Astria Fireplaces Altair-OLD Instruction Sheet

Type
Instruction Sheet
This addendum is in addition to the Installation and Operation
Manuals provided with IHP Electronic gas appliances listed to
Z21.88 / CSA 2.33 (standard for Vented Gas Fireplace Heaters)
and are sold in areas where local codes prohibit use of fireplaces
with standing or continuous pilots (CPI).
DISABLING THE CPI INSTRUCTIONS:
NOTE: Standing Pilots are not allowed in areas where local
codes prohibit use of fireplaces with standing or continuous
pilots (CPI), therefore the CPI function must be disabled per
these instructions.
SIT Proflame I System (see below)
Disconnect the 2 wires from the IPI/CPI switch (see Figures 1A & 1B)
1) Remove the switch and discard
2) CPI function will be disabled
NOTE: The Fireplace shall not be operated in the continuous
pilot mode.
Addendum for Disabling the
CPI (continuous pilot ignition)
feature on IHP Electronic Gas
Appliances
P/N 900949-00 Rev. NC 12/2018
For more information, visit IHP.US.com
1
Figure 1A - SIT Proflame I System (Fixed Valve)
Figure 1B - SIT Proflame I System (Adjustable Valve)
Figure 2 - SIT Proflame II System
SIT Proflame II System (see below)
1) Cut gray jumper wire on module (see Figure 2)
2) Once the gray jumper wire is cut the CPI function on the
remote control will be disabled
NOTE: The Fireplace shall not be operated in the continuous
pilot mode.
Gray jumper wire
Disconnect Wires, Remove
and discard switch
Disconnect Wires, Remove
and discard switch
2
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Printed in U.S.A. © 2018 Innovative Hearth Products
P/N 900949-00 Rev. NC 12/2018
Innovative Hearth Products (IHP) reserves the right to make changes at any time, without notice,
in design, materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
1769 East Lawrence Street • Russellville, AL 35654
Figure 3 - Skytech System
Skytech System (see below)
1) Disconnect the 2 wires from the IPI/CPI switch
2) Remove the switch and discard
NOTE: The Fireplace shall not be operated in the continuous pilot mode
Disconnect Wires, Remove
and discard switch