Victron energy Battery Alarm Owner's manual

Type
Owner's manual
Battery Alarm
ENGLISH
Remote panel adjustments
Dipswitch explanation:
A
B
12V
24V
12V
24V
1
-0,1V -0,1V ON ON
2
-0,2V -0,2V ON OFF
3
-0,2V -0,2V Not used Not used
4
-0,5V -0,5V HYSB +1,25V HYSB +2,50V
5
-1V -1V HYSA +2,50V HYSA +5V
6
-2V -2V Uhigh -2V Uhigh -2V
7
ON OFF Uhigh -1V Uhigh -1V
8
Not used Not used ON OFF
1. Place A7, B2, B8 on the 12V or 24V setting. [ON=12V]
[OFF=24V]
2. B1 always ON
3. With the Dipswitches A1 t/m A6 chose a higher or lower Ulow
alarm.
4. Place A1, A2, A3, A4, A5, A6 = ON, then Ulow = 9.5V or
A1, A2, A3, A4, A6 = ON, and A5 = OFF, then Ulow = 10.5V or
A1, A2, A3, A4, A5 = ON, and A6 = OFF, then Ulow = 11.5V.
5. With the Dipswitches B6, B7 chose a higher or lower Uhigh
alarm.
B6, B7 = ON. The Uhigh alarm is 15V. Change this with B6 and
B7.
B6 = ON, and B7 = OFF, then Uhigh alarm is 16V
B6 = OFF, and B7 = ON, then Uhigh alarm is 16.5V
6. B4, B5 = OFF. The hysteresis for Ulow alarm is now 1V for 12V
and 24V Battery Alarm remote panel.
For another hysteresis; switch B4 and/or B5 to the ON position.
B4 gives a 1V+1.25V hysteresis for a 12V Battery Alarm and
2V+2.5V for a 24V Battery Alarm.
B5 gives a 1V+2.50V hysteresis for a 12V Battery Alarm and
2V+5V for a 24V Battery Alarm.
Revision : Rev00
Date : 22-06-2012
Victron Energy bv / De Paal 35 / 1351 JG ALMERE / The Netherlands
Phone: (+31) (0)36 535 97 00 / Fax: (+31) (0)36 535 97 40 / www.victronenergy.com / e-mail: sal[email protected]
Warning:
For the J1 connector on the PCB the contacts
(COM, N0 and NC) are as per diagram below!
  • Page 1 1

Victron energy Battery Alarm Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI