Coaire CIC-24M2Z User manual

Category
Split-system air conditioners
Type
User manual

This manual is also suitable for

MODEL : CIC-09M1Z CIH-09M1Z
CIC-12M1Z CIH-12M1Z
CIC-18M2Z CIH-18M2Z
CIC-24M2Z CIH-24M2Z
SERVICE MANUAL
Content
- 1 -
Content
1 Precaution......................................................................................................................... 1
1.1 Safety Precaution ................................................................................................................................... 1
1.2 Warning .................................................................................................................................................. 1
2 Function ............................................................................................................................ 4
3 Dimension ......................................................................................................................... 5
4 Specification ..................................................................................................................... 7
5 Refrigerant cycle diagram ............................................................................................. 10
6 Operation limits .............................................................................................................. 11
7 Wiring diagram ............................................................................................................... 12
8 Installation details .......................................................................................................... 22
8.1 Wrench torque sheet for installation .................................................................................................... 22
8.2 Connecting the cables ......................................................................................................................... 22
8.3 Pipe length and the elevation .............................................................................................................. 22
8.4 Air purging of the piping and indoor unit .............................................................................................. 23
8.5 Pumping down (Re-installation) ........................................................................................................... 25
8.6 Re-air purging (Re-installation) ............................................................................................................ 26
8.7 Balance refrigerant of the 2-way, 3-way valves ................................................................................... 27
8.8 Evacuation ........................................................................................................................................... 28
8.9 Gas charging ........................................................................................................................................ 29
9 Electronic function ......................................................................................................... 30
9.1 Electronic control working environment ............................................................................................... 30
9.2 Proper symbols and their meaning ...................................................................................................... 30
9.3 Function ............................................................................................................................................... 31
9.4 Protection ............................................................................................................................................. 31
9.5 Fan only mode ..................................................................................................................................... 32
9.6 Cooling mode ....................................................................................................................................... 32
9.7 Dehumidifying mode ............................................................................................................................ 33
9.8 Heating mode ....................................................................................................................................... 33
9.9 Defrosting mode(available for heating mode) ..................................................................................... 34
9.10 Auto mode .......................................................................................................................................... 35
9.11 Force cooling function ........................................................................................................................ 35
9.12 Sleep mode(Economic mode) ........................................................................................................... 36
9.13 Auto restart function ........................................................................................................................... 37
9.14 Turbo mode ........................................................................................................................................ 37
9.15 Ionizer (air clean) function ................................................................................................................. 37
9.16 Follow me function ............................................................................................................................. 37
10 Model and Parameters ................................................................................................... 39
11 Troubleshooting ............................................................................................................. 41
11.1 Display board ..................................................................................................................................... 41
11.2 Troubleshooting .................................................................................................................................. 42
11.3 Diagnostic chart.................................................................................................................................. 43
11.4 Resetting phenomenon often occurs during operation. ..................................................................... 45
Content
- 2 -
11.5 Indoor fan speed out of control . ........................................................................................................ 45
11.6 Temperature sensor error. .................................................................................................................. 46
11.7 Over current protection of the compressor occurs 4 times ................................................................ 46
11.8 EEROM error ...................................................................................................................................... 46
11.9 Outdoor unit protects .......................................................................................................................... 47
11.10 Indoor unit communication error. ..................................................................................................... 47
12 Characteristic of temperature sensor .......................................................................... 48
Service manual
- 1 -
1 Precaution
1.1 Safety Precaution
 To prevent injury to the user or other people and property damage, the following instructions
must be followed.
 Incorrect operation due to ignoring instruction will cause harm or damage.
 Before service unit, be sure to read this service manual at first.
1.2 Warning
 Installation
 Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated
circuit.
There is risk of fire or electric shock.
 For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized service
center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
 Always ground the product.
There is risk of fire or electric shock.
 Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
 Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric shock.
 Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
 Do not modify or extend the power cable.
There is risk of fire or electric shock.
 Do not install, remove, or reinstall the unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
 Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and
evaporator.
 For installation, always contact the dealer or an Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
 Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
 Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal
injury.
 Do not let the air conditioner run for a long time when the humidity is very high and a door or
windows is left open.
Moisture may condense and wet or damage furniture.
 Take care to ensure that power cable could not be pulled out or damaged during operation.
There is risk of fire or electric shock.
Service manual
- 2 -
 Do not place anything on the power cable.
There is risk of fire or electric shock.
 Do not plug or unplug the power supply plug during operation.
There is risk of fire or electric shock.
 Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
 Do not place a heater or other appliance near the power cable.
There is risk of fire and electric shock.
 Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
 Do not store or use flammable gas or combustible near the product.
There is risk of fire or failure of product.
 Do not use the product in a tightly closed space for a long time.
Oxygen deficiency could occur.
 When flammable gas leaks, turn off the gas and open a window for ventilation before turn the
product on.
Do not use the telephone or turn switches on or off.
There is risk of explosion or fire.
 If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect
the power supply cable.
There is risk of electric shock or fire.
 Stop operation and close the window in storm or hurricane. If possible, remove the product
from the window before the hurricane arrives.
There is risk of property damage, failure of product, or electric shock.
 Do not open the inlet grill of the product during operation. (Do not touch the electrostatic
filter, if the unit is so equipped.
There is risk of physical injury, electric shock, or product failure.
 When the product is soaked (flooded or submerged), contact an Authorized service center.
There is risk of fire or electric shock.
 Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
 Ventilate the product from time to time when operating it together with a stove, etc.
There is risk of fire or electric shock.
 Turn the main power off when cleaning or maintaining the product.
There is risk of electric shock.
 When the product is not be used for a long time, disconnect the power supply plug or turn off
the breaker.
There is risk of product damage or failure, or unintended operation.
 Take care to ensure that nobody could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
 CAUTION
 Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
 Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
 Keep level even when installing the product.
To avoid vibration of water leakage.
 Do not install the product where the noise or hot air from the outdoor unit could damage the
neighborhoods.
It may cause a problem for your neighbors.
Service manual
- 3 -
 Use two or more people to lift and transport the product.
Avoid personal injury.
 Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause
product malfunction or inefficient operation.
 Operational
 Do not expose the skin directly to cool air for long periods of time. (Do not sit in the draft).
This could harm to your health.
 Do not use the product for special purposes, such as preserving foods, works of art, etc. It is
a consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
 Do not block the inlet or outlet of air flow.
It may cause product failure.
 Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
 Do not touch the metal parts of the product when removing the air filter. They are very sharp.
There is risk of personal injury.
 Do not step on pr put anything on the product. (outdoor units)
There is risk of personal injury and failure of product.
 Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
 Do not insert hands or other object through air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
 Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
 Use a firm stool or ladder when cleaning or maintaining the product.
Be careful and avoid personal injury.
 Replace the all batteries in the remote control with new ones of the same type. Do not mix old
and mew batteries or different types of batteries.
There is risk of fire or explosion.
 Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn of explode.
 If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do
not use the remote of the batteries have leaked.
The chemical in batteries could cause burns or other health hazards.
Service manual
- 4 -
2 Function
 Indoor unit
1. Operation ON/OFF by remote
controller
2. Sensing by room temperature
Room temperature sensor. Pipe temperature
sensor.
3. Room temperature control
Maintain the room temperature in accordance with
the setting temperature.
4. Starting temperature control
Indoor fan is delayed for 5 sec at the starting.
5. Time Delay Safety control
Restarting is for approx. 3 minutes.
6. Indoor fan speed control
High, med, low, breeze.
7. Operation indication Lamps (LED)
Light up in the LED for each operation mode.
8. Two-direction air vane
The unit will decide the louver direction according
to operation mode.
9. Sleep mode auto control
The fan is turn to low speed (cooling/heating).
The unit will be turn off after seven hours.
10. Independent dehumidification
The function is usually used in rainy days in
springtime or damp areas
11. Self-diag. function
The function will be operate in any operation mode.
12. Air flow Direction control
The louver can be set at the desired position or
swing up and down automatically
13. Auto mode
The unit can be change by the room temperature.
14. Anti-cold function
Prevent the cold wind at the beginning of unit start.
15. Temp. Compensation
16. Defrost mode
17. Auto-restart function
18. Flexible wiring connection
19. Easy clean panel
20. Ionizer (optional)
The function is operated by remote controller.
21.Follow me (optional)
The function is operated by remote controller.
22. Turbo
This function enables the unit to reach the preset
temperature in the shortest time under cooling mode.
 Outdoor unit
1. Power relay control
The unit has 3 mins delay between continuously
ON/OFF operations.
2. Low noise air flow system
Bird tail propeller fan makes the outdoor unit run
more quietly
3. Hydrophilic aluminum fin
For the cooling & heating mode only.
The hydrophilic fin can improve the heating
efficiency at operation mode.
4. 4 way valve control
It is only operated in the heating operation mode
except defrosting operation.
5. Anti-rust cabinet
Made from electrolytic zinc steel sheet and anti-rust
coated components.
6. Valve protection cover
It protects the valves and prevents water from
dripping.
Service manual
- 5 -
3 Dimension
Indoor unit
Dimension
Mode W H D
9K 790265195
12K920292225
18K1080330225
24K1250325230
Service manual
- 6 -
outdoor unit
Dimension
ModeW H D L1 L2
9K 780540250549276
12K760590285530290
18K845695335560335
24K895860330590333
Service manual
- 7 -
4 Specification
Ph-V-Hz 1, 115V~,60Hz 1, 115V~,60Hz 1, 115V~,60Hz 1, 115V~,60Hz
Capacity
Btu/h 900090001200012000
Input W 78078010901090
Rated current A 7.3 7.3 10 10
EER Btu/w.h 13 13 13 13
Capacity Btu/h / 10000 / 12500
Input W / 810 / 1060
Rated current A / 7.6 / 10
COP Btu/w.h / 7.7 / 7.7
W1350135017001700
A13.6 13.6 17.2 17.2
A 40 40 47 47
Model EA82×1C-1FZDU1 EA82X1C-1FZDU1 EA108×1C-1FZDU1 EA108×1C-1FZDU1
Type ROTARY ROTARY ROTARY ROTARY
Brand GD TOSHIBA GD TOSHIBA GD TOSHIBA GD TOSHIBA
Capacity Btu/h 814081401091810918
Input W 81081010851085
Rated current(RL
A)
A 7.5 7.5 9.9 9.9
Locked rotor Amp(
LRA)
A 40 40 47 47
Thermal protector B350-135-141E B350-135-141E B440-135-141E B440-135-141E
Capacitor μF45μF /250VAC 45μF /250VAC 45μF /250VAC 45μF /250VAC
Refrigerant oil ml 350350350350
Model WZDK20-38D WZDK20-38D WZDK25-38D WZDK25-38D
Brand Welling Welling Welling Welling
Input W 25 25 32 32
Capacitor μF —— —— —— ——
Speed(hi/mi/lo) r/min 1250/1000/8001250/1000/8001270/1100/10001270/1100/1000
m3/h
580/500/420
580/500/420800/730/600800/730/600
dB(A) 40/34/27 40/34/27 44/40/36 44/40/36
Model YDK23-6A YDK23-6A YDK23-6A YDK23-6A
Brand DY DY DY DY
Input W 77 77 77 77
Capacitor μF 6μF/250V 6μF/250V 6μF/250V 6μF/250V
Speed r/min 880880880880
m3/h 1800180018501850
dB(A) 53 53 55 55
g R410A/1050 R410A/1070 R410A/1330 R410A/1350
MPa 4.5 4.5 4.5 4.5
Liquid side/ Gas s
ide
mm(inch) Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф12.7 Ф6.35/Ф12.7
m 10 10 10 10
m 5 5 5 5
℃17-3017-3017-3017-30
℃18-45-7-4518-45-7-45
m2 14~20 14~20 18~26 18~26
Ambient temp
Application area
Outdoor fan
motor
Outdoor noise level
Refrigerant
piping
Operation temp
Model
Power supply
Cooling
Heating
Max. input consumption
Max. current
Starting current
Design pressure
Refrigerant type
Outdoor air flow
Compressor
Indoor fan
motor
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
CIC-09M1Z CIH-09M1Z CIC-12M1Z CIH-12M1Z
Max Pipe Length
Max Vertical Rise
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are
normally somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product
improvement.
Service manual
- 8 -
Ph-V-Hz 1, 208-230V~, 60Hz 1, 208-230V~, 60Hz 1, 208-230V~, 60Hz 1, 208-230V~, 60Hz
Capacity
Btu/h 12000120001800018000
Input W 1070107015501550
Rated current A 4.75 4.75 6.8 6.8
EER Btu/w.h 13 13 13 13
Capacity Btu/h / 12500 / 18000
Input W / 1060 / 1600
Rated current A / 4.7 / 7
COP Btu/w.h / 7.7 / 7.7
W1550155025502550
A 7.8 7.8 12.7 12.7
A23.5 23.5 32.6 32.6
Model PA108×1C-3FZDU PA108×1C-3FZDU PA150×2CS-3KUU PA150×2CS-3KUU
Type ROTARY ROTARY ROTARY ROTARY
Brand GD TOSHIBA GD TOSHIBA GD TOSHIBA GD TOSHIBA
Capacity Btu/h 10850/1100010850/1100015166/1535415166/15354
Input W 1070/10751070/10751505/15101505/1510
Rated current(RLA
)
A 5.2/4.8 5.2/4.8 7.30/6.65 7.30/6.65
Locked rotor Amp(
LRA)
A23.5 21/23.5 32.6 32.6
Thermal protector B185-135-141C B185-135-141C UP3RE0391-T39 UP3RE0391-T39
Capacitor μF35μF /370VAC 35μF /370VAC 40μF /370VAC 40μF /370VAC
Refrigerant oil ml 350350750750
Model WZDK25-38D WZDK25-38DYDK36-4CB YDK36-4CB
Brand Welling Welling Welling Welling
Input W 32 32 85/81/72/61 85/81/72/61
Capacitor μF —— —— 3.0μF/450V 3.0μF/450V
Speed(hi/mi/lo) r/min 1270/1100/10001270/1100/10001285/1235/1145/10451285/1235/1145/1045
m3/h 800/730/600800/730/6001150/1080/1020/9601150/1080/1020/960
dB(A) 44/40/36 44/40/36 50/47/44 50/47/44
Model YDK36-6B YDK36-6B YDK53-6KB YDK53-6KB
Brand Welling Welling Welling Welling
Input W 85 85 172172
Capacitor μF 2.5μF/450V 2.5μF/450V 3μF/450V 3μF/450V
Speed r/min 930930840840
m3/h 1900190025002500
dB(A) 55 55 58 58
g R410A/1330 R410A/1350 R410A/2000 R410A/2040
MPa 4.5 4.5 4.5 4.5
Liquid side/ Gas s
ide
mm(inch) Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7
Max. refrigerant p
ipe length
m 10 10 15 15
Max. difference in
level
m 5 5 8 8
℃17-3017-3017-3017-30
℃18-45-7-4518-45-7-45
m2 18~26 18~26 26~40 26~40
Ambient temp
Application area
Outdoor fan
motor
Outdoor noise level
Refrigerant
piping
Operation temp
Model
Power supply
Cooling
Heating
Max. input consumption
Max. current
Starting current
Design pressure
Refrigerant type
Outdoor air flow
Compressor
Indoor fan
motor
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are
normally somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product
improvement.
CIC-12M2Z CIH-12M2Z CIC-18M2Z CIH-18M2Z
Service manual
- 9 -
Ph-V-Hz 1, 208/230V~, 60Hz 1, 208/230V~, 60Hz
Capacity Btu/h 2400024000
Input W 20002000
Rated current A 8.8 8.8
SEER Btu/w.h 13 13
Capacity Btu/h / 24000
Input W / 2000
Rated current A / 8.8
HSPF W/W / 7.7
A31903190
A16.5 16.5
Model 34.8 A 34.8 A
Type PA200X2CS-3MUU PA200X2CS-3MUU
Brand Rotary Rotary
Capacity Btu/h GD TOSHIBA GD TOSHIBA
Input W 19824/2013019824/20130
Rated current(RLA) A 2000/1980 2000/1980
Locked rotor Amp(LRA) A 9.70/8.75 9.70/8.75
Thermal protector 34.8 34.8
Capacitor uF UP3SE0396-T39 UP3SE0396-T39
Refrigerant oil ml 50μF /370VAC50μF /370VAC
Model 750750
Brand YDK50-4B YDK50-4B
Input W Welling Welling
Capacitor uF 86/69/58 86/69/58
Speed(hi/mi/lo) r/min 3μF/450V 3μF/450V
m3/h 1260/1100/9901260/1100/990
dB(A) 1350/1200/10901350/1200/1090
Model 52/48/45 52/48/45
Brand YDK100-6EB YDK100-6EB
Input W Welling Welling
Capacitor uF 140140
Speed r/min 4μF/450V 4μF/450V
m
3
/h
760760
dB(A) 25002500
g 59 59
MPa R410A/2400 R410A/2450
Liquid side/ Gas side mm 4.5 4.5
Max. refrigerant pipe length m Ф9.53/Ф16 Ф9.53/Ф16
Max. difference in level m 20 20
℃10 10
℃17-3017-30
m
2
18-45-7-45
Model
Power supply
Cooling
Heating
Max. current
Starting current
Compressor
Indoor
fan motor
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo)
Outdoor
fan motor
Outdoor air flow
Operation temp
Ambient temp
Application area
Outdoor noise level
Refrigerant type R410A
Design pressure
Refrigerant
piping
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are
normally somewhat different as a result of ambient condition.
