  • Hello! I am an AI chatbot trained to assist you with the Victron energy Battery Alarm Owner's manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Battery Alarm
ENGLISH
Remote panel adjustments
Dipswitch explanation:
A
B
12V
24V
12V
24V
1
-0,1V -0,1V ON ON
2
-0,2V -0,2V ON OFF
3
-0,2V -0,2V Not used Not used
4
-0,5V -0,5V HYSB +1,25V HYSB +2,50V
5
-1V -1V HYSA +2,50V HYSA +5V
6
-2V -2V Uhigh -2V Uhigh -2V
7
ON OFF Uhigh -1V Uhigh -1V
8
Not used Not used ON OFF
1. Place A7, B2, B8 on the 12V or 24V setting. [ON=12V]
[OFF=24V]
2. B1 always ON
3. With the Dipswitches A1 t/m A6 chose a higher or lower Ulow
alarm.
4. Place A1, A2, A3, A4, A5, A6 = ON, then Ulow = 9.5V or
A1, A2, A3, A4, A6 = ON, and A5 = OFF, then Ulow = 10.5V or
A1, A2, A3, A4, A5 = ON, and A6 = OFF, then Ulow = 11.5V.
5. With the Dipswitches B6, B7 chose a higher or lower Uhigh
alarm.
B6, B7 = ON. The Uhigh alarm is 15V. Change this with B6 and
B7.
B6 = ON, and B7 = OFF, then Uhigh alarm is 16V
B6 = OFF, and B7 = ON, then Uhigh alarm is 16.5V
6. B4, B5 = OFF. The hysteresis for Ulow alarm is now 1V for 12V
and 24V Battery Alarm remote panel.
For another hysteresis; switch B4 and/or B5 to the ON position.
B4 gives a 1V+1.25V hysteresis for a 12V Battery Alarm and
2V+2.5V for a 24V Battery Alarm.
B5 gives a 1V+2.50V hysteresis for a 12V Battery Alarm and
2V+5V for a 24V Battery Alarm.
Revision : Rev00
Date : 22-06-2012
Victron Energy bv / De Paal 35 / 1351 JG ALMERE / The Netherlands
Phone: (+31) (0)36 535 97 00 / Fax: (+31) (0)36 535 97 40 / www.victronenergy.com / e-mail: sal[email protected]
Warning:
For the J1 connector on the PCB the contacts
(COM, N0 and NC) are as per diagram below!
/