  • Hello! I am an AI chatbot trained to assist you with the Lennox GFI Kit for LG/LC/LH/TG/TC/TH/KG/KC/KH Units Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
505,165M
*P505165M*
10/12
*2P1012* Page 1
INSTALLATION INSTRUCTIONS FOR GFI KIT (LB−101063A, C & D; 31M77, 74M70 & 67E01)
USED ON PACKAGED LG/LC/LH/TG/TC/TH/KG/KC/KH SERIES UNITS
Litho U.S.A.
505,165M
10/2012
Supersedes 1/2008
E20012
GFI RECEPTACLE KIT
PACKAGED UNITS KITS
AND ACCESSORIES
Shipping and Packing List
LB−101063A; 31M77
Package 1 of 1 contains:
1− GFI Receptacle J117
1− Receptacle flip−cover
1− Handy box
1− Bag assembly containing:
4−#6−16 X 1/2 TFS Screws
2−#6−32 X 1/2 TFS Screws
LB−101063C & D; 74M70 & 67E01
Package 1 of 1 contains:
1− GFI Receptacle J117
1− Handy box
1− L Bracket
1− Bag assembly containing:
4−#10−32 X 1/2 TFS Screws
Application
The GFI Kit is used as follows:
31M77 LG/LC/LH 036−072
74M70 & 67E01 LG/LC/LH 090−360 and
TG/TC/TH/KG/KC/KH 024−300S
WARNING
Improper installation, adjustment, alteration, ser-
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser-
vice must be performed by a qualified installer, ser-
vice agency or the gas supplier
CAUTION
Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.
Installation
1− Disconnect all power to unit.
2− A Box LG/LC/LH 036−072 Units −
Remove and discard lower patch plate on mullion to
the left of the compressor section.
A Box TG/TC/TH/KG/KC/KH 024−072 Units −
Open or remove compressor access panel.
B Through D Box 090−360 Units −
Open or remove compressor access panel.
3− B Box 090−150 Units − NO Wiring Make−Up Box −
Use L−Bracket to mark and drill holes on unit mullion
as shown in figure 1. Install L−Bracket on inside of
mullion. Secure bracket from outside of unit.
4− C Box 156−300S Units − NO Wiring Make−Up Box −
Use L−Bracket to mark and drill holes on unit mullion
as shown in figure 2. Install L−Bracket on inside of
mullion. Secure bracket from outside of unit.
Note − Discard L−bracket when unit has a wiring make−up
box or when installing TG/TC/TH/KG/KC/KH 024−072 units.
B BOX UNITS (090 THROUGH 150)
NO WIRING MAKE−UP BOX
FIGURE 1
SEAL
WATERTIGHT
ROUTE WIR-
ING IN FIELD
PROVIDED
CONDUIT
GFI IN
HANDY
BOX
29"
(737mm)
L−BRACKET
Page 2
C BOX UNITS (156 THROUGH 300S)
NO WIRING MAKE−UP BOX
FIGURE 2
SEAL
WATERTIGHT
ROUTE WIR-
ING IN FIELD
PROVIDED
CONDUIT
GFI IN
HANDY
BOX
10"
(254mm) L−BRACKET
5− Install handy box in location as follows:
Figure 3 LG/LC/LH A Box units
Figure 4 TG/TC/TH/KG/KC/KH A Box units
Figure 5 B Box units with wiring make−up box
Figure 1 B Box units NO wiring make−up box
Figure 6 C Box units with wiring make−up box
facing the front of unit
Figure 2 C Box units NO wiring make−up box
Figure 7 C and D Box units with wiring make−up
box facing the side of the unit.
Note − Use #6 screws to secure handy box to LG/LC/LH
036−072 units and #10 screws to secure handy box in all
other units.
6− Route field−provided wiring through conduit and
appropriate knock−out in handy box. Connect wires to
terminals on back of GFI receptacle according to
wiring diagram on unit and local codes.
7− Secure GFI receptacle to handy box with 2 screws
provided with receptacle.
8− LG/LC/LH A box Units −
Install receptacle flip−cover over GFI receptacle on
outside of unit. Secure with 4 #6 screws.
LG/LC/LH/TG/TC/TH/KG/KC/KH A, B, C, & D Box
Units −
Install GFI faceplate on receptacle; screws and
faceplate are packaged with the receptacle.
FIGURE 3
SEAL
WATERTIGHT
LG/LC/LH A BOX UNITS (036 − 072)
GFI RECEPTACLE
ROUTE WIRING IN FIELD−
PROVIDED CONDUIT
HANDY BOX
INSTALL HANDY BOX
ON INSIDE OF UNIT;
SECURE FROM OUTSIDE
TG/TC/TH/KG/KC/KH A BOX UNITS (024−072)
FIGURE 4
ROUTE WIRING IN FIELD−
PROVIDED CONDUIT
GFI IN
HANDY BOX
SEAL
WATERTIGHT
Page 3
B BOX UNITS (090 THROUGH 150)
WITH WIRING MAKE−UP BOX
FIGURE 5
SEAL
WATERTIGHT
ROUTE WIR-
ING IN FIELD
PROVIDED
CONDUIT
GFI IN
HANDY
BOX
C BOX UNITS (156 THROUGH 300S)
WITH WIRING MAKE−UP BOX FACING UNIT FRONT
FIGURE 6
ROUTE WIRING IN FIELD
PROVIDED CONDUIT
SEAL
WATERTIGHT
GFI
C AND D BOX UNITS (156 THROUGH 360)
WITH WIRING MAKE−UP BOX FACING UNIT SIDE
FIGURE 7
SEAL
WATERTIGHT
RUN FIELD WIR-
ING IN FIELD
PROVIDED
CONDUIT
GFI IN
HANDY
BOX
/