The above design and specifications are subject to change without prior notice for product
improvement.
CIC-24M2Z CIH-24M2Z
Service manual
- 10 -
5 Refrigerant cycle diagram
 Cooling only
 Heat pump mode
Service manual
- 11 -
6 Operation limits
Cooling operation
Outdoor unit air temp.℃ DB
Indoor air temp. ℃ DB
Note: The chart is the result from the continuous operation under constant air temperature
conditions. However, excludes the initial pull-down stage.
Heating operation
Indoor air temp. ℃ DB
Outdoor unit air temp.℃ DB
Note: The chart is the result from the continuous operation under constant air temperature
conditions. However, excludes the initial pull-down stage.
Service manual
- 12 -
7 Wiring diagram
Indoor unit:
outdoor unit:
COMP
CA P1
1
2
MFAN2
RED RED
XT1
1
2
C
SR
2
N
L 1 4
3
WIRING DIAGRAM
(OUTDOOR UNIT)
CODE
COMP
CAP1
FAN2
CAP2
XTI
CT1
RELAY
PAR T NAME
COMPRE SSOR
COMPRE SSOR CAP ACITOR
OUTDOO R FAN
OUTDOO R FAN CA PACITOR
7-WAY TERMINAL
CURREN T INDUCT OR
COMPRE SSOR REL AY
CN 2
CN 3
CN4
CN 1 0
CN 9
BR OW N
BL UE
BL AC K
RE D
R E LA Y
WHITE
BLACK
Y/G
WH ITE
WH ITE
RE DRE D
BLACK
BL UE WHITE
Y/G
POWER SUPPLY
TO INDOOR UNIT
P1 P2
N
N
L
Y/G
Y/G
CAP2
G
G
G
CT 1
G
CIC-09M1Z
Service manual
- 13 -
Indoor unit:
outdoor unit:
COMP
CAP1
M
F AN2
RED
RED
XT 1
C
SR
WIRING DIAGRAM
(OUTDOOR UNIT)
CO DE
CO MP
CA P1
FA N2
CA P2
XT I
CT 1
RE LAY
VA LVE
FS 1,FS2
PART NAME
COMPRES SOR
COMPRESSOR CA PACITO R
OUTDOOR FAN
OUTDOOR FAN C APACIT OR
7-WAY TERMINA L
CURRENT INDUC TOR
COMPRESSOR RE LAY
FUSE
REVERSING VAL VE
CN2
C N3
CN4
CN10
CN6
CT 1
BR OWN
BLU E
BLA CK
RED
R EL AY
WHIT E
BLAC K
Y/G
WHITE
RE D
BLACK
BLUEWHI TE
Y/G
POWER SUPPLY
TO INDOOR UNIT
P1 P 2
N
N
L
CN5
BLAC K
( OR )BLUE
FS2
FS1
VALVE
CA P2
WHITE
G
G
G
G
Y/G
Y/G
CN1
CONDEN SATOR
SENSOR
B LACK
( OR )BLU E
CIH-09M1Z
Service manual
- 14 -
Indoor unit:
outdoor unit:
COMP
CA P1
1
2
MFAN2
RED RED
XT1
1
2
C
SR
2
N
L 1 4
3
WIRING DIAGRAM
(OUTDOOR UNIT)
CODE
COMP
CAP1
FAN2
CAP2
XTI
CT1
RELAY
PAR T NAME
COMPRE SSOR
COMPRE SSOR CAP ACITOR
OUTDOO R FAN
OUTDOO R FAN CA PACITOR
7-WAY TERMINAL
CURREN T INDUCT OR
COMPRE SSOR REL AY
CN 2
CN 3
CN4
CN 1 0
CN 9
BR OW N
BL UE
BL AC K
RE D
R E LA Y
WHITE
BLACK
Y/G
WH ITE
WH ITE
RE DRE D
BLACK
BL UE WHITE
Y/G
POWER SUPPLY
TO INDOOR UNIT
P1 P2
N
N
L
Y/G
Y/G
CAP2
G
G
G
CT 1
G
CIC-12M1Z
Service manual
- 15 -
Indoor unit:
outdoor unit:
COMP
CAP1
M
F AN2
RED
RED
XT 1
C
SR
WIRING DIAGRAM
(OUTDOOR UNIT)
CO DE
CO MP
CA P1
FA N2
CA P2
XT I
CT 1
RE LAY
VA LVE
FS 1,FS2
PART NAME
COMPRES SOR
COMPRESSOR CA PACITO R
OUTDOOR FAN
OUTDOOR FAN C APACIT OR
7-WAY TERMINA L
CURRENT INDUC TOR
COMPRESSOR RE LAY
FUSE
REVERSING VAL VE
CN2
C N3
CN4
CN10
CN6
CT 1
BROWN
BLU E
BLA C K
RED
R EL AY
WHIT E
BLAC K
Y/G
WHITE
RE D
BLACK
BLUEWHI TE
Y/G
POWER SUPPLY
TO INDOOR UNIT
P1 P 2
N
N
L
CN5
BLAC K
( OR )BLUE
FS2
FS1
VALVE
CA P2
WHITE
G
G
G
G
Y/G
Y/G
CN1
CONDEN SATOR
SENSOR
B LACK
( OR )BLU E
CIH-12M1Z
Service manual
- 16 -
Indoor unit:
Outdoor unit
COMP
CA P1
1
2
M
FAN2
RED
XT1
1
2
C
SR
2
N
L 1 4
3
WIRING DIAGRAM
(OUTDOOR UNIT)
CODE
COMP
CAP1
FAN2
CAP2
XTI
CT1
RELAY
PAR T NAME
COMPRE SSOR
COMPRE SSOR CAP ACITOR
OUTDOO R FAN
OUTDOO R FAN CA PACITOR
7-WAY TERMINAL
CURREN T INDUCT OR
COMPRE SSOR REL AY
CN 2
CN 3
CN4
CN 1 0
CN 9
BR OW N
BL UE
BL AC K
RE D
R E LA Y
WHITE
BLACK
Y/G
WH ITE
WHITE
RE DRE D
BLACK
WHITE
BL UE
Y/G
POWER SUPPLY
TO INDOOR UNIT
P1 P2
N
N
L
Y/G
Y/G
CAP2
BLUE
G
G
G
G
CT1
CIC-12M2Z
Service manual
- 17 -
Indoor unit:
Outdoor unit
COMP
CA P1
M
F AN2
RED
BLUE
X T1
C
S
R
WIRING DIAGRAM
(OUTDOOR UNIT)
CO DE
CO MP
CA P1
FA N2
CA P2
XT I
CT 1
RE LAY
VA LVE
FS 1,FS2
PAR T NAME
COMPRE SSOR
COMPRE SSOR CAPACITO R
OUTDOO R FAN
OUTDOO R FAN CAPACIT OR
7-WAY TERMINAL
CURREN T INDUCTOR
COMPRE SSOR RELAY
FUSE
REVERS ING VALVE
CN2
CN 3
C N4
CN10
C N6
BROWN
BLUE
B LA CK
R ED
R ELAY
WHI TE
BLA CK
Y/G
WHITE
RE DRE D
BLACK
BLU E WHI TE
Y/G
POWER SUPPLY
TO INDOOR UNIT
P1 P2
N
N
L
CN5
BL UE
B LUE
FS2
F S1
VALVE
CA P2
WHITE
G
G
G
G
Y/ G
Y/ G
CONDEN SATOR
SENSOR
CN1
CT1
CIH-12M2Z
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51

Coaire CIC-24M2Z User manual

Category
Split-system air conditioners
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI