of damage to the device, components or surroundings if
instructions are not followed.
Read this instruction. Note indicates important information.
1.2. Transportation and storage
Transport and store the heat pump in a vertical position.
Transport the heat pump to the installation site on its
transporting platform.
Be careful when lifting the heat pump. Use appropriate lifting tools.
You can lift the heat pump from the bottom with hand truck.
4 (48) RE03 1406 EN
1.3. Delivery content, optional equipment and accessories
Standard delivery content
Heat pump standard delivery includes the following:
heat pump
condenser pump
ground circuit pump
temperature sensor for outdoors
temperature sensor for supply water
3 temperature sensors for buffer tanks
installation and operation manual, electrical drawings
installation, commissioning and warranty records
maintenance sheets.
Optional equipment
In addition to the standard delivery content, the following optional equipment may be
separately ordered:
desuperheater package (includes exchanger, circulation pump and hoses)
wired or wireless remote control unit, including room temperature sensor
Smartweb connection.
Accessories
When installing the heat pump, depending on the installation site, few extra
accessories and devices maybe needed. Among other things, the following
accessories may be separately ordered:
ground circuit diaphragm expansion tank
ground circuit safety valve
heating circuit diaphragm expansion tank
heating circuit 3 or 4-way valves
electric cables needed outside the heat pump
heating system expansion tank
pump for heating circuits 1, 2 and 3
mixing valve for domestic hot water
heating system safety valve (1,5 bar)
heating system pressure gauge (0–4 bar)
ground circuit pressure gauge (0–4 bar)
filters for ground circuit and heating circuit
flexible connection hoses for brine and condenser circuits with seals
pipes and pipe accessories.
1.4. Control system
The heat pump is equipped with an automatic control system which manages heating
and domestic hot water production. The control system includes the built-in automation
system, the sensors attached to it, and a control panel. Browsing and changing system
settings is done on the control panel. It is also used for browsing and resetting error
notifications.
RE03 1406 EN 5 (48)
A remote control unit (option) can also be used for browsing and changing system
data and error notifications. The remote control unit can also be used as a remote
temperature sensor, providing the control system with room temperature data.
The system settings have been organised into menus, similar to folders on a computer.
In addition, there are various user levels in the system. The visibility of menus or
menu items depends on the user level. To access user levels other than End user or
Commissioning, you need an access code.
1.5. Ground source heat pump operating principle
A ground source heat pump is a device that uses heat energy from the Sun that is
absorbed into Earth’s surface.
A
B
C
RE15 ver. 2
1. Evaporator
2. Compressor
3. Condenser
4. Expansion valve
A. Brine circuit
B. Refrigerant circuit
C. Heating circuit
There are three closed circuits running within, or through, the heat pump:
brine circuit
refrigerant circuit
heating circuit.
The heat pump's operation is based on the vaporisation and condensation of the
refrigerant circulating within the heat pump.
The brine circuit is a circuit for collecting heat energy from the ground. When the brine
enters to the circuit at the evaporator, it is very cold. As it travels along the circuit, it
collects heat energy from the ground or water, which causes the brine temperature
to rise. The brine completes its circuit by returning to the evaporator and releasing
the heat energy into the refrigerant, which circulates between the evaporator and the
condenser.
6 (48) RE03 1406 EN
When the refrigerant is in the condenser, it is colder than the brine, so the heat
energy transfer from brine into refrigerant can take place. The heat transfer raises the
temperature of the refrigerant up to the point where it becomes gaseous.
The gaseous refrigerant is then led into a compressor, which compresses it into a
high pressure. As the pressure of the gaseous refrigerant increases, so does its
temperature.
Next, the high-pressure gaseous refrigerant is led into the condenser, where it releases
its heat energy into the water that circulates between the heat pump and the buffer
tank. As the refrigerant releases its heat energy and its temperature drops, it becomes
liquid again.
The liquid refrigerant is then led into an expansion valve, where the pressure and
temperature are lowered further. The refrigerant completes its circuit by returning back
to the vaporiser, where it receives heat energy from the brine circuit.
1.6. Ground source heat pump features
RE17 ver. 1
1. Evaporator
2. Compressor
3. Condenser
4. Expansion valve
5. Desuperheater (option)
6. Liquid injection
A. Brine circuit
B. Refrigerant circuit
C. Condenser circuit
D. Desuperheater circuit
E. Domestic hot water
F. Heating circuit out
G. Domestic cold water
H. Heating circuit in
RE03 1406 EN 7 (48)
The RE heat pump is always connected to separate buffer tank or buffer tanks.
Domestic hot water is warmed up in hot water loops inside buffer tank. Preheating loop
can be located in the middle of the same buffer tank or in another buffer tank. Rest of
the heating is carried out by loop in the upper part of the buffer tank or loop in separate
domestic hot water buffer tank.
For all RE heat pumps desuperheater functionality can be ordered as an option.
The compressors are equipped with liquid injection functionality. In case the
temperature of the refrigerant gets too high in the compressor, low temperature
refrigerant is injected to the compressor. This functionality enables higher temperature
taken out from the heat pump and optimizes the temperature and pressure for the
compressor. This functionality includes an own internal operating control system with
fault diagnostics.
1.7. Coefficient of performance
Heat pump efficiency ratios are compared by their coefficient of performance (COP)
values.
COP indicates the amount of heat energy produced by the heat pump divided by the
energy consumed by the heat pump.
COP depends largely on heat source and heating network temperatures. The highest
possible heat source temperature and the lowest possible supply water temperature
improve efficiency ratio.
1.8. Ground source heat pump sizing
Ground source heat pump can be sized to operate at
partial capacity
full capacity.
With partial capacity heat pump maximum capacity is sized up to correspond 60 – 80%
of a building’s maximum heating demand. In this case the heat pump produces the
most part of the building’s annual heat energy demand.
With partial capacity, heat pump operating periods are long during heating season.
This reduces the number of compressor stops and start-ups. During hardest freezing
periods at winter additional capacity from heat pump can be obtained with in-built
electric heater or oil boiler.
With full capacity, heat pump is sized up according to a building’s maximum capacity
demand, practically slightly over sized. With full capacity, the use of additional heating
capacity is minimised, thus in electric heaters’ case it is possible to use smaller fuse
size in electrical connection.
8 (48) RE03 1406 EN
1.9. Collecting heat
Oilon RE heat pump’s heat source is usually a drilled well. The number and depth of
wells depend on heating demand. Soil or water can also be used as heat source. Heat
is collected from soil using horizontal piping in 1–1.5 m depth. When using water the
piping is anchored to the bottom.
During heating period, the ground circuit fluid warms up a few degrees during
circulation. Collected heat is used to vaporise refrigerant in heat pump unit.
Horizontal piping requires applicable soil type and sufficient land area for piping.
Applicable soil types are fine grained and moist, such as clay or silt.
Drilled well is suitable for all locations except places where solid rock goes deep
underground.
When piping is installed into water, building should be located sufficiently close to
shoreline, preferably less than 50 m away. Water should also be sufficiently deep, over
2 m right from shore.
In addition, waste heat from industrial processes can be used as heat source for the
heat pump.
RE03 1406 EN 9 (48)
2. Installation
2.1. Installation site requirements
General site requirements
Follow local construction rules and regulations when installing
the heat pump.
In addition, make sure that the following requirements are met:
The installation site must have a floor drain.
Maximum temperature for the site is 40 °C.
Minimum temperature for the site is 10 °C.
The heat pump installation surface is horizontal and even.
The heat pump is covered against moisture and water.
Refrigerant circulation site requirements
Refrigerant circulations are equipped with pressure relief valves. In fault situations they
burst out the excess pressure from the circulations.
Ensure that a possible burst of the refrigerant circulations’
pressure relief valves do not endanger people or properties.
When R410A refrigerant is used, if the amount of the used refrigerant compared to
the engine room’s volume is less than 0,44 kg/m3, it is not obligatory to pipe out the
pressure relief valves. For example, if the heat pump contains 32 kg of refiregerant, it is
not necessary to pipe out the pressure relief valves, if the room’s volume is more than
32 kg / 0,44 kg/m3 = 73 m3.
Follow the pressure equipment regulations and SFS-EN 13136 standard when piping
and dimensioning the refrigerant.
Space requirements
All heat pump connections are at the back of the device and with flexible hoses
they can be bent to desired directions. For installation, operating and maintenance
purposes, leave enough space on each side of the heat pump. The minimum space
requirements are listed below.
By default, the electric switchboard is attached to the left side of the heat pump. On
request, the electrical switchboard can be attached to the right side of the heat pump.
10 (48) RE03 1406 EN
RE01 ver. 2
Model/
Dimension RE 110, RE 140 and RE 170
a
(left)
800 mm
(100 mm, if electric switchboard
attached to the right side.)
b
(back) 300 mm
c
(right)
100 mm
(1200 mm, if electric switchboard
attached to the right side.)
d
(front) 800 mm
e
(top) 100 mm
2.2. Main components
MCRE03 ver. 3
RE03 1406 EN 11 (48)
Number Component Number Component
1 Main electrical switch 8 Compressor operating control
system (OCS) devices
2 Control panel 9 Refrigerant pressure double
relief valves with change valves
3 Cooling fan with filters 10 Refrigerant expansion tanks
4 Evaporator 11 Dryer-filters
5 Condenser 12 Expansion valves
6 Desuperheaters (optional) 13 Solenoid valves
7 Compressors
2.3. Connections
RE 110, RE 140 and RE 170
Connection positions and sizes are listed below.
RE10 ver. 3
Connection Size (external thread)
1 condenser out G 2 1/2
2 condenser in G 2 1/2
3 vaporiser in G 2 1/2
4 vaporiser out G 2 1/2
5 desuperheater in (optional) G 1 1/4
12 (48) RE03 1406 EN
6 desuperheater out (optional) G 1 1/4
7 and 8 plugged, do not connect -
9 and 10 holes for piping out refrigerant pressure
relief valves
-
2.4. Piping diagrams
2.4.1. Ground circuit piping
It is recommended to install line regulation valves with flow meters, shut-off valves and
pressure gauge as shown in the figure below. If there is a risk that the ground circuit
pipes are not clean, install two filters to the return line to ensure fluent flow.
RE04 ver. 2
A filters
B pressure gauge
C safety valve
D expansion tank
E line regulating valve with flow meter
RE03 1406 EN 13 (48)
Make approx. 1 m deep service well on top of heat well. Connect service wells to one
shared collector well using insulated pipes. One of the drilled wells can also operate as
a collector well. Fluid from collector well is led to heat pump well through two insulated
pipes.
2.4.2. Heating circuit piping
In the following, few examples of heating circuit piping options are presented.
Heat pump with desuperheater and buffer tank
PI RE ver. 6
1 heat pump A desuperheater out
2 buffer tank B desuperheater in
3 heating circuit C condenser out
BX11temp.sensor, supply water D condenser in
BX1 temp.sensor, buffer tank middle part E domestic hot water out
BX2 temp.sensor, buffer tank lower part F domestic hot water circulation
BX8 temp.sensor, buffer tank upper part G domestic cold water in
BX9 temp.sensor, outdoors
14 (48) RE03 1406 EN
Heat pump with desuperheater, buffer tank and extra heating system
PI RE 1 ver. 6
1 heat pump A desuperheater out
2 buffer tank B desuperheater in
3 heating circuit C condenser out
4 extra heating system, e.g. electric or
oil heater
D condenser in
BX11temp.sensor, supply water E domestic hot water out
BX1 temp.sensor, buffer tank middle part F domestic hot water circulation
BX2 temp.sensor, buffer tank lower part G domestic cold water in
BX8 temp.sensor, buffer tank upper part
BX9 temp.sensor, outdoors
RE03 1406 EN 15 (48)
Heat pump with desuperheater and two external buffer tank
PI RE 2 ver. 6
1 heat pump A desuperheater out
2 buffer tanks B desuperheater in
3 heating circuit C condenser out
BX11temp.sensor, supply water D condenser in
BX1 temp.sensor, buffer tank middle part E domestic hot water out
BX2 temp.sensor, buffer tank lower part F domestic hot water circulation
BX8 temp.sensor, domestic hot water
buffer tank
G domestic cold water in
BX9 temp.sensor, outdoors
16 (48) RE03 1406 EN
Heat pump with desuperheater, two external buffer tank and solar heating system
PI RE 3 ver. 4
1 heat pump A desuperheater out
2 buffer tank B desuperheater in
3 heating circuit C condenser out
4 solar heat collectors D condenser in
BX11temp.sensor, supply water E domestic hot water out
BX1 temp.sensor, buffer tank middle part F domestic hot water circulation
BX2 temp.sensor, buffer tank lower part G domestic cold water in
BX8 temp.sensor, domestic hot water
buffer tank
 
B6 temp.sensor, solar heat collector
BX9 temp.sensor, outdoors
RE03 1406 EN 17 (48)
2.5. Installing filters
At renovation sites, flush and clean the existing heating system.
A filter should always be installed on both the heating circuit return line and the brine
circuit return line before the heat pump.
Install a shut-off valve on both sides of the filter to facilitate easy
cleaning and replacing of the filter element.
2.6. Connecting to cooling systems
If the brine circuit is laid into boreholes, the collector circuit can also be used for cooling
the house. If the brine circuit is laid in surface soil or in water, it is not recommended to
connect it to a cooling system, as the soil and water temperature usually rises to such
levels that there is not much cooling capacity in the brine.
Take a separate branch from the brine circuit’s return line and lead it to an air-
conditioner with integrated cooling radiator or to a cooling radiator placed in separate
air intake duct. Install a separate circuit for the cooling radiator, equipped with own
rotary pump, see figure below.
GSHP26 ver. 4
A fan
B cooling radiator
C filter
D circulation pump
E regulating valve
F non-return valve
G ground circuit return line
H shut-off valves
For more detailed information in connecting to air conditioner,
refer to the manufacturer’s instructions.
18 (48) RE03 1406 EN
2.7. Electrical connections
A general description of the needed electrical connections is given in this section. The
actual connections should be made according to the wiring diagrams delivered with the
heat pump.
Do not connect devices that draw over 2 A of current directly to
the controller. Use a contactor instead.
Switches and fuses
Fuse sizeSwitch Device
RE 110 RE 140 RE 170
F1 Circuit breaker, compressor 1 63 A 80 A 80 A
F2 Circuit breaker, compressor 2 63 A 80 A 80 A
F3 Motor protection switch, ground
circuit pump
3,3 A 4,5 A 4,5 A
F4 Motor protection switch,
condenser circuit pump
2,0 A 2,0 A 2,0 A
F5 Motor protection switch,
domestic hot water circuit pump
2,0 A 2,0 A 2,0 A
F6 Motor protection switch,
desuperheater circuit
(optional)
2,0 A 2,0 A 2,0 A
F10 Circuit breaker, control system 6 A 6 A 6 A
Sensor connections
The sensor connections are illustrated and listed in the following.
The amount of sensors depends on the heat pump model and
accessories.
Some of the sensors are pre-connected.
RE03 ver. 2
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

Oilon RE 140 Operating instructions

Category
Heat pumps
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